Suniva Optimus OPTXXX-60 Series Quick guide

OPTXXX-##-4-1YY IEC & UL EN Suniva, Inc. SI&IM _9 Rev 9 Pa e 1
Suniva Inc.
5765 Peachtree Industrial Blvd
Norcross, GA 30092
Tel: 404-477-2700
www.suniva.com
Suniva OPTIMUS Installation and Instruction Manual
Introduction
This manual provides safety and installation instructions for
Suniva photovoltaic modules, herein referred to as module(s),
with the followings model numbers:
•OPTXXX-72-4-YYY; Where XXX could be 285 to 350 in
increments of 5. YYY could be either 100, 101, 1B0, or 1B1
•OPTXXX-60-4-YYY; Where XXX could be 235 to 285 in
increments of 5. YYY could be either 100, 101, 1B0 or 1B1
To maintain the safety of yourself and others, carefully read the
entire installation and instruction sheet prior to installation and
operation. System safety and proper design should be ensured
by qualified personnel. Failure to comply with these
instructions will invalidate the Suniva Limited Warranty for the
module. For more information, please visit our website.
Safety
Suniva modules produce electricity when exposed to light.
To avoid electric shock and injury, completely cover the front
of the module with an opaque material before making any
electrical connections and disconnect the module from all
electrical connections before any maintenance or cleaning.
Only individuals trained in the principles of electricity and
electrical equipment should install modules.
Modules must be installed in a manner compliant with the
National Electric Code (NEC) and/or all applicable standards
and codes.
Use properly insulated tools and appropriate protective
equipment and work only in dry conditions.
Protective gloves should be worn when handling modules to
protect against sharp edges and burns.
Do not artificially concentrate sunlight on the module(s).
Do not install the modules in an area where flammable gas
or material may be present.
Do not remove any part installed by a qualified installer, or
disassemble the module in any way.
Do NOT cut connectors off of the PV module
Use original packaging to transport and store module.
Avoid excessive loads, bending, and twisting of the module.
Do not step/stand on the module.
Avoid wearing metallic jewelry when installing or handling
the module to protect against electric shock.
Do not leave the module unsupported or loosely fixed during
or prior to installation and avoid installing during heavy winds.
Do not attempt to repair a broken or damaged module,
replace immediately to avoid fire danger and shock hazard.
Use caution when handling as damaged modules may
conduct electricity to the frame.
Long-term storage of PV modules
PV modules should be stored, before and during
installation, in a manner to protect the unconnected
connectors from ingress of foreign elements such as: dust,
dirt, snow, ice, and water.
Product Information
This solar module can be used in series and parallel array
configurations or as a stand-alone system.
