Stanley PS161-6 User manual

02140-11-E Copyright©Stanley Security, Inc. 2014
1/9
PS161-6 Power Supply
Installation Instructions
Overview: PS161-6 converts a 120VAC / 60Hz input, to a 12VDC or 24VDC nominal output. PS161-6 comes with a power-limited power
distribution module with 8 outputs. Class 1 wiring methods and separation of circuits must be considered when connecting DC power supply to the
Delayed Egress hardware.
UL Listings for US Installations:
UL 294 - UL Listed for Access Control System Units.
UL 603 - UL Listed for Power Supplies for Use with Burglar-Alarms Systems.
UL 1481 - UL Listed for Power Supplies for Fire Protective Signaling Systems.
UL Listings for Canadian Installations:
ULC-S318-96 - Power Supplies for Burglar Alarm Systems. Also suitable for Access Control.
Altronix Corp.
140 58th St. Brooklyn, NY
California State Fire Marshal
European Conformity
Specifications:
Input:
Voltage: 120V AC, 60HZ
Current: 3.5A AC
Input fuse ratings:5A/250V
Battery fuse ratings: 7.5A/32V
Output:
Voltage: 20.0-26.4V
Total output: 6 amps
Power limit/output: 2 amps/per channel
Outputs: 8 (For Delayed Egress applications: use only 4)
Ripple voltage: 910mV (Filtered and regulated outputs)
Protection: Thermal and short circuit protection with auto reset overload protection.
Battery Backup
Built-in charger for sealed lead acid or gel type batteries
Maximum charge current 1.54 amp
Automatic switch over to stand-by is instantaneous with no interruption
Enclosure Dimensions: 12.5” x 13” x 3.25” (3.18mm x 330.2mm x 82.55mm)
Fire Alarm Disconnect:
Supervised Fire Alarm disconnect (latching or non-latching) 10K EOL resistor. Operates on a normally open (NO) or normally closed (NC) trigger.
Supervision
AC fail supervision (form “C” contacts).
Visual Indicators
Green AC Power LED indicates 120VAC present.
Additional Features
Short circuit and overload protection.
Unit is complete with power supply, enclosure, battery leads and cam lock.
Enclosure Dimensions
12.5” x 13” x 3.25” (318mm x 330.2mm x 82.55mm)

02140-11-E Copyright©Stanley Security, Inc. 2014
2/9
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, The Canadian Electrical Code, Part 1 and with all
local codes and authorities having jurisdiction. The product must be located indoors within the protected premises.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two
upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws,
level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place
the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure
Dimensions, pg. 8).
2. Secure enclosure to earth ground.
3. Set the DC output voltage to 24DC by setting SW1 to the open position on the power supply board (Figure 2-1a).
4. Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, N] (Figure 1). Use 18 AWG for all power connections and 18 AWG
to 22 AWG for power limited circuits (AC Fail/Low Battery reporting). Secure green wire lead to earth ground. Keep power-limited wiring
separate from non power-limited wiring (120VAC 60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided.
5. Measure output voltage before connecting devices. This helps avoid potential damage.
6. Connect the delayed egress exit device locking hardware positive leads to terminals marked 1 through 4 POS (+) on the PD8ULCB board
and negative leads to the NEG 1 terminals through 4 terminals.
Figure 1 - Wiring Diagram for Connecting DE Exit Devices to a PS161-6 Power Supply
Note A 10k EOL (End of Line) Resistor must be installed across terminals marked (Trigger EOL Supervised) on the PS161-6 board or the
unit will remain in fire alarm condition.
7. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage.
Batteries must be lead acid or gel type if used. Use two 12VDC batteries connected in series for 24VDC operation (Battery leads included).
8. Connect battery to terminals marked [-- BAT + ] (Figure 2 - 1g). Use two (2) 12VDC batteries connected in series for 24VDC operation
(battery leads included). Use batteries - Casil CL1270 (12V/7AH), CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH)
batteries or UL recognized BAZR2 batteries of an appropriate rating.
9. To trigger the power supply from a re alarm control panel (FACP), connect signaling circuit of FACP to terminals marked Trigger End of
Line Supervised.
10. To delay AC reporting for 2 hrs. set dip switch [AC Delay] to OFF position (Figure 2 - 1c).
11. To delay AC reporting for 1 min. set dip switch [AC Delay] to ON position (Figure 2 - 1c).
Note Must be set to ON position for Burglar Alarm Applications.
Delayed Egress
Exit Device #1
Delayed Egress
Exit Device #2
Delayed Egress
Exit Device #3
Delayed Egress
Exit Device #4
L
G
N
NC
C
NO
NC
C
NO
BAT
FAIL AC FAIL
--- DC +
AC
DC
--- BAT +
–AUX + TRIGGER EOL
SUPERVISED
5A 250V
RESET
GND NO
Disable
Enable
2 hr.
1 min.
AC DELAY
SHUTDOWN
O
N
N
COMMON POWER OUTPUTS
P
FUSED POWER OUTPUTS
1 2 3 4 5 6 7 8
D1
INPUT
R1 LED
Divider
DC Output to Devices
(1P-8P Power Outputs)
(1N-8N Common Outputs)
AC1
Battery & AC
Supervision Circuit
(Power-limited)
Potentiometer
Power-limited
Green Lead
(Ground)
120VAC Power Mains
(Non Power-limited)
From Power Supply Board
(Factory Installed)
Open - 24V
Closed - 12V
Switch Detail
Closed - 12V
Open - 24V
Battery
Connections
(Non
Power-limited) 12VDC Rechargeable
Battery
+–
12VDC Rechargeable
Battery
+–
No Fire
Connections
N.O. Input
from
Fire Panel
N.C. Input
from
Fire Panel
OR OR
10K EOL
10K EOL
10K EOL
Separation of power-
limited wiring from
non power-limited
wiring must be at
least 1/4 inch.
Power must be
turned off
before changing
the voltage
select switch.

