manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Summit
  6. •
  7. Controllers
  8. •
  9. Summit 4CDC+ User manual

Summit 4CDC+ User manual

Summit Ice Melt Systems
PO Box 6928, Tahoe City, CA 96145
Ph 530-583-8888
summiticemelt.com
Multi-Circuit Standard Ambient Temp Sensing Digital Controllers
4CDC+ ALL-Contactor Controller
Overview
Summit Ice Melt Systems, Inc. Multi-Circuit Digital Controller provides On/O operation
o its S1 and S2 (120Vac to 277Vac) and EverClear 812 and 822 (120Vac to 277Vac)
sel -regulating heater cables by energizing multiple (4, 8, or 12) individual branch
circuits via adjustable control values as set on the temperature controller.
The Controller provides a set point or on/o operation as well as a low-temp cutout o
the circuits. The low-temp cutout shuts the system o when temperatures are so cold
that no snow and ice melting occurs. Both temperatures are easily ield adjustable to
suit local conditions.
Summit Ice Melt Systems
PO Box 6928, Tahoe City, CA 96145
Ph 530-583-8888
summiticemelt.com
Multi-Circuit Ambient Temp Sensing Digital Controllers
Operation
The Multi-Circuit Controller uses a thermistor to sense ambient temperatures. When the
temperature drops below the Heater-On set-point, the system is energized. When the
temperature rises above the Heater-On set-point, the system is de-energized.
I the temperature drops below the low-temp cuto , the system is de-energized. When
the temperature rises above the low-temp cuto , the system is energized.
The 3-position rocker switch allows the operator to set the system in Automatic,
Manual, or O mode (center position). When the rocker switch is set to the MANUAL
position, heaters are energized, regardless o ambient conditions.
Installation
The Multi-Circuit Controller enclosures vary in size to accommodate the number o
circuits controlled. The enclosures are NEMA 4/12 rating so they may be mounted
indoors or outdoors, typically near the circuit breaker panel. Each branch circuit must be
protected by a ground ault protection device per the NEC. A 120Vac protected circuit is
required to energize the controller.
The ambient sensor is mounted outdoors in a shaded location representative o
minimum ambient conditions (typically on the north side o a building), and away rom
any heat source, such as direct sunlight or a utility room exhaust vent, so that the
temperature sensor gives an accurate reading o the air temperature re lective o actual
ambient conditions. The ambient sensor comes with a standard 10 t lead, but its range
can be extended up to hundreds o eet using ordinary stranded copper wire. See
schematic diagram or details.
Pre-Season Testing
The heater circuits may be energized and tested or proper unctionality prior to the cold
weather season by simply setting the 3-position rocker switch to Manual. Amperage
readings may then be taken on each branch circuit. Amperage will depend on ambient
temperature and time. Follow heater manu acturer test procedures.
Summit Ice Melt Systems
PO Box 6928, Tahoe City, CA 96145
Ph 530-583-8888
summiticemelt.com
Multi-Circuit Standard Ambient Temp Sensing Digital Controller
Changing Set-Point Values
To change the Heater-On and Low-temperature Cutout set-point values, ollow the
steps below with the controller powered and the rocker switch set to AUTO:
1) Press the SET button once to display the current Heater-On set-point value
(displays temperature in tenths o degrees). A red indicator light under “out1" will
appear.
2) Press the UP or DOWN arrow button to adjust the value. Hold button to scroll.
3) Press the SET button again to display the current Low-Temp Cutout set-point
value. A red indicator light under “out2" will appear.
4) Press the UP or DOWN arrow button to adjust the value. Hold button to scroll.
5) Press the SET button again to return to the normal operating mode (will display
the current sensed temperature with no decimal point.)
Low-Temp Cutout can e ectively be avoided by setting its value below the lowest
expected ambient temperature ( or example: -50.0.)
NOTE Multi-Circuit controllers default start-up temperature is set to 36E and
should be adjusted to actual field needs.
Alarm Buzzer and Error Messages
I the alarm buzzer sounds, it can be silenced by simultaneously pressing the SET and
Down buttons. The alarm message will continue until condition is corrected.
Common Error Messages
1) “ErP” = Error o the probe not shown on display
2) “ooo” = Open sensor (one or both sensor leads are not connected).
3) “- - -” = Shorted Sensor (direct short between sensor leads).
1
Temperature Switch Heater-On
Out1 LT Cutout
Out2
2 3 456 7 8 910 11 A
HO
UL Listed
Ground Fault
Circuit Breakers
(by others)
Field Wiring
(by others)
10' long
Sensor Lead
For 120V / 277
Applications
120V Input
For 208V / 240V
Applications
Ambient
Sensor
Bulb
L
N
L1
L2
L
N
To
Heater
Circuit
To
Heater
Circuit
To Heater Cable
Ground Braid
(Typical)
Ground
Bar
Ground
Factory
Wiring
A1
A2
X1
X2
H-O-A
Switch
Enclosure
LHeater On Indicator Lamp
Multi-Circuit All-Contactor
Digital Controller
Switches 120V/208/240/277V 30A branch circuits,
wire per example as shown
Available in 4-, 8-, and 12-circuit configurations
NEMA Type 4/12 enclosure. Short circuit current: 5kA rms symmetrical, 480V Max.
Circuit 1: 120V 10A
protected circuit
breaker to be
provided by installer
Circuits 2 - 13: 30A, 30mA
ground fault equipment
protection circuit breakers to
be provided for each circuit by
installer (typical)
A1 A2 X1A X2 X1A X19 X19 X19
X19
X1
X1A
X19
X2
(Typical)
A1
A2
Ground Bar
Sized as
Required
xxx
Turn off all power before servicing
panel or branch circuits
CAUTION
HIGH VOLTAGE
DANGER
Note: Locate sensor on the coldest exterior side of structure (usually
north) under the overhang and not exposed to heat sources such as
sunlight, heating vents, etc. If using extension wiring for remote
placement of sensor bulb, use copper extension wire, 300Vac rated
insulation:
16 gauge up to 60' max. 14 gauge up to 120' max.
12 gauge up to 240' max. 10 gauge up to 480' max.
Important: DO NOT exceed maximum extension wire length
versus wire gauge!
Terminals A1, A2, X1, X2:
Torque at 4.4-7.1 lb In.
Use copper conductors only with a
temperature rating of 60° F. for
terminals rated less than 100
amperes, and a temperature rating of
75° F. for terminals rated for 100
amperes or higher

