SUNGOLD POWER APV Series User manual

Sun Gold Power Co.,Ltd www.sungoldpower.com
1
APV Series
Pure Sine Wave Inverter/Charger
User’s Manual
Version 1.0

Sun Gold Power Co.,Ltd www.sungoldpower.com
2
Table of Contents
1. Important Safety Information ........................................................................................................................3
1-1. General Safety Precautions.........................................................................................................................3
1-2. Precautions When Working with Batteries ................................................................................................3
2. Introduction....................................................................................................................................................4
2-1. General Information ...................................................................................................................................4
2-2. Application..................................................................................................................................................4
2.3 Mechanical Drawing....................................................................................................................................5
2-4. Features.......................................................................................................................................................8
2.5 Electrical Performance.................................................................................................................................8
2.5.1 Invert..................................................................................................................................................8
2.5.2 AC Charger ........................................................................................................................................8
2.5.3 Transfer ............................................................................................................................................11
2.5.4 Auto frequency adjust ......................................................................................................................12
2.5.5 Solar Charger ...................................................................................................................................12
2.5.6 Automatic Voltage Regulation ........................................................................错误!未定义书签。
2.5.7 Power Saver .....................................................................................................................................14
2.5.8 Protections........................................................................................................................................15
2.5.9 Remote control.................................................................................................................................15
2.5.10 LED Indicator & LCD ...................................................................................................................16
2.5.11 Audible Alarm ...............................................................................................................................17
2.5.12 FAN Operation...............................................................................................................................17
2.5.13 DIP Switches..................................................................................................................................17
2.5.14 Output Socket.................................................................................................................................18
2.5.15 Other features.................................................................................................................................18
3 Installation.....................................................................................................................................................20
3.1 Location ..............................................................................................................................................20
3.2 DC Wiring recommendation...............................................................................................................20
3.3 AC Wiring...........................................................................................................................................20
3.4 Install Flange.......................................................................................................................................22
4 Troubleshooting Guide .................................................................................................................................23
5 Warranty .......................................................................................................................................................25
Appendix 1.......................................................................................................................................................26

Sun Gold Power Co.,Ltd www.sungoldpower.com
3
1. Important Safety Information
WARNING! Before using the Inverter, you need to read and save the safety instructions.
1-1. General Safety Precautions
1-1-1.Do not expose the Inverter to rain, snow, spray, bilge or dust. To reduce risk of hazard, do not cover or
obstruct the ventilation openings. Do not install the Inverter in a zero-clearance compartment. Overheating
may result. Allow at least 30CM of clearance around the inverter for air flow. Make sure that the air can
circulate freely around the unit. A minimum air flow of 145CFM is required.
1-1-2. To avoid a risk of fire and electronic shock. Make sure that existing wiring is in good electrical
condition; and that wire size is not undersized. Do not operate the Inverter with damaged or substandard
wiring.
1-1-3. This equipment contains components which can produce arcs or sparks. To prevent fire or explosion
do not install in compartments containing batteries or flammable materials or in locations which require
ignition protected equipment. This includes any space containing gasoline-powered machinery, fuel tanks,
or joints, fittings, or other connection between components of the fuel system.
See Warranty for instructions on obtaining service.
1-1-4. Do not disassemble the Inverter/Charger. It contains no user-serviceable parts. Attempting to service
the Inverter/Charger yourself may result in a risk of electrical shock or fire. Internal capacitors remain
charged after all power is disconnected.
1-1-5. To reduce the risk of electrical shock, disconnect both AC and DC power from the RV Series
Inverter/Charger before attempting any maintenance or cleaning. Turning off controls will not reduce this
risk
CAUTION: Equipment damage
The output side of the inverter’s AC wiring should at no time be connected to public power or a generator.
This condition is far worse than a short circuit. If the unit survives this condition, it will shut down until
corrections are made.
Installation should ensure that the inverter’s AC output is, at no time, connected to its AC input.
Warning: Limitations On Use
SPECIFICALLY, PLEASE NOTE THAT THE GLOBAL LF INVERTER/CHARGER SHOULD NOT BE
USED IN CONNECTION WITH LIFE SUPPORT SYSTEMS OR OTHER MEDICAL EQUIPMENT OR
DEVICES.
1-2. Precautions When Working with Batteries
1-2-1. If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters eye,
immediately flood eye with running cold water and get medical attention immediately.
1-2-2. Never smoke or allow a spark or flame in vicinity of battery or engine.
1-2-3. Do not drop a metal tool on the battery. The resulting spark or short-circuit on the battery of other
electrical part may cause an explosion.
1-2-4. Remove personal metal items such as rings, bracelets, necklaces, and watches when working with a
lead-acid battery. A lead-acid battery produces a short-circuit current high enough to weld a ring or the like
to metal, causing a severe burn.
1-2-5. To reduce the risk of injury, charge only deep-cycle lead acid, lead antimony, lead calcium gel cell,
absorbed mat, or NiCad/NiFe type rechargeable batteries. Other types of batteries may burst, causing
personal injury and damage.