02140-11-E Copyright©Stanley Security, Inc. 2014
3/9
12. To enable Low Output Power Shutdown set dip switch [Shutdown] to ON position (Figure 2 - 1c).
13. To disable Low Output Power Shutdown set dip switch Shutdown] to OFF position (Figure 2 - 1c).
14. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals will cause [DC] output to
shutdown (Figure 2 - 1d).
15. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching [Trigger EOL Shutdown] (Figure 2 - 1e).
16. For Access Control Applications: mount UL Listed tamper switch (Sentrol model 3012 or equivalent) at the top of the enclosure. Slide
tamper switch bracket onto the edge or the enclosure approx. 2” from the right side (Figure 4 or Figure 5). Connect tamper switch wiring
to the Access Control Panel input or the appropriate UL Listed reporting device.
Wiring:
Use 18 AWG or larger for all low voltage power connections.
Note Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level PS161-6: 24VDC nominal
rated @ 6 amp max.
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage (24VDC @ 26.4) both at the battery
terminal and at the board terminals marked [-- BAT + ] to ensure that there is no break in the battery connection wires.
Note Maximum charging current under discharges is 1.54 amp.
Note Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.
LED Diagnostics:
Power Supply/Charger
Red (DC) Green (AC/AC1) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC, Stand-by battery supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Power Distribution Module
Green (AC) Power Distribution Module Status
ON Normal operating condition.
OFF No Power Output.
Terminal Identification:
Power Supply/Charger
Terminal Legend Function/Description
L, N Connect 120VAC 60Hz to these terminals: L to hot, N to neutral (non power-limited) (Figure 2 - 1a).
– DC + 12VDC or 24VDC nominal @ 6 amp continuous output (non power-limited output) (Figure 2 - 1h).
Trigger EOL
Supervised
Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open, normally closed from an FACP
output circuit (power-limited input) (Figure 2 - 1d).
NO, GND
RESET FACP interface latching or non-latching (power-limited) (Figure 2 - 1e).
+ AUX – Auxiliary Power-Limited output rated @ 1 amp (unswitched) (power-limited output) (Figure 2 - 1f).
AC Fail
NC, C, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is
present. Contact rating 1 amp @ 30VDC (power-limited) (Fig. 1b).

