TestProcedure
NemoMeterSet‐Up
ProcedureNo.:T18
Page3of4
Revision:1
Approved:F.Foley
Uncontrolledwhenprinted.
3.5.1 Ifthemeterisconnectedtoa1N1EcircuitpresstheEnterKeyagainandthenchangethe
secondscreentoLin2Abypressingthedownarrowkey10times,thenhitEnter.Noteon
thetopcornertherewillbeanumber1shownasintheFiguresbelow.
3.5.2 Pressthedownarrow9timesuntilthescreensshowna1intheTopLeftHandCornerand
themainsectiondisplaysLin3w,thenhittheEnterKey
3.5.3 Pressthedownarrow3timestoselect1n1EontheSYSdisplaythenhitEnter.
3.5.4 PresstheEnterKey3timesuntilthebASECUrrscreenappearsensureitssetto5A
3.5.5 ChangePASSto2001bypressingtheuparrowtwice,thenpressingtherightarrow3times
andtheuparrowonce,thenpressenter.
3.5.6 ChangetheCtratioscreenasappropriate,commonlyusedtransformersratiosare:
60/5=15;100/5=20;150/5=30and200/5=40
Top Corner: 1
Line 1: L in 1 V
Line 2:
Line 3:
Bottom: 1-11
Top Corner: 1
Line 1:
Line 2: L in 2 A
Line 3:
Bottom: 11-11
Figure 2. Screen 1
Figure 3. Screen 2
Top Corner: 1
Line 1:
Line 2: L in 3 W
Line 3:
Bottom: 10-11
Figure 4. Screen 3