Other Summit Controllers manuals

Summit SMH4804 User manual

Summit

Summit SMH4804 User manual

Summit S93WD462 User manual

Summit

Summit S93WD462 User manual

Summit HOTEL BOX HBOX168 User manual

Summit

Summit HOTEL BOX HBOX168 User manual

Popular Controllers manuals by other brands

Crestron ZUMMESH-JBOX-20A-SW installation guide

Crestron

Crestron ZUMMESH-JBOX-20A-SW installation guide

Honeywell HCU 23 Installation and operation manual

Honeywell

Honeywell HCU 23 Installation and operation manual

HUSH OnAir Briefing Book

HUSH

HUSH OnAir Briefing Book

YASKAWA U1000 iQpump Drive Quick start quide

YASKAWA

YASKAWA U1000 iQpump Drive Quick start quide

Kessler SECOND SHOOTER user guide

Kessler

Kessler SECOND SHOOTER user guide

Notifier FTM-1 Installation and maintenance instructions

Notifier

Notifier FTM-1 Installation and maintenance instructions

Sunlover SL3 instructions

Sunlover

Sunlover SL3 instructions

Massoth DiMAX Navigator manual

Massoth

Massoth DiMAX Navigator manual

Crestron C3COM-3 installation guide

Crestron

Crestron C3COM-3 installation guide

Jakka EVO PH manual

Jakka

Jakka EVO PH manual

TVILIGHT SkyLite V3.1 External installation manual

TVILIGHT

TVILIGHT SkyLite V3.1 External installation manual

American Dynamics ADTT16E Touch Tracker reference guide

American Dynamics

American Dynamics ADTT16E Touch Tracker reference guide

Carrier 40BNC installation instructions

Carrier

Carrier 40BNC installation instructions

Grundfos UPZCV-3 Installation and operating instructions

Grundfos

Grundfos UPZCV-3 Installation and operating instructions

Distech Controls LonMark ECL-VAV-N installation guide

Distech Controls

Distech Controls LonMark ECL-VAV-N installation guide

Federal Signal Corporation UltraVoice UVRI-B Series Description, Specifications, Installation, and Operation Manual

Federal Signal Corporation

Federal Signal Corporation UltraVoice UVRI-B Series Description, Specifications, Installation, and Operation Manual

Elan S6 brochure

Elan

Elan S6 brochure

ABB REC603 Product guide

ABB

ABB REC603 Product guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.