02140-11-E Copyright©Stanley Security, Inc. 2014
4/9
Bat Fail
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power
is present. Contact rating 1 amp @ 30VDC. A removed battery is reported within 5 minutes.
Battery reconnection is reported within 1 minute (power-limited) (Figure 2 - 1b).
– BAT + Stand-by battery connections. Maximum charge current 1.54 amp (non power-limited) (Figure 2 - 1g).
Terminal Identification:
Power Distribution Module
Terminal Legend Function/Description
1P to 8P Positive DC power outputs
1N to 8N Negative DC power outputs
Figure 2 - PS161-6 Board configuration
Trouble/Time Limited Warning of Stand-by Batteries:
For compliance with ULC S318-96, the Time Limited Warning circuit must be connected for local or remote annunciation with an Amber or Red LED
to indicate DC Trouble (low battery, loss of battery or when 95% of the stand-by battery has been depleted). Connect the circuit to the Batt Fail
relay contacts to an appropriate input of a UL Listed Burglar Alarm or Access Control Panel. The following figure shows the circuitry needed for local
annunciation.
LGNNC C NO NC C NO
BAT FAILAC FAIL
--- DC +
AC
AC1
DC
--- BAT +
+ AUX –
enable
disable
1 min.
2 hr.
AC DELAY SHUTDOWN
TRIGGER EOL
SUPERVISED
NO GND
RESET
OPEN --- 24V
CLOSED --- 12V
O
N
5A 250V
1a 1b
1g
1h
1e 1f1d1c
1i

02140-11-E Copyright©Stanley Security, Inc. 2014
5/9
Figure 3 - Battery trouble indication
For Canadian use, a red indicating lamp must be visible from the exterior of this enclosure. Wire one leg of a UL Listed, power-limited power source to the
indicating lamp. Wire the second leg of the power source to the indicating lamp in series with the battery fail relay contact terminals marked [BAT FAIL - C,
NO].
Power Distribution Module:
Figure 4 - PD8ULCB - Power Distribution Board
Power-Limited Outputs
NC C NO NC C NO
BAT FAILAC FAIL
POWER
SOURCE
RED INDICA
TING
LAMP
N
COMMON POWER OUTPUTS
P
FUSED POWER OUTPUTS
1 2 3 4 5 6 7 8
D1
INPUT
R1 LED
From Power Supply
Board
(Factory Installed)
DC Output to devices
1P-8P Power Outputs,
1N-8N Common Outputs
()

02140-11-E Copyright©Stanley Security, Inc. 2014
6/9
Figure 5
L
G
N
NC
C
NO
NC
C
NO
BAT FAIL AC FAIL
--- DC +
AC
AC1
DC
--- BAT +
– AUX +TRIGGER EOL
SUPERVISED
5A 250V
RESET
GND NO
OPEN --- 24V
CLOSED --- 12V
disable
enable
2 hr.
1 min.
AC DELAY
SHUTDOWN
O
N
Door
Wire
Strap
(from
Enclosure
to Door)
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
7AH Rechargeable batteries are the largest batteries that can t in this enclosure.
Green
Lead
(ground)
Power-
limited
120VAC
power mains
Non Power-
limited
Battery & AC
Supervision
Circuit
(Power-limited)
Battery
Connections
(Non
Power-limited)
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries required for UL603,
UL1481 and Canadian installations.
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries required for UL603,
UL1481 and Canadian installations.
DC Output to devices*
(refer to Fig. 3a, 3b, 4a or 4b
for board conguration pg. 6)
PD8UL/PD8ULCB PD16W/
PD16WCB
OPEN 24V
CLOSED 12V
Switch Detail
Edge of
Enclosure
to Access Control
Panel or
U.L. Listed
Reporting
Device
Enclosure
Sentrol
model # 3012
Tamper Switch
or equivalent
(Not Included)

02140-11-E Copyright©Stanley Security, Inc. 2014
7/9
NEC Power-Limited Wiring Requirements:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least
0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter
and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit
knockouts to be used. Any conduit knockouts may be used. For power-limited applications, use of conduit is optional. All field wiring connections
must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional UL Listed battery enclosure must be mounted
adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections.
Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire, (Figure 5).
Figure 5
External
Jacketed
Shield
Incorrect Wire
Handling Correct Wire
Handling
Pull back
external jacketed
shield approx. 1/2”.
Wire
Insulation
Solid Copper
Conductors
Figure 6