Sun Gold Power Co.,Ltd www.sungoldpower.com
4
2. Introduction
2-1. General Information
APV Series Pure Sine Wave Inverter is a combination of an inverter, battery charger and AC auto-transfer
switch into one complete system with a peak conversion efficiency of 88%.
It is packed with unique features and it is one of the most advanced inverter/chargers in the market today.
It features power factor corrected, sophisticated multi-stage charging and pure sine wave output with
unprecedentedly high surge capability to meet demanding power needs of inductive loads without
endangering the equipment.
For the regular model, when utility AC power cuts off(or falls out of acceptable range), the transfer relay is
de-energized and the load is automatically transferred to the Inverter output. Once the qualified AC utility is
restored, the relay is energized and the load is automatically reconnected to AC utility.
APV Series Inverter is equipped with a powerful charger of up to 90Amp(depending on model).
The overload capacity is 300% of continuous output for up to 20 seconds to reliably support tools and
equipment longer
Another important feature is that the inverter can be easily customized to Battery priority via a DIP switch,
this helps to extract maximum power from battery in renewable energy systems.
Thus, the APV Series Pure Sine Wave Inverter is suitable for Renewable energy system, Utility, RV, Marine
and Emergency appliances.
To get the most out of the power inverter, it must be installed, used and maintained properly. Please read the
instructions in this manual before installing and operating.
2-2. Application
Power tools–circular saws, drills, grinders, sanders, buffers, weed and hedge trimmers, air compressors.
Office equipment – computers, printers, monitors, facsimile machines, scanners.
Household items – vacuum cleaners, fans, fluorescent and incandescent lights, shavers, sewing machines.
Kitchen appliances – coffee makers, blenders, ice markers, toasters.
Industrial equipment – metal halide lamp, high – pressure sodium lamp.
Home entertainment electronics – television, VCRs, video games, stereos, musical instruments, satellite
equipment.

Sun Gold Power Co.,Ltd www.sungoldpower.com
5
2.3 Mechanical Drawing
Model No: APV1500W12V230V (below)

Sun Gold Power Co.,Ltd www.sungoldpower.com
6
Model No: APV1500W12V120V, APV3000W12V120V, APV3000W24V120V (below)