For IEC installations: This module is certified to IEC 61730-1
and IEC 61730-2 for application Class A and is rated for use
in systems operating at voltages greater than 50 VDC or 240
W, where general contact access is expected. And for Class
A applications this module meets requirements of Safety
Class II as defined by IEC 61140.
The allowable operating temperatures range of the module is
185 ⁰F to -40 ⁰F (85 ⁰C to -40 ⁰C).
Serial Number
The structure of the module serial number provides the
following information:
Example: SJWSH00011103310017
S-JWSH-0001 – 11– 03 – 31 - 0017
A-BBCC-DDDD-EE-FF-GG-HHHH
A: Manufacturer; BB: Factory; CC: Factory Location
DDDD: Engineering Number; EE: Year of Production; FF:
Month of Production; GG: Date of Production; HHHH: 4 digit
sequence 0 to 9999 for sequential production starting on
each new day of production at 0001.
Electrical Characteristics
See tables at end of installation manual for electrical
parameters.
The electrical characteristics are within ±10 percent of the
indicated values of I
SC
, V
OC
, and P
MAX
under standard test
conditions; irradiance of 100 mW/cm
2
, AM 1.5 spectrum, and
a cell temperature of 25°C (77°F).
Maximum series fuse rating is 15 A
This module is rated for use in systems of up to 1000 V for
TUV/IEC and up to 1000 V for UL
Under normal conditions, a photovoltaic module is likely to
experience conditions that produce more current and/or
voltage than reported at standard test conditions.
Accordingly, the values of I
SC
and V
OC
marked on this
module should be multiplied by a factor of 1.25 when
determining component voltage ratings, conductor
ampacities, fuse sizes, and size of controls connected to the
PV output.
Per NEC: “Refer to Section 690-8 of the NEC for an
additional multiplying factor of 125 percent (80 percent
derating) which may be applicable.”
Temperature Coefficients
Temperature Coefficients
Power , Pmax (%/°C) - 0.420
Voltage ß, Voc (%/°C) - 0.335
Current , Isc (%/°C) + 0.047
NOCT C 46 +/- 2
Mounting Overview
Mounting design and installation should be performed by
trained professional and must conform to local codes.
Select a site and configuration that maximizes direct sunlight
exposure and eliminates or minimizes shadowing.
Avoid small tilt angles to prevent the accumulation of
dirt/debris along module edge.
Improper mounting of the module(s) can lead to damage or
injury and will void the warranty. Do not drill additional
mounting holes into module frames. This will void the
warranty.
The module(s) should be fixed in a manner that withstands
all expected loads, including those caused by wind, snow
and ice. Verify by certified engineer.
Orient the module junction box in such a way and provide
clearance between the module frame and mounting surface
to ensure that water cannot build up at the junction box and
so the junction box does not contact the mounting surface.
The PV module is listed as Type 2 under the revised
ANSI/UL 1703 standard.

