CONNECTING ELECTRICAL SUPPLY
CAUTION: Thisfurnaceisdesignedfornegativeground12voltD.C. system
only. Do notattempt to alter the furnace for a positive ground system or
connectthefurnacedirectly to 115vo1tsA.C. Damagetofurnacecomponent
partswill occur.
Be sure all wiring to the furnace is of heavyenough gauge to keep the voltage
dro~throuahitto a minimumandto orovideenouah Dowerfor start-uo surae. No.
12gaugewire is recommended.lfanyof theorig;ai wire that issuppliedwith the
appliancemustbereplaced,itmustbereplacedwithtype 105"Cor itsequivalent.
Powersupplyconnectionsareto beontherightsideofthefurnace. Thewires are
colorcoded, redfor positive
(+)
and yellow for negative
(-).
This polaritymust be
observed so the furnacemotorwill run the proper directionof rotation to insure
correctair delivery. (Seewiring diagram.)
If the furnace power supply is to be from a converter, we recommend that the
convertersystemusedto power thefurnace be wired inparrallelwiththe battery.
This will servetwo purposes:
I.
Providea constant voltage supplyto thefurnace.
2. Filter anyA.C. spikes or volt surges.
CONNECTING DUCTS TO FURNACE
The following duct requirements must be followed in order to assure proper
operation of the furnace:
A. The minimumopen duct areas listed below must be maintainedthroughout
entireduct system including through register:
SH-42F
1
48 SQ. IN.
I
4
(
4"
1
56 SQ. IN.
I
72SQ. IN.
'SH-42F
Bottom
Duct requires use
of Bottom
Duct Kit,
Part
No.
520864.
NOTE:
Ducts terminating in a dead air space (like holding tank
compartments) with no means for return air recirculation should not be
counted inthe required duct area. Also, ducts 2" indiameter or smaller
shouldnotbecounted inthe required duct area.
B. Maketheductconnectionsatthefurnacecabinet tight. Looseconnectionswill
resultinoverheatingofthecomponentpartson thefurnaceand a reductionofthe
heatedair flow throughthe duct system.
C. Avoid makinganysharp turnsinthe duct system.Sharpturnswillincreasethe
static pressureinthe plenumarea and could cause the furnace to cycle.
D. Avoid makingalot ofturns inthe duct system. Thestraightertheductsystem,
the better the performanceof the furnace.
E. Maintain a minimum of 114" clearance where ducts pass through any
combustible construction,such as coachcabinetry. (See Figure
3.)
NOTE: UL
listedduct materialscan be
0
clearance.
F. Do not install air boosters in the duct system. Such deviceswill cause the
furnace to cycle on limitand to have erratic sail switch operation.
NOTE:Afterinstallationofthefurnaceandductsystemiscompleted,adjustments
must be made to obtain a temperature rise within the range specified on the
Rating Plate. INSTALLINGTHERMOSTAT
Locatethe roomthermostatapproximately
4-112 feetabove theflooronan inside
bulkhead where it is not affected by heat from any source except room air.
Connectthermostatwiring to the bluewireson right side offurnace. (Seewiring
diagram.)
PREVENTIVEMAINTENANCE
MODEL
SH-35F
inwhich
it
was shipped from the factory or ifthe appliance isnotused
solely for its intended purpose or if appliance is not maintained in
accordance with the instructions inthis manual, then the risk of a fire
andlor the production of carbon monoxide exists which can cause
CAUTION:Labelallwires
beforedisconnedingforservicing.
Properpolarity
mustbeobservedso thefurnacemotorwill runwiththeproperdirection of
rotationto insure correctair delivery. (See wiring diagram).
CAUTION: Labelall wires prior todisconnection whenservicing controls.
Wiring errors cancause improper and dangerous furnace operation.
SlDE DUCTS
Always verify proper operationoffurnace after servicing.
TOP DUCT
Min. Open
DuctArea
56 SQ. IN.
Your fumace should be inspectedby a qualifiedservice agency yearly before
turningthe furnace on. Particularattentionshouldbegivento thefollowing items.
BOTTOMDUCT
Min. Open
DuctArea
56 SQ. IN.
Duct
Size
4"
Min. Open
DuctArea
48
SQ. IN.
I.
lnspectfurnace installationandventterminationtobesurefurnace isproperly
secured in place (see Installation Instructions), that vent terminates to the
atmosphere,and thatventtubesoverlapproperly(seeInstallingVentAssembly.)
Min. No.
DuctsUsed
4
2. lnspectchamberand venting to assurethat these components are physically
;
.: sound without holes or excessive corrosion and that the installationandlor re-
:
'
p
~nstallationisinaccordancewith Suburban's installationinstructions.(Reference
';-/
~nstallationmanual suppliedwithfumace.)