Sun Gold Power Co.,Ltd www.sungoldpower.com
7
Model No: APV6000W24V240VS

Sun Gold Power Co.,Ltd www.sungoldpower.com
8
2-4. Features
High overload ability up to 300% rated power (20 sec)
Low quiescent current, low power “Power Saving Mode “ to conserve energy
4-step intelligent battery charging, PFC (Power Factor Correction) for charger
8 pre set battery type selector plus de-sulphation for totally flat batteries
Powerful charge rate up to 90Amp, selectable from 0%-100%
10 ms typical transfer time between battery and AC, guarantees power continuity
Smart remote control
15s delay before transfer when AC resumes, extra protection for loads when used with generator
Allows start up and through power with depleted batteries
30A/40A through current ability
Multiple controlled cooling fan
Extensive protections against various harsh situations
13VDC battery recover point, dedicated for renewable energy systems
2.5 Electrical Performance
2.5.1 Invert
Topology
The APV inverter/charger is built according to the following topology.
Invert: Full Bridge Topology.
Charge: Isolate Boost Topology
Because of high efficiency Mosfets and 16bit, 4.9MHZ microprocessor and heavy transformers, it outputs
PURE SINE WAVE AC with an average THD of 15% (min 5%, max 25%) depending of load connected
and battery voltage.
The peak efficiency of APV series is 88%.
Overload Capacity
The APV series inverters have different overload capacities, making it ideal to handle demanding loads.
1 For 110%<Load<125%(±10%), no audible alarm in 14 minutes, beeps 0.5s every 1s in the 15th minute,
and Fault(Turn off) after the 15th minute.
2 For 125%<Load<150%(±10%), beeps 0.5s every 1s and Fault(Turn off) after the 1 minute.
3 For 300%≧Load>150%(±10%), beeps 0.5s every 1s and Fault(Turn off) after 20s.
2.5.2 AC Charger
APV Series is equipped with an active PFC (Power Factor Corrected) multistage battery charger. The PFC
feature is used to control the amount of power used to charge the batteries in order to obtain a power factor
as close as possible to 1.
Unlike other inverters whose max charging current decreases according to the input AC voltage, APV series
charger is able to output max current as long as input AC voltage is in the range of
164-243VAC(95-127VAC for 120V model), and AC freq is in the range of 48-54Hz(58-64Hz for 60Hz

Sun Gold Power Co.,Ltd www.sungoldpower.com
9
model).
The APV series inverter is with a strong charging current of 90Amp (for 3KW,12V), and the max charge
current can be adjusted from 0%-100% via a liner switch at the right of the battery type selector. This will be
helpful if you are using our powerful charger on a small capacity battery bank. Fortunately, the liner switch
can effectively reduce the max charging current to 20% of its peak.
Choosing “0” in the battery type selector will disable charging function.
There are mainly 3 stages:
Bulk Charging: This is the initial stage of charging. While Bulk Charging, the charger supplies the battery
with controlled constant current. The charger will remain in Bulk charge until the Absorption charge voltage
(determined by the Battery Type selection) is achieved.
Software timer will measure the time from A/C start until the battery charger reaches 0.3V below the boost
voltage, then take this time asT0 and T0×10 = T1.
Absorb Charging: This is the second charging stage and begins after the absorb voltage has been reached.
Absorb Charging provides the batteries with a constant voltage and reduces the DC charging current in order
to maintain the absorb voltage setting.
In this period, the inverter will start a T1 timer; the charger will keep the boost voltage in Boost CV mode
until the T1 timer has run out. Then drop the voltage down to the float voltage. The timer has a minimum
time of 1 hour and a maximum time of 12 hours.
Float Charging: The third charging stage occurs at the end of the Absorb Charging time. While Float
charging, the charge voltage is reduced to the fl oat charge voltage (determined by the Battery Type
selection*). In this stage, the batteries are kept fully charged and ready if needed by the inverter.
If the A/C is reconnected or the battery voltage drops below 12Vdc/24Vdc, the charger will reset the cycle
above.
If the charge maintains the float state for 10 days, the charger will deliberately reset the cycle to protect the
battery.

Sun Gold Power Co.,Ltd www.sungoldpower.com
10
Battery type selector
Switch setting Description Boost / Vdc Float / Vdc
0 Charger Off
1 Gel USA 14.0 13.7
2 AGM 1 14.1 13.4
3 AGM 2 14.6 13.7
4 Sealed lead acid 14.4 13.6
5 Gel EURO 14.4 13.8
6 Open lead acid 14.8 13.3
7 Calcium 15.1 13.6
8 De-sulphation 15.5 (4 Hours then Off)
9 Not used
12Vdc Mode (*2 for 24Vdc ; *4 for 48Vdc)
De-sulphation
The de-sulphation cycle on switch position 8 is marked in red because this is a very dangerous setting if you
do not know what you are doing. Before ever attempting to use this cycle you must clearly understand what
it does and when and how you would use it.
What causes sulphation? This can occur with infrequent use of the batteries(nor), or if the batteries have
been left discharged so low that they will not accept a charge. This cycle is a very high voltage charge cycle
designed to try to break down the sulphated crust that is preventing the plates taking a charge and thus allow
the plates to clean up and so accept charge once again.
Charging depleted batteries
The APVseries inverter allows start up and through power with depleted batteries.