OPTXXX-##-4-1YY IEC & UL EN Suniva, Inc. SI&IM _9 Rev 9 Pa e 2
If the module is to be mounted to a roof of a building, the
assembly must be mounted over a fire resistant roof
covering suitable for the application. A slope less than 5 in/ft
(127 mm/305mm) is required to maintain the fire class rating.
Mounting Instructions
It is acceptable to mount this module using bolts or clamps
to secure module to a structure on a roof, building or ground.
The module is considered to be in compliance with UL 1703
only when the module is mounted in the manner specified by
the mounting instructions below.
If mounting module in landscape orientation please ensure
cable length is of appropriate length for interconnection.
Provide a minimum of 4 in. (~100 mm) clearance between
back of module and roof or ground or building, etc. when
installing to ensure proper air flow.
Allow for thermal expansion of the frames by providing a
minimum of 0.25 in. (or approximately 6 mm) spacing
between modules.
OPTXXX-60-4-1YY Series modules are rated to 5400 Pa or
2400 IEC Positive Static Load and 2400 Pa IEC61215
Negative Load when mounted according to these
instructions. Read the module label to determine load rating.
OPTXXX-72-4-1YY Series modules are rated to 2400 Pa
IEC61215 Positive and Negative Load when mounted
according to these instructions.
Both OPTXXX-60-4-1YY and OPTXXX-72-4-1YY are rated
to UL1703 design load rating of 30 lb/ft
2
.
Any alternative configurations must be verified to meet load
requirements.
Rail Mounting
A supporting structure can be used to mount the modules at
various tilt angles. See Figure 1 for recommend
configuration. Ensure no dissimilar combinations of metals
be used that when damp or wet could result in degradation
of the materials and as a result create conditions that
prevent the module from meeting installation requirements
and instructions set forth in this manual.
The frame of each module has four mounting holes. These
are to be used to secure the module(s) to the supporting
structure. Use ¼ in. (or M6) bolt with a ¼ in. (or M6) flat
washer beneath bolt head and a ¼ in. (or M6) lock washers
between ¼ in. (or M6) nut and rail with a minimum of 80 in-lb
(9 N-m) of torque to secure bolt. Use only stainless steel
mounting hardware.
It is recommended that the mounting rails must be aligned
with the frame mounting holes (Figure 1) and run
perpendicular to the length of the module.
Figure 1: Mounting Hole Location and Example of Rail Mount
Clamp Mounting
Clamps can be used to achieve mounting to a support
structure. A minimum of four points of contact at the location
(+/- 3 in. or 76.2 mm) of pre-drilled mounting holes should be
used. See Figure 2 for typical clamp assembly.
Figure 2: Clamp Mounting Example Diagram
Equipment Grounding
A module with exposed conductive parts is considered to be
in compliance with UL 1703 only when it is electrically
grounded in accordance with the instructions presented
below and the requirements of the National Electrical Code
(NEC)
Where common grounding hardware (nuts, bolts, star
washers, spilt-ring lock washers, flat washers and the like) is
used to attach a listed grounding/bonding device, the
attachment must be made in conformance with the
grounding device manufacturer’s instructions.
Common hardware items such as nuts, bolts, star washers,
lock washers and the like have not been evaluated for
electrical conductivity or for use as grounding devices and
should be used only for maintaining mechanical connections
and holding electrical grounding devices in the proper
position for electrical conductivity. Such devices, where
supplied with the module and evaluated through the
requirements in UL 1703, may be used for grounding
connections in accordance with the instructions provided
with the module.
Ground the module in accordance with local requirements
and NEC Article 250 where applicable. Size and earth
ground conductor accordingly.
Earth conductors should be large enough for let-through
energy.
Methods to secure earth wires to PV module frame should
be mechanically sound to ensure electrical continuity at all
times.
When using a self-tapping screw to make bonding
connection ensure at least two full threads engage in the
metal.
Do NOT use bare copper grounding lug.
The following methods are certified for grounding the module.
For Canada; Grounding method must comply with Safety
Standard for Electrical Installations, Canadian Electrical
Code, Part 1. CSA C22.1
When using provided grounding holes on module frame
locate 4.2 +/- 0.2 mm diameter grounding holes shown in
Figure 3 that are marked by the grounding symbol. . The
flange on which the grounding hole is located

