
Installation (qualified contractors)
www.stiebel-eltron.com | 7
Heating circuit oxygen diffusion
NOTICE
Property damage
In underfloor heating systems with plastic pipes that
are permeable to oxygen and in open vented heating
systems, oxygen diffusion may lead to corrosion on
the steel components of the heating system (e.g. on
the indirect coil of the DHW cylinder, on buffer cylin-
ders, steel radiators or steel pipes).
uAvoid open vented heating systems and under-
floor heating systems with plastic pipes that are
permeable to oxygen.
NOTICE
Property damage
The products of corrosion (e.g. rusty sludge) can
settle in the heating system components, which may
result in a lower output or fault shutdowns due to re-
duced cross-sections.
Supply lines
The maximum permissible line length between the appliance
and the heat pump will vary, depending on the version of the
heating system (pressure drop). As a standard value, assume a
maximum line length of 10m and a pipe diameter of 22-28mm.
uProtect the flow and return lines against frost with sufficient
thermal insulation. The thermal insulation must be at least
twice as thick as the diameter of the pipe. Provide thermal
insulation in accordance with applicable regulations.
uAlso protect all supply lines against humidity, damage and
UV radiation by means of a conduit.
Pressure differential:
If the available external pressure difference is exceeded, the
pressure drop in the heating system could result in a reduced
heating output.
uWhen sizing the pipes, ensure that the available external
pressure differential is not exceeded (see chapter
Data table
[}13]
).
uWhen calculating the pressure drops, take account of the
flow and return lines and the pressure drop of the heat
pump. The pressure drop must be covered by the available
pressure differential.
7.5.1 Installing the heating water line
uUse suitable pipes.
uUse a suitable thread sealant.
uSeal off unused connection apertures.
uNOTICE:Foreign bodies, such as welding pearls, rust or
sealing material, can impair the operational reliability of
the appliance. Flush the pipework thoroughly before con-
necting the appliance.
uInstall suitable pipes at the connections for the radiator and
heat pump circuits (see chapter
Installation example
[}13]
).
7.6 Filling the system
NOTICE
uNever switch on the power before filling the sys-
tem.
uFirst fill the appliance's DHW cylinder, then the
buffer cylinder.
7.6.1 Filling the DHW cylinder
uCheck that all connections are seated correctly and not leak-
ing.
uOpen a DHW valve of the draw-off point that is furthest
away from the appliance.
uLeave the DHW valve open until the appliance is full and the
pipes are free of air and dirt.
uClose the DHW valve.
uTo remove residual air from the pipes, open all downstream
DHW valves.
uClose all DHW valves.
uCarry out a tightness check.
uTo open the T&P valve, turn it anti-clockwise.
uCheck that water can flow unimpeded through the drain
pipe to the drain.
uTo close the T&P valve, continue turning the rotary selector
anti-clockwise until the T&P valve closes.
7.6.2 Heating system
The heating system is filled with drinking water. To prevent
damage to the heating system, comply with the following limits.
Unit Value
Water hardness °dH ≤3
pH value 6.5-8.5
Chloride mg/l <30
You can find out the water hardness and the chlorine value in
the fill water from the local water supplier.
uObserve local requirements (e.g. VDI2035 in Germany).
We do not recommend desalinating the fill water, as this may
cause a negative change in the pH value.
uIf you desalinate the fill water or the pH value of the fill wa-
ter is less than 8.2, check the pH value 8 to 12weeks after
installation, every time the system is topped up and the next
time it is serviced.
uDo not add inhibitors or additives to the filling water.
Accessories for water softening
If you need to soften the fill water, you can use the following
product.
– Water softening device HZEA
– HZEN replacement cartridge
uRecheck these limits 8-12weeks after commissioning, every
time the system is topped up and during the annual service.
Appliance in low-occupancy buildings
During regular operation, the connection lines and the system
are protected by the frost protection function of the appliance.
en