Sun Gold Power Co.,Ltd www.sungoldpower.com
11
For 12VDC model, after the battery voltage goes below 10V, if the switch is still (and always) kept in "ON"
position, the inverter is always connected with battery, and the battery voltage doesn’t drop below 2V, the
inverter will be able to charge the battery once qualified AC inputs are present.
Before the battery voltage goes below 9VDC, the charging can be activated when the switch is turned to
“Off”, then to “ON”.
When the voltage goes below 9VDC, and you accidently turn the switch to OFF or disconnect the inverter
from battery, the inverter will not be able to charge the battery once again, because the CPU loses memory
during this process.
Charging current for each model
Model Current Model Current
APV1000W12V230V 35+/-5A APV1000W12V120V 20+/-5A
APV1000W24V230V 20+/-5A APV1000W24V120V 15+/-5A
APV1500W12V230V 45+/-5A APV1500W12V120V 45+/-5A
APV1500W24V230V 25+/-5A APV1500W24V120V 25+/-5A
APV2000W12V230V 65+/-5A APV2000W12V120V 40+/-5A
APV2000W24V230V 30+/-5A APV2000W24V120V 30+/-5A
APV2000W48V230V 20+/-5A APV2000W48V120V 15+/-5A
APV3000W12V230V 85+/-5A APV3000W12V120V 65+/-5A
APV3000W24V230V 45+/-5A APV3000W24V120V 40+/-5A
APV3000W48V230V 30+/-5A APV3000W48V120V 25+/-5A
APV4000W24V230V 65+/-5A APV4000W24V120V 50+/-5A
APV4000W48V230V 35+/-5A APV4000W48V120V 30+/-5A
APV5000W24V230V
APV5000W24V230VS 70+/-5A
APV5000W48V230V
APV5000W48V230VS 40+/-5A
APV6000W24V230V
APV6000W24V230VS 85+/-5A
APV6000W48V230V
APV6000W48V230VS 55+/-5A
The charging capacity will go to peak in around 3 seconds. This may cause a generator to drop frequency,
making inverter transfer to battery mode.
It is suggested to gradually put charging load on the generator by switching the charging switch from min to
max, together with the 15s switch delay, our inverter gives the generator enough time to spin up. This will
depend on the size of the generator and rate of charge.
2.5.3 Transfer
While in the Standby Mode, the AC input is continually monitored. Whenever AC power falls below the
VAC Trip voltage (154 VAC, default setting for 230VAC,90VAC for 120VAC), the inverter automatically
transfers back to the Invert Mode with minimum interruption to your appliances - as long as the inverter is
turned on. The transfer from Standby mode to Inverter mode occurs in approximately 10 milliseconds. And
it is the same time from Inverter mode to Standby mode.
Though it is not designed as a computer UPS system, this transfer time is usually fast enough to keep your