02140-11-E Copyright©Stanley Security, Inc. 2014
8/9
Enclosure Dimensions:
12.5” x 13” x 3.25” (318mm x 330.2mm x 82.55mm)
Figure 7 - Power Supply Enclosure Template
1.40”
(36mm)
0.75” (19mm)
0.94”
(24mm)
1.40”
(36mm)
1.20”
(31mm)
1.20”
(31mm)
3.25”
(83mm)
3.25”
(83mm)
3.25”
(83mm)
5.10”
(130mm)
5.10”
(130mm)
4.85”
(123mm)
11.0” (279mm)
12.5” (318mm)
4.85”
(123mm)
1.20”
(31mm)
1.40”
(36mm)
5.10”
(130mm)
6.57”
(167mm)
1.40”
(36mm)
1.0”
(25mm)
10.5”
(267mm)
1.0”
(25mm)
1.0”
(25mm)
13.0” (330mm)
1.0 (25mm)
3.25 (83mm)
Edge of Enclosure
Enclosure
Sentrol Model
# 3012 Tamper
Switch or equivalent
(Not Included)
To Access Control
Panel or U.L.
Listed Reporting
Device
0.75” (19mm)
0.94”
(24mm)
Notes
1 Separation of power limited
wiring from non-power limited
wiring must be at least 1/4 inch.
2 Power must be turned off before
changing the voltage select
switch.

02140-11-E Copyright©Stanley Security, Inc. 2014
9/9
Appendix A - UL Listed Compatible Devices
A.1 Four (4) Wire Smoke Detectors
Table A-1 below lists four (4) wire smoke detectors compatible with PS161-6 output.
System Sensor
Smoke Detector/Base Detector Type Max Stand-by
Current (mA)
Alarm Current
(mA)
B112LP Base 0.12 36
DH100ACDC Photoelectric 0.15 0.70
DH100ACDCLP Photoelectric 0.15 0.70
DH100ACDCLPW Photoelectric 0.15 0.70
DH400ACDCI Ionization Duct 25 95
DH400ACDCP Photoelectric Duct 25 95
1112/24/D Ionization 0.05 50
1424 Ionization 0.10 41
1451 (w/B402B Base) Ionization 0.10 39
2112/24ATR Photoelectric 0.50 60/70
2112/24AITR Photoelectric 0.50 60/70
2112/24/D Photoelectric 0.05 50
2112/24T/D Photoelectric w/135o Thermal 0.05 50
2112/24TSRB Photoelectric w/135o Thermal Supervisory Relay 15 45
2312/24TB Photoelectric 0.12 50
2412 (12 volt) Photoelectric 0.12 77
2424 Photoelectric 0.10 41
2451 Photoelectric 0.10 39
2451TH (with/B402B Base) Photoelectric 0.10 39
2W-MOD Loop Test/Maintenance Mod. 30 50
4W-B (12/24 volt) Photoelectric I3 .05 23
4WT-B (12/24 volt) Photoelectric I3 w/Therm .05 23
4WTA-B (12/24 volt) I3 Photo w/Therm/Sounder .05 35
4WTR-B (12/24 volt) I3 Photo w/Therm/Relay .05 35
4WITAR-B (12/24 volt) I3 Photo w/Isolated Therm/Sounder/Relay .05 50
6424 Projected Beam 10 28.4
Beam 1224(S) Projected Beam 17 38.5
A.2 Relays
Table A-2 below lists relays compatible with PS161-6 output.
Manufacturer Model Current (mA) Manufacturer
System Sensor EOLR-1 30 System Sensor
For assistance or warranty information:
Call 1-855-365-2407 or visit
www.stanleysecurity.com/precision
Warning: This Manufacturer advises that no lock can provide complete security by itself. This lock may be defeated by forcible or technical means,
or evaded by entry elsewhere on the property. No lock can substitute for caution, awareness of your environment, and common sense. Builder’s
hardware is available in multiple performance grades to suit the application. In order to enhance security and reduce risk, you should consult a
qualified locksmith or other security professional.
Table of contents
Other Stanley Power Supply manuals
Popular Power Supply manuals by other brands

turck
turck PSU67-3P-1H2-1H0-24250 quick start guide

Matsusada Precision
Matsusada Precision RE Series instruction manual

National Instruments
National Instruments RMX-4101 user manual

D-Link
D-Link DGS-6604-SK Quick installation guide

Altronix
Altronix ALTV2432UL Series installation guide

Master
Master PS12 quick start guide