OPTXXX-##-4-1YY IEC & UL EN Suniva, Inc. SI&IM _9 Rev 9 Pa e 3
Grounding using Screw and Washer Assembly
Attach the grounding conductor to the module frame through at
least one of the two grounding holes, See Figure 3.
Figure 3: Grounding Hole Location
Wrap an un-insulated portion of 10 to 12 AWG copper
grounding wire around the grounding screw between two
0.2”ID x 0.394”OD x 0.030” (5 x 10 x 1 mm) stainless steel flat
washers, ensuring any exposure part of the wire is covered by
insulation. Connect a #10-32× 0.5 in (12.7 mm) stainless steel
screw and flat washers to the grounding hole. Use a flat head
screwdriver to tighten them applying a torque of 18 in-lb (2 N-
m). Flat washer should be cupped side in towards the
grounding wire. To avoid corrosion of dissimilar metals ensure
washer is between grounding wire and aluminum frame. See
Figure 4
Figure 4: Grounding with #10-32 Screw
(Or) Use of Tyco SolKlip Grounding Clip Assembly
The grounding clip manufactured by Tyco Electronics Corp.
(Part number: 1954381-1) is UL listed and designed for module
grounding applications using a solid 10 to 12 AWG un-
insulated ground wire. It is attached to grounding hole on
module frame, Figure 3, by an integrated, 10-32 in. self-tapping
screw. Place the grounding clip onto the frame, making sure
that the screw straddles the grounding hole. Using a No. 2
cross–recessed screwdriver, thread the screw into the hole
until the head is flush with the base and the base is flush with
the frame, then tighten the screw with another 1/4 to 1/2 turn.
Recommended torque is between 20 in-lb (2.3 N-m) for screw.
Insert the wire into the wire slot. Press down on both ends of
the wire (the wire slot will cause the wire to form a slight
curve). Manually, or using channel lock pliers, push the slider
over the base until it covers the base. This will terminate the
wire.
Figure 5: SolKlip Grounding Diagram
(Or) Use of Tyco Solklamp Grounding Bolt Assembly
The grounding bolt manufactured by Tyco Electronics Corp.
(Part number: 2058791-1) is UL listed and designed for module
grounding applications using a solid 6 to 12 AWG un-insulated
ground wire. It is attached to grounding hole on module frame,
Figure 3, by an integrated, 8-32 in threaded post and nut.
Locate the grounding hole on the underside of the module
frame (1). Insert the threaded post end of the wire bolt into the
hole (2). Finger-tighten the hex washer nut onto the threaded
post (3). Position the grounding wire into the wire slot (4).
Finger-tighten the nut onto the wire slot end until wire is
compressed (5). Using a 9/16” open end wrench to hold the
hex body of the wire bolt, and using a 9/16” socket wrench,
tighten the mounting hex washer nut (3) to a torque of 25 in-lb
(2.82 N-m). While holding the hex body, use an 11-32” socket
wrench to tighten the wire binding hex nut (5) to a torque of 45
in-lb (5.08 N-m). See Figure 6.
Figure 6: SolKlamp Grounding Bolt Diagram
(Or) Use of Self Tapping Grounding Lug
The grounding bolt manufactured by Ilsco (Part number: GBL-
4DBT) and bolt manufactured by Burndy (Part number:
CL501TN) are UL listed and designed for module grounding
applications using a solid 4 to 14 AWG un-insulated ground
wire. Locate module grounding hole, Figure 3. Assemble a #
10 stainless steel star washer (1) and #10-32 self-tapping
screw (2) through grounding lug (1) and into the module
grounding hole until washer and lug are flush with frame as
shown in Figure 7. Using a 5/16 in. open ended wrench to
tighten the screw (2) another ¼ to ½ turn with recommended
torque between 20 and 25 in-lb (2.3 and 2.8 N-m). Insert
grounding wire into conductor slot of lug and tighten threaded
set screw using a 5.5 x 0.8 mm (
3
/
16
x 0.025 in.) flat headed
driver to the torque specified in Table 1 to compress the
conductor.
Figure 7: Self Threaded Grounding Lug: Grounding Diagram
Tightening Torque Guide for Conductor (#14 - #4 Cu Only)
Conductor Size Tightening Torque
#14 - #10 35 in-lb (4.0 N-m)
#8 40 in-lb (4.5 N-m)
#6 - #4 45 in-lb (4.1 N-m)
Table 1: Torque Guide for Conductor in Grounding Lug