Sun Gold Power Co.,Ltd www.sungoldpower.com
12
equipment powered up.
There is a 15-second delay from the time the inverter senses that continuously qualified AC is present at the
input terminals to when the transfer is made. This delay is built in to provide time for a generator to spin-up
to a stable voltage and avoid relay chattering. The inverter will not transfer to generator until it has locked
onto the generator’s output. This delay is also designed to avoid frequent switching when input utility is
unstable.
2.5.4 Auto frequency adjust
The inverter is with Auto Frequency adjust function.
The factory default configuration for 220/230/240VAC inverter is 50Hz, and 60Hz for 110/110/120VAC
inverter.
While the output freq can be easily changed once a qualified freq is applied to the inverter.
If you want to get 60Hz from a 50Hz inverter, just input 60Hz power, and the inverter will automatically
adjust the output freq to 60Hz and vice versa.
2.5.5 Solar Charger
Listed below is the spec for solar charger
Table 1 Electrical Specification @ 25℃
Rated Voltage 12 Vdc 24Vdc
Rated charge current (includes
load current) 60Amp
Load current 15Amp
Input voltage range 15-30Vdc 30-55Vdc
Max. PV open circuit array
voltage 30Vdc 55Vdc
Overload protection (DC load)
2.0 * I(Rated)>5s
1.5 * I(Rated) >20s
1.25 * I(Rated) temperature controlled
Typical idle consumption At idle < 10mA
Bulk charge 14.6Vdc (default) 29.2Vdc (default)
Floating charge 13.4Vdc (default) 26.8Vdc (default)
Equalization charge 14.0Vdc (default) 28.0Vdc (default)
Over charge disconnect 14.8Vdc 29.6Vdc
Over charge recovery 13.6Vdc 27.2Vdc
Over discharge disconnect 10.8Vdc (default) 21.6Vdc (default)
Over discharge reconnect 12.3Vdc 24.6Vdc
Temperature compensation -13.2mV/℃-26.4mV/℃
Lead acid battery settings Adjustable
NiCad battery settings Adjustable
Low voltage reconnect 12.0-14.0Vdc 24.0-28.0Vdc
Low voltage disconnect 10.5-12.5Vdc 21.0-25.0Vdc
Ambient temperature 0-40℃(full load) 40-60℃(de-rating)

Sun Gold Power Co.,Ltd www.sungoldpower.com
13
Altitude Operating 5000 m, Non-Operating 16000 m
Protection class IP21
Battery temperature sensor BTS - optional remote battery temperature sensor for increased
charging precision
Terminal size (fine/single wire) #8 AWG
NOTE:
The optional battery temp①erature sensor automatically adjusts the charging process of the controller
according to the type of battery that is selected by user through battery type selector. With the battery
temperature sensor installed, the controller will increase or decrease the battery charging voltage depending
on the temperature of the battery to optimize the charge to the battery and maintain optional performance of
the battery.
Maximum Power Point Tracking (MPPT) Function
Maximum Power Point Tracking, frequently referred to as MPPT, is an electronic system that operates the
Photovoltaic (PV) modules in a manner that allows the modules to produce all the power they are capable
of.
The PV-seeker Charge controller is a microprocessor-based system designed to implement the MPPT.
And it can increase charge current up to 30% or more compared to traditional charge controllers (see figure
1).
Figure 1 Current, Power vs. Voltage Characteristics
The Charge controller built in is with 12/24V battery voltage auto detecting function.
For 12VDC inverter, the output voltage of solar charger will be accordingly 12VDC, and the qualified DC
input volt range is 15v-30VDC.
For 24VDC inverter, the output voltage of solar charger will be accordingly 24VDC, and the qualified DC
input volt range is 30v-55VDC.
If the voltage falls out of this range, the charger will not work properly. Special attention should be paid to
this when configuring the solar array.

Sun Gold Power Co.,Ltd www.sungoldpower.com
14
2.5.6Power Saver
There are 2 different working status for Global LF
inverter:“PowerOn”and“PowerOff”.
When power switch is in “Unit Off” position, the inverter is powered off.
When power switch is turned to either of “Power Saver Auto” or “Power Saver Off”, the inverter is powered
on.
Power saver function is designed to conserve battery power when AC power is not or rarely required by the
loads.
In this mode, the inverter pulses the AC output looking for an AC load (i.e., electrical appliance). Whenever
an AC load (greater than 25 watts) is turned on, the inverter recognizes the need for power and automatically
starts inverting and output goes to full voltage. When there is no load (or less than 25 watts) detected, the
inverter automatically goes back into search mode to minimize energy consumption from the battery bank.
In “Power saver on” mode, the inverter will draw power mainly in sensing moments, thus the idle
consumption is significantly reduced.
The inverter is factory defaulted to detect load for 250ms every 30 seconds. This cycle can be customized to
3 seconds thru SW3 on the DIP switch.
Power saver on
Power saver off
Power saver on(Load detected)
Note: The minimum power of load to take inverter out of sleep mode (Power Saver On) is 25 Watts.
APV Series Idle Power Consumption
Power Saver Off Power Saver Auto
Model Idle 3Secs(Max) 30Secs(MAX)
1000W 42W 16W 10W
1500W 48W 20W 10W
2000W 60W 25W 10W
3000W 72W 28W 12W
4000W 120W 45W 15W
5000W 135W 50W 18W
6000W 145W 55W 18W

