-22 - - 23 -
Technical Specifications
DIP 4
In the'ON'-'OFF' setting,thelight
can be switched 'ON' and 'OFF'
manually at any time (exceptin
pulsemode: nomanual 'OFF').
In the'ON' setting,lightcan no
longer be switched 'OFF' manu-
ally.Thestay-'ON' time starts
from thebeginning again each
time thebutton is pressed.
'ON'/'ON'-'OFF' button
DIP 1
Functions – Settings by DIP switch
Testmodehas priority over all
other settings on thepresence
detector and serves thepurpose
of checking for proper working
order as well for testing thede-
tection zone. Irrespectiveof am-
bientlightlevel,thepresence
detector activates thelightto
stay 'ON' for approx. 8sec.in re-
sponseto movementin the
room (blueLED flashes when
movementis detected). All user-
selected potentiometer settings
apply in normal mode. Thepres-
encedetector can alsobe set by
means of theblueLED without
any load connected.
Normal mode / Test mode (NORM / TEST)
DIP 2
Thelightautomatically switches
'ON' and 'OFF' in relation to
brightness when someoneis
present. Lightcan be switched
'ON' and 'OFF manually at any
time. This temporarily interrupts
theautomatic switching func-
tion.Irrespectiveof thesettings
selected,lightstays 'ON' for 4
hours after manually pressing
thebutton twiceor switches
'OFF' after manually pressing the
button once. Pressing thebut-
ton before the4hours elapse
returns thePresenceControl IR
Quattro to thenormal operating
mode.
Semi-automatic mode (MAN) / fully automatic mode (AUTO)
Fully automatic mode: (AUTO)
Semi-automatic mode: (MAN)
Thelightnow only switches
'OFF' automatically.Lightis
switched 'ON' manually.Light
mustbe requested using the
button and stays 'ON' for the
time set at thepotentiometer.
(pressing twiceswitches 'ON' for
4hours).
DIP 3
Tells thesensor how to interpret
theincoming signal.Assigning
external buttons/switches allows
you to operate thedetector as a
semi-automatic unit and over-
rideit manually at any time.
■ Operation either by button
or switch
■ Several buttons possible
on onecontrol input
■ Only useilluminated push-
button with neutral conductor
connected
■ Cablelength between sensor
and switch < 50 m
Button/switch
COM 1 + COM 2
DIP 5
Provides aconstantlevel of
brightness.Detector measures
theprevailing level of daylight
and activates sufficientartificial
lightto achievetherequired lev-
el of brightness.As daylight
changes,theswitched-in artifi-
cial lighting componentis ad-
justed accordingly.In addition to
thedaylightcomponent, artificial
lightis alsoswitched 'ON' and
'OFF' in relation to whether or
not persons are present.
Constant light 'ON'/'OFF'
DIM
Dimensions
(w xh xd)
HF 360
120 x120 x56 mm Dual HF
120 x120 x76 mm
Supply voltage 230 – 240 V, 50 Hz /60Hz
Capacity,switching output 1
(COM 1/COM 2)
Relay 230 V
Resistiveload 2000 W max. (cos ϕ= 1)
1000 VA max. (cos ϕ = 0,5)
Electronic ballast:
(COM 1/COM 1AP/
COM 2/DIM)
Max. 'ON' current800 A/200 μs
30 x(1 x18 W), 25 x(2 x18 W)
25 x(1 x36 W), 15 x(2 x36 W)
20 x(1 x58 W), 10 x(2 x58 W)
Pay attention to specific 'ON' currents of electronic ballasts!
A relay or contactor mustbe provided on linesidefor higher switching
capacities.
Capacity,switching output 2
(COM 2only)(HF 360only)
Presence
230 W max. /230 V
1A max. (cos ϕ= 1) for HVAC(heating/ventilation/air-conditioning)
Applicationindoors
Mounting height
(mounted to ceiling)
2.5 m– 3.5 mceiling height
Detection angleHF 360
360° with 140° aperture angle
alsothrough glass,wood and
stud walls.1or 2detection direc-
tions can be masked outfor ad-
justmentto theroom situation.
Dual HF
see diagrams on p.20
alsothrough glass,wood and stud
walls
Reach HF 360
8mmax. all round,
electronically and infinitely
variable
Dual HF
10 x3mmax. in each direction,
electronically and infinitely
adjustable
Switching output 1
Time setting
30 sec.– 30 min., pulsemode(approx. 2sec.)
IQ mode(automatic adjustmentto useprofile)
Switching output 2
Time setting COM2 only for HVAC
0sec.– 10 min.switch-'ON' delay
1min.– 2h stay-'ON' time
Automatic room surveillance
DIM:
Time setting
30 sec.-30 min.
IQ mode(automatic adjustmentto useprofile)
Control output1– 10 V/max. of 50 electronic ballasts,max. of 100 mA
Sensor system High-frequency 5.8 GHz,transmission power < 1mW
Function setting by
DIP switches
DIP 1Normal /testmode
DIP 2Semi- /fully automatic mode
DIP 3Button /switch mode
DIP 4'ON' button /'ON'-'OFF' button
DIP 5Constant-lighting control 'ON'-'OFF' (DIM)
Parallel connections Master/slave
Master/master
User-friendly setting capabilityTeach-in (with optional remote control RC3)
Light-level setting 10 – 1000 lux, ∞ /daylight
DIM 100 – 1000 lux
IP rating IP 20 (IP 54 with surface-mounted box)
Safety class II
Temperature range0° to +40° C
Housing UV-resistant, paintable
PresenceControlPRO_HF360-Dual HF_DEU_ENG.indd 22-23PresenceControlPRO_HF360-Dual HF_DEU_ENG.indd 22-23 06.07.10 11:5406.07.10 11:54