OPTXXX-##-4-1YY IEC & UL EN Suniva, Inc. SI&IM _9 Rev 9 Pa e 4
(Or) Use of Grounding Lug with Nut
The grounding bolt manufactured by Burndy (Part number:
CL501TN) is UL listed and designed for module grounding
applications using a solid 4 to 14 AWG un-insulated ground
wire. Locate module grounding hole, Figure 3. Using a 5/16
open ended wrench, thread #10-32 self-threading screw
through the grounding hole to open up the hole size and
remove. Assemble a #10-32 bolt (2) through the grounding lug
(1) and into the module grounding hole. Install a # 10 stainless
steel star washer (3) and hex nut (4) around the frame until
washer and lug are flush with frame, as shown in figure 8.
Using two 5/16 in. open ended wrenches to tighten the screw
(2) and bolt (4) another ¼ to ½ turn with recommended torque
between 20 and 25 in-lb (2.3 and 2.8 N-m). Insert grounding
wire into conductor slot of lug and tighten threaded set screw
using a 5.5 x 0.8 mm (
3
/
16
x 0.025 in.) flat headed driver to the
torque specified in Table 1 to compress the conductor.
Figure 8: Grounding Lug with Nut: Grounding Diagram
(Or) Use of WEEBs and Associated Racking
Cat. No. Racking System Torque
WEEB-DMC DP&W Power Rail 10 ft-lb (13.5 N-m)
WEEB-PMC SnapNrack 15 ft-lb (20 N-m)
Table 2: WEEB and Racking Guide
Listed WEEB devices intended for use in bonding PV modules
to mounting structures may be used for grounding as
described in the NEC or CEC accordingly. Prior to installation,
all bolts that employ bonding and grounding hardware shall
have general purpose anti-seize applied onto the bolt threads.
Install the WEEB onto the midclamp of racking hardware to
bond PV module frames to mounting rail in accordance with
the layout specified in the Burndy installation manual for the
pertinent racking systems. Pre-assemble WEEB-DMC on to
PD&W midclamp assembly as showing in Figure 9. Pre-
assemble WEEB-PMC onto SnapNRack midclamp assembly
as shown in Figure 10. Ensure both sides of the modules are
positioned against midclamp and WEEB teeth are underneath
module frames. Hand tighten fasteners to keep modules in
place since WEEBs are intended for one time use only and
cannot be reused. When position is finalized, tighten hardware
to torque specified in Table 2. Using the approved hardware,
install the WEEB Lug at the end of each rail to connect the
equipment ground conductor to the system. Each nut/bolt
combination that installs a Lug and Bonding Jumper shall be
tightened to the torque specified in the Burndy manual. Lug is
capable of securing one 6 AWG or two 10/12 AWG copper
conductors. Tighten bolt securing copper conductor to 7 ft-lb
(10 N-m) torque. For WEEB details, refer to the Burndy
Installation Manual.
Figure 9: WEEB-DMC Assembly
Figure 10: WEEB-PMC Assembly
Wiring
Connect modules using the supplied connectors in series or
parallel configurations according to the “+” positive or “-
”negative.
Use only same type of connector, to ensure the reliability of
the electrical connection.
For conductor utilize suitable “Wet or Dry” type sunlight
resistant cable (PV-Wire, or USE-2 type) with temperature
rating of 90 ⁰C or higher and sized 12 AWG or larger.
Paralleled configurations may require greater wire size to
accommodate increase current. Ensuring proper conductor
sizing is the responsibility of the installer.
Maintain a minimum bending radius of 50 mm at all locations
along the cable. Pay particular attention to the exit point from
the junction box and interconnection point between modules.
Junction Box
Do not open the junction box or change inter-module wiring.
All wiring connections are made in the factory and doing so
may void the warranty.
Verify junction box lid is firmly closed when installing panel.
Do not alter the connectors. Doing so will void the warranty.
Bypass Diodes
3 Schottky type bypass diodes are pre-assembled in each
module in parallel with cell strings.
Do not uninstall these diodes.
Bypass Diode Ratings: V
RRM
: 40 V, I
FAV
: 16 A @75 ⁰C
or V
RRM
: 40 V, I
FAV
: 20 A @ 95 ⁰C
Series/Parallel Configurations
Series or Parallel configurations must be restricted to a
maximum system voltage of 1000 VDC (UL) or 1000 VDC
(IEC).
Voltage and current are temperature dependent and
systems should be designed to allow for variations due to
local conditions.
The voltage of modules in series connections will be equal to
the sum of the individual voltages.
The current of modules in parallel connections will be equal
to the sum of the individual currents.