Sun Gold Power Co.,Ltd www.sungoldpower.com
15
When in the search sense mode, the green power LED will blink and the inverter will make a ticking sound.
At full output voltage, the green power LED will light steadily and the inverter will make a steady humming
sound. When the inverter is used as an “uninterruptible” power supply the search sense mode or “Power
Saver On” function should be defeated.
Exceptions
Some devices when scanned by the load sensor cannot be detected. Small fluorescent lights are the most
common example. (Try altering the plug polarity by turning the plug over.) Some computers and
sophisticated electronics have power supplies that do not present a load until line voltage is available. When
this occurs, each unit waits for the other to begin. To drive these loads either a small companion load must
be used to bring the inverter out of its search mode, or the inverter may be programmed to remain at full
output voltage.
2.5.7 Protections
The APV series inverter is equipped with extensive protections against various harsh situations/faults.
These protections include:
AC Input over voltage protection/AC Input low voltage protection
Low battery alarm/High battery alarm
Over temperature protection/Over load protection
Short Circuit protection (1s after fault)
Back feeding protection
When Over temperature /Over load occur, after the fault is cleared, the master switch has to be reset to
restart the inverter.
The Low batter voltage trip point can be customized from defaulted value 10VDC to 10.5VDC thru the SW1
on DIP switch.
The inverter will go to Over temp protection when heat sink temp. ≥105ºC, and go to Fault (shutdown
Output) after 30 seconds. The switch has to be reset to activate the inverter.
The Global LF series Inverter has back feeding protection which avoids presenting an AC voltage on the AC
input terminal in Invert mode.
After the reason for fault is cleared, the inverter has to be reset to start working.
2.5.8 Remote control
Apart from the switch panel on the front of the inverter, an extra switch panel connected to the RJ11 port at
the DC side of the inverter thru a standard telephone cable can also control the operation of the inverter.
If an extra switch panel is connected to the inverter via “remote control port”, together with the panel on the
inverter case, the two panels will be connected and operated in parallel.
Whichever first switches from “Off” to “Power saver off” or “Power saver on”, it will power the inverter
on.
If the commands from the two panels conflict, the inverter will accept command according to the following
priority:
Power saver on> Power saver off> Power off
Only when both panels are turned to “Unit Off” position will the inverter be powered off.
The Max length of the cable is 10 meters.

Sun Gold Power Co.,Ltd www.sungoldpower.com
16
WARNING
Never cut the telephone cable when the cable is attached to inverter and battery is connected to the inverter.
Even if the inverter is turned off. It will damage the remote PCB inside if the cable is short circuited during
cutting.
2.5.9 LED Indicator & LCD
SHORE POWER ON GREEN LED lit in AC Mode
INVERTER ON GREEN LED lit in Inverter Mode
FAST CHARGE Yellow LED lit in Fast Charging Mode
FLOAT CHARGE GREEN LED lit in Float Charging Mode
OVER TEMP TRIP RED LED lit in Over Temperature
OVER LOAD TRIP RED LED lit in Over Load
POWER SAVER ON GREEN LED lit in Power Saver Mode (Power Saver
Load ≦25W)
The LCD will display the following content:
1 Greeting message 2 AC Status & Input Voltage
“AC: abnormal” will be displayed when AC input
is not qualified.
3 Output Voltage/Frequency and Battery voltage 4 Output Current( in percentage)