WARNING! Itisimperative that the productsofcombustion beproperly
vented to atmosphere and that all combustion air supplied to burner be
drawnfrom outsideatmosphere.
3. Check the base onwhich furnace is mounted.Be sure it isphysicallysound.
void of any sagging, deterioration, etc.
4. lnspect furnace, the venting, ducting and gas piping to furnace for obvious
signs of deterioration. Correctany defects at once.
5. lnspect combustion chamber for restrictions in exhaust or intake. It is
imperativethat the flow of intake combustion air and the flow of exhaust gases
being expelledto the outside atmosphere not be obstructed. Any soot or loose
debris should be blownout usingcompressedair. (See Figure
6.)
6. lnspect all gaskets. If any gaskets show signs of leakage or deterioration.
replacethem. Safe operation of the furnace depends on all gaskets being tight.
7. lnspect return air inlet openings to the furnace. Remove any restrictions to
assureadequateair flow.
You, as the ownerluser, should inspect the furnace monthly during the
heating seasonfor presenceof soot on vent. Operatingthe furnace underthis
conditioncould leadto serious propertydamage, personal injury or lossof life. If
soot is observedon the vent, immediately shut the furnace down and contacta
qualifiedserviceagency.
Listed below are several safety related itemsthat you should follow during the
heatingseasonto assurecontinued safeoperationof the furnace.
1. lnspectfurnace venting.Ventingmust befree of obstructions,vo~dof soot,and
properly terminated to the atmosphere.(See InstallingVent Assembly.)
WARNING! Do notinstall screens over theventfor any reason. Screens
will becomerestrictedandcause unsafefurnaceoperation.Accessories
are being marketed for RV productswhich we do not recommend. For
2. Periodically inspect the vent for obstructionsor presence of soot. Soot is
formed whenever combustionisincomplete.This isyour visual warning that the
furnace is operatingin an unsafe manner. If soot is present, immediatelyshut
fumace down and contact your dealer or a qualifiedservice person.
3. Keepfurnace clean.Morefrequent cleaningmaybe requireddue to excessive
lint from carpeting. bedding material, etc. It is imperative that control
compartments,burnersandcirculatingair passagewaysof theappliance be kept
clean.
4. The motor is permanently lubricatedand requires no oiling.
5. Keepthe furnace area clear of any combustible materials, gasoline or other
flammablevapor and liquids.
6.
Beforeoperatingfurnace, check the locationofthefurnace vent to makesure
itwill not beblockedbytheopeningofanydooronthe trailer. Ifit canbe blocked.
do not operatethe fumacewith the dooropen.
7. Do not restrict the flow of combustion air or the warm air circulation to the
furnace. To do so could cause personalinjuryandlor death.
8.
Never operate the furnace ifyou smellgas. Do not assume that the smell of
gas in your RV is normal. Any time you detect the odor of gas, it is to be
considered life threatening and corrected immediately. Extinguish any open
flamesincludinaciaarettesandevacuateail oersonsfromthevehicle.Shutoffoas
supply at LP gas Gottle. (See safety notice bnfront cover of this manual.)
9.
Immediatelyshut furnace down and call a service agency if furnace cycles
erraticallyor delaysonignition.
~p
-
-
-
WARNING! Shouldoverheating occur, orthe gas supplyfail to shut off,
shut off the manual gas valve to the appliance before shutting off the
electrical supply.
10. Never attempt to repair damaged parts. Always have them replaced by a
qualifiedserviceagency.
11. Never attempt to repair the furnace yourself. Seek the help of a qualified
serviceperson.
12. Neverrestricttheductinginstalledbyyourtrailer manufacturer.Todoso could
cause improperfumace operation.
13. Do not install air bwsters in the duct system. Such devices will cause the
fumace to cycleand to haveerratic sail switch operation.
14. Clothing or other flammable material should not be placed on or near the
appliance.
15.AlwaysfollowtheOperatingInstructions.Donotdeviatefromthestep-by-step
procedures.
16. Do not use this appliance if any part has been submerged under water.
Immediately call a qualified service technician to inspect the appliance and to
replace any part of the control system and any gas control that has been
submergedunder water.
17. Whenconsidering
addanrooms, porchor patio,attentionmustbegivento the
venting of your furnace. Foryour safety,do notterminatefurnaceventinsideadd-
on rooms, screen porch or onto patios. Doing so will result in products of
combustionbeingventedintothe room or occupied areas.
18. Inanyinstallationinwhichtheventofthisappliancecanbecovereddueto the
constructionof the RV or some special feature of the RV suchas slide out. pop-
up, etc. always insure that the appliance cannot be operated by setting the
thermostat to the positive'OFF" position and shutting off all electricaland gas
supplyto the appliance. Neveroperate furnacewith vent covered.