OPTXXX-##-4-1YY IEC & UL EN Suniva, Inc. SI&IM _9 Rev 9 Pa e 5
Refer to the electrical characteristics for the values of Isc
and Voc.
Series and Parallel interconnection restrictions
At standard conditions (AM1.5G, 25⁰C) the number of
allowable modules in series is equal to the maximum system
voltage divided by the Open Circuit voltage. The number of
modules in series should be constrained by the expected
minimum ambient temperature, module Voc temperature
coefficient (), and module Voc. Suniva recommends the
following to allow for a minimum ambient temperature of -40
C.
To prevent an open circuit voltage in excess of 1000 V:
For OPTXXX-60 Series modules: 21
For OPTXXX-72 Series modules: 17
To prevent an open circuit voltage in excess of 600 V:
For OPTXXX-60 Series modules: 12
For OPTXXX-72 Series modules: 10
Overcurrent protection (such as fuses) must be used when
connecting three (3) or more strings in parallel.
Over Current Protection
Series or parallel connections of modules or strings must be
provided adequate over current protection such as a
recognized circuit breaker or fuse meeting minimum
requirements listed in the Product Information section of this
manual and be certified and properly rated. System design
and protection for any series/parallel configuration must be
verified by a certified engineer and is the responsibility of the
system integrator as currents may exceed 1.25 times I
SC
under some conditions.
Disconnection Under Load
Do NOT disconnect or connect module under load.
Modules will produce electricity even under low light
conditions. Treat modules as if they are live electrical
equipment.
To avoid electric shock and injury, completely cover the front
of the module with an opaque material and disconnect the
module from all electrical connections before disconnecting
or connecting module wiring.
Maintenance
Maintenance is recommended to ensure optimal performance:
Depending on local conditions, periodically inspect and clean
the surface of the module with water and a soft cloth or
sponge when the modules surface becomes dirty and rain
water is insufficient to remove dirt/debris.
Never clean the modules during the middles of the day when
the glass is hot to avoid injury.
Never scratch or rub away any dirt when the modules are
dry.
Check the electrical and mechanical connections annually to
ensure all the connections are secure, tight, clean and free
of corrosion.
To prevent PV module frame damage due to the formation of
ice-dams, excessive amounts of snow and ice should be
cleaned off the PV modules and not allowed to accumulate
and remain on the modules indefinitely
Disclaimer of Liability
Suniva does not assume responsibility and expressly disclaims
liability for loss, damage or expense arising out in any way
connected with installation, operation, use or maintenance by
using this manual. Suniva assumes no responsibility for any
infringement of patents or other rights of third parties that may
result from use of the module. No license is granted by
implication or otherwise under any patent or patent rights.
Suniva reserves the right to make changes to the product,
specifications or this manual without prior notice.
Electrical Characteristics by Module Type
For OPTXXX-60 Series modules ending in 100
Module ID P
MP
[W]
V
OC
[V]
I
SC
[A]
V
MP