Sun Gold Power Co.,Ltd www.sungoldpower.com
17
2.5.10 Audible Alarm
Battery Voltage Low Inverter green LED lit, and the buzzer beeps 0.5s every 5s.
Battery Voltage High Inverter green LED lit, and the buzzer beeps 0.5s every 1s and Fault after
60s.
Invert Mode Over-Load
(1)110%<load<125%(±10%), No audible alarm in 14 minutes,
Beeps 0.5s every 1s in 15th minute and Fault after 15 minutes;
(2)125% <load<150%(±10%), Beeps 0.5s every 1s and Fault after 60s;
(3)Load>150%(±10%), Beeps 0.5s every 1s and Fault after 20s;
Over Temperature Heat sink temp. ≥105ºC, Over temp red LED Lighting, beeps 0.5s every
1s;
2.5.11 FAN Operation
For 1-3KW, there is one multiple controlled DC fan which starts to work according to the following logic.
For 4-6KW, there is one multiple controlled DC fan and one AC fan. The DC fan will work in the same way
as the one on 1-3KW, while the AC fan will work once there is AC output from the inverter.
So when the inverter is in power saver mode, the AC fan will work from time to time in response to the
pulse sent by the inverter in power saver mode.
The Operation of the DC fan at the DC terminal side is controlled by the following logic:
Condition Enter Condition Leave condition Speed
T < 85 ℃T ≥85℃50%
HEAT SINK
TEMPERATURE T ≥85℃T < 80℃100%
I ≤50%Max I > 50%Max 50%
CHARGER
CURRENT I > 50%Max I ≤40%Max 100%
Load < 50% Load ≥50% 50%
LOAD Percentage
(INV MODE) Load ≥50% Load ≤40% 100%
Allow at least 30CM of clearance around the inverter for air flow. Make sure that the air can circulate freely
around the unit.
Fan noise level <60db at a distance of 1m
2.5.12 DIP Switches
On the DC end of inverter, there are 4 DIP switches which enable users to customize the performance of the
device.

Sun Gold Power Co.,Ltd www.sungoldpower.com
18
Switch NO Switch Function Position: 0 Position: 1
10.0VDC 10.5VDCSW1 Low Battery Trip Volt
*2 for 24VDC, *4 for 48VDC
SW2(230V) AC Input Range 184-253VAC 154-253VAC
SW2(120V) AC Input Range 100-135VAC 90-135VAC
SW3 Load Sensing Cycle 30 seconds 3 seconds
SW4 Battery/AC Priority Utility Priority Battery Priority
Low Battery Trip Volt:
For 12VDC model, the Low Battery Trip Volt is set at 10.0VDC by default. It can be customized to
10.5VDC using SW1, this is to prevent batteries from over-discharging while there is only a small load
applied on the inverter.
*2 for 24VDC, *4 for 48VDC
AC Input Range:
There are different acceptable AC input ranges for different kinds of loads.
For some relatively sensitive electronic devices, a narrow input range of 184-253VAC (100-135V for
120VAC model) is required to protect them.
While for some resistive loads which work in a wide voltage range, the input AC range can be customized to
154-253VAC (90-135V for 120VAC model), this helps to power loads with the most AC input power
without frequent switches to the battery bank.
Load Sensing Cycle:
The inverter is factory defaulted to detect load for 250ms in every 30 seconds. This cycle can be customized
to 3 seconds thru the SW3 on the DIP switch.
AC/Battery Priority:
Our inverter is designed with AC priority by default. This means, when AC input is present, the battery will
be charged first, and the inverter will transfer the input AC to power the load. Only when the AC input is
stable for a continuous period of 15 days, the inverter will start a battery inverting cycle to protect the
battery. After 1 cycle normal charging and ac through put will be restored.
The AC Priority and Battery Priority switch is SW4. When you choose battery priority, the inverter will
inverting from battery despite the AC input. Only when the battery voltage is reaches low voltage alarm
point(10.5V for 12V), the inverter transfers to AC Input, charges battery, and switches back to battery when
battery is charged full. This function is mainly for wind/solar systems taking utility power as back up.
2.5.13 Output Socket
The inverter is either equipped with a dual GFCI socket (rated at 30Amps) or an universal socket (rated at
10Amps) for more convenient wiring.
2.5.14 Other features
Battery voltage recover start
After low battery voltage shut off (10V for 12V model or 20V for 24V model), the inverter is able to restore
operation after the battery voltage recovers to 13V/26V (with power switch still in the “On” position). This

Sun Gold Power Co.,Ltd www.sungoldpower.com
19
function helps to save the users extra labor to reactivate the inverter when the low battery voltage returns to
an acceptable range in the renewable energy systems. The built in battery charger will automatically
reactivate as soon as city/generator ac has been stable for 15 seconds.
WARNING
Never leave the loads unattended, some loads (like a Heater) may cause accident in such cases.
It is better to shut everything down after low voltage trip than to leave your load on, due to the risk of fire.
Auto Gen Start
The inverter can be customized to start up a generator when battery voltage goes low.
When the inverter goes to low battery alarm, it can send a signal to start a generator, and turn the generator
off after battery charging is finished.
The auto gen start feature will only work with generators designed to work with this feature. There is an
open/closed relay that will short circuit the positive and negative cable from a generator. The input DC
voltage can vary, but the Max current the relay can carry is 16Amp.
Conformal Coating
EYEN entire line of APV inverters have been processed with a conformal coating on the PCB making it
water, rust, and dust resistant.

Sun Gold Power Co.,Ltd www.sungoldpower.com
20
3 Installation
3.1 Location
Follow all the local regulations to install the inverter.
Please install the equipment in a location that is Dry, Clean, Cool and that has good ventilation.
Working temperature: ‐10℃‐40℃
Storage temperature: ‐40‐70℃
Relative Humidity: 0%‐95%,non-condensing
Cooling: Forced air
3.2 DC Wiring recommendation
It is suggested the battery bank be kept as close as possible to the inverter. The following able is a suggested
wiring option for 1 meter DC cable.
Please find the following minimum wire size. In case of DC cable longer than 1m, please increase the cross section of
cable to reduce the loss.
Power DC Input voltage Wire Gage
1KW 12V AWG 1/0
1KW 24V AWG 4
1.5KW 12V AWG 1/0
1.5KW 24V AWG 4
2KW 12V AWG 1/0
2KW 24V AWG 1/0
2KW 48V AWG 4
3KW 12V AWG 4/0
3KW 24V AWG 1/0
3KW 48V AWG 4
4KW 24V AWG 1/0
4KW 48V AWG 1/0
5KW 24V AWG 4/0
5KW 48V AWG 1/0
6KW 24V AWG 4/0
6KW 48V AWG 1/0
3.3 AC Wiring
We recommend using 10-5Awg wire to connect to the ac terminal block.
There are 3 different ways of connecting to the terminal block depending on the model. All the wirings are CE
compliant, Call our tech support if you are not sure about how to wire any part of your inverter.
This manual suits for next models
7
Table of contents
Other SUNGOLD POWER Inverter manuals

SUNGOLD POWER
SUNGOLD POWER CUT-50H User manual

SUNGOLD POWER
SUNGOLD POWER SPH302480A User manual

SUNGOLD POWER
SUNGOLD POWER SGR-18K20E User manual

SUNGOLD POWER
SUNGOLD POWER SPH8K48SP User manual

SUNGOLD POWER
SUNGOLD POWER Hybrid BluePower TP6048 User manual

SUNGOLD POWER
SUNGOLD POWER BluePower SP6548 User manual

SUNGOLD POWER
SUNGOLD POWER 6000W 48V Hybrid Solar Inverter Split Phase... User manual

SUNGOLD POWER
SUNGOLD POWER LFPV Series User manual

SUNGOLD POWER
SUNGOLD POWER SGM-655M User manual

SUNGOLD POWER
SUNGOLD POWER SPH504880A User manual