[V]
I
MP
[A]
OPT240-60-4-1YY
240
37.2
8.84
28.9
8.30
OPT245-60-4-1YY
245
37.5
8.89
29.4
8.35
OPT250-60-4-1YY
250
37.7
8.98
29.6
8.44
OPT255-60-4-1YY
255
37.9
9.05
30.0
8.50
OPT260-60-4-1YY
260
38.1
9.08
30.2
8.60
OPT265-60-4-1YY
265
38.3
9.12
30.7
8.64
OPT270-60-4-1YY
270
38.5
9.15
31.2
8.68
OPT275-60-4-1YY
275
38.6
9.25
31.5
8.74
OPT280-60-4-1YY
280
38.7
9.3
31.7
8.84
OPT285-60-4-1YY
285
38.9
9.71
31.9
8.93
For OPTXXX-60 Series modules ending in 101, 1B0 or 1B1
Module ID P
MP
[W]
V
OC
[V]
I
SC
[A]
V
MP
[V]
I
MP
[A]
OPT235-60-4-1YY
235
37.1
8.73
28.7
8.18
OPT240-60-4-1YY
240
37.3
8.76
29.2
8.23
OPT245-60-4-1YY
245
37.6
8.84
29.5
8.30
OPT250-60-4-1YY
250
37.8
8.90
30.0
8.34
OPT255-60-4-1YY
255
38.1
8.96
30.2
8.45
OPT260-60-4-1YY
260
38.3
9.01
30.5
8.52
OPT265-60-4-1YY
265
38.3
9.12
30.7
8.64
OPT270-60-4-1YY
270
38.5
9.14
31.0
8.70
OPT275-60-4-1YY
275
38.6
9.28
31.5
8.74
OPT280-60-4-1YY
280
38.7
9.3
31.7
8.84
OPT285-60-4-1YY
285
39.2
9.61
32.2
8.84
For OPTXXX-72 Series modules ending in 100
Module ID P
MP
[W]
V
OC
[V]
I
SC
[A]
V
MP
[V]
I
MP
[A]
OPT290-72-4-100
290
45.0
8.76
35.2
8.23
OPT295-72-4-100
295
45.2
8.84
35.5
8.30
OPT300-72-4-100
300
45.5
8.90
36.0
8.34
OPT305-72-4-100
305
45.6
9.00
36.1
8.45
OPT310-72-4-100
310
45.7
9.06
36.2
8.56
OPT315-72-4-100
315
45.9
9.10
36.5
8.62
OPT320-72-4-100
320
46.1
9.20
36.8
8.69
OPT325-72-4-100
325
46.3
9.27
37.0
8.77
OPT330-72-4-100
330
46.5
9.30
37.5
8.80
OPT335-72-4-100
335
45.9
9.66
37.7
8.89
OPT340-72-4-100
340
46.0
9.78
37.8
8.99
For OPTXXX-72 Series modules ending in 101, 1B0 or 1B1
Module ID P
MP
[W]
V
OC
[V]
I
SC
[A]
V
MP
[V]
I
MP
[A]
OPT285-72-4-1YY
285
44.9
8.64
35.1
8.12
OPT290-72-4-1YY
290
45.1
8.71
35.4
8.18
OPT295-72-4-1YY
295
45.5
8.78
35.8
8.23
OPT300-72-4-1YY
300
45.6
8.85
36.1
8.30
OPT305-72-4-1YY
305
45.7
8.90
36.2
8.42
OPT310-72-4-1YY
310
45.8
8.79
36.4
8.51
OPT315-72-4-1YY
315
45.9
9.05
36.6
8.62
OPT320-72-4-1YY
320
46.2
9.08
36.9
8.68
OPT325-72-4-1YY
325
46.4
9.12
37.1
8.76
OPT330-72-4-1YY
330
46.6
9.15
37.5
8.80
Revision History
Revisio
n
Date Notes
1 6.14.12 Release
2 3.25.13 Added 270 W Bin Class, Added 1000 V UL.
3 4.19.13 Added 270, 315, 320, 325, 330 Bin Class
4 1.27.14 Clarified connector language
5 8.25.2014 Expanded Equipment Grounding section, Added 275
& 280 Bin Class
6 1.7.15 Updated fire classification text.
7 4.13.2015 Added 280 bin class
8 6.4.2015 Added Maintenance notes
9 8.17-15 Added 285, 335, 340 Bin classes. Revised
Maintenance text notes, Updated fire class Type 2,
added Long-term storage text.
This manual suits for next models
87
Table of contents
Popular Solar Panel manuals by other brands

AEROCOMPACT
AEROCOMPACT CompactPITCH XM-P Assembly instructions

Clas Ohlson
Clas Ohlson LS1024EU quick start guide

Epever
Epever LORA 433A/470A quick start guide

Solfex
Solfex IRC 2.1 System installation, commissioning and maintenance manual

LEJ LINE
LEJ LINE LSK-JC-2V Installation and maintenance manual

FARMDROID
FARMDROID FD20 Original user manual

Wasserstein
Wasserstein Solar Panel For Blink XT and Blink XT 2 Cam user manual

LG
LG N1T-A5 Series installation manual

Van Der Valk
Van Der Valk ValkBox3 installation manual

Arlo
Arlo solar panel quick start guide

Thermo King
Thermo King Ingersoll Rand ThermoLite EMEA 36W Installation

SCHOTT solar
SCHOTT solar POLY 1 Series instructions