Instructions for the hand-held terminal
of the fan motor control system, TBLZ-4-75
SILVER C
1. General
The hand-held terminal TBLZ-4-75 is a control panel with
touch screen that is used to set motor parameters on
SILVER C. The hand-held terminal communicates with the
motor control system via a Modbus interface.
2. Installation
The hand-held terminal can be mounted on a flat surface
using screws or magnets.
There is a keyhole slot at the rear of the hand-held termi-
nal for mounting with a screw, which is inserted on a flat
surface, see the diagram to the right. Use a screw with
a maximum diameter of 3.5 mm and a max. length of 9
mm.
The black shock-absorbing casing comes with two mag-
nets that make it possible to hang the hand-hand terminal
on a vertical, flat and metallic surface.
3. Technical data
Supply voltage From the motor control
system's wiring terminal
Modbus RTU 1 x RJ12 (RS485)
Enclosure class IP21
Relative humidity 0 – 95 % (non-condensing)
Ambient temperature -10... +40 °C (in operation)
Dimensions without
shock-absorbing casing 80 x 121 x 42 mm
Dimensions with
shock-absorbing casing 86 x 127 x 51 mm
Max. power consumption 900 mW

EN.TBLZ475.190701
Swegon reserves the right to alter published specifications without notice.
2 www.swegon.com
4. Function
4.1 Start screen
The motor control system’s function selector switch should
normally be set to position 1 for control 0-10 V, but if the
fan is to be controlled or settings are to be made via the
hand-held terminal, the function selector switch should be
set to position 0.
If the screen lock is enabled, press on the screen once to
open the start screen.
The start screen provides access to basic functions, for
example, fan speed, type of drive, supplied power and
type of control. Enabled alarms and warnings are shown
at the top of the screen. An alarm clock shows that an
alarm is enabled. A warning sign shows if there is an
active warning. Press the alarm clock or warning sign to
navigate to the list of alarms/warnings.
To change set point values, press “Set point” on the start
screen.
The fan icon shows if the fan is running or stopped. Press
the fan icon to start or stop the fan.
4.2 Menus
To access the settings menu, where you can read and
change settings, press on the menu icon in the top right
corner of the start screen.
The hand-held terminal’s setting menu contains the fol-
lowing:
• Status:
Motor control system’s operating parameters can be
read.
• Drive setup:
Motor control system’s operating parameters can be
set.
• User settings:
User specific settings can be changed.
• I/O:
Digital inputs and outputs can be configured.
• Warnings and alarms:
Active warnings and alarms can be read.
• Modbus:
Modbus settings for motor control system
• Configuration:
The motor control system can be configured.
• Software:
The software version can be read.

EN.TBLZ475.190701
Swegon reserves the right to alter published specifications without notice. www.swegon.com 3
4.3 Set point
The set point screen can be used to change set point
values. Use the numerical keypad displayed to select set
points and press OK to confirm the new set point.
Factory and user settings are stored in the motor control
system. The settings are preserved in the memory even
if the mains voltage is switched off or if the hand-held
terminal is removed.
4.4 Modbus communication
The hand-held terminal communicates with the motor
control system via Modbus RTU, with the following
Modbus settings:
• Autodetect = Autoscanning to find the address, must
be set to On.
• Address = Modbus address.
• Baud rate = 38.4
• Parity = None.
• Stop bits = 1/2.
The motor control system has two Modbus settings, one
preset and one alternative.
Preset Modbus setting:
• Address = 54.
• Baud rate = 38.4
• Parity = Even.
• Stop bits = 2.
Alternative Modbus setting. Set at the from the factory:
• Address = 0.
• Baud rate = 115.2 kbps.
• Parity = Even.
• Stop bits = 2.
It is possible to change the alternative Modbus setting
with the help of a Modbus register.
The motor control system automatically detects whether
communications occur via the preset or alternative
Modbus setting. If no communications occur via the
preset Modbus setting after 10 seconds the motor control
system searches for the alternative Modbus setting and
vice versa.
4.5 Change Modbus address
Wait 10 seconds so that settings can be saved before the
hand-held terminal is switched off.
The motor control system will search for the preset
Modbus setting for 10 seconds before searching for the
alternative Modbus setting.
4.6 Shock-absorbing casing
The hand-held terminal is equipped with a silicone casing
that protects against shocks, oils and dirt.

EN.TBLZ475.190701
Swegon reserves the right to alter published specifications without notice.
4 www.swegon.com
4.7 Menu tree
The highest level for the hand-held terminal’s menu tree
is shown below. The settings menu contains eight sub-
menus, some of these submenus in turn have their own
submenus.

EN.TBLZ475.190701
Swegon reserves the right to alter published specifications without notice. www.swegon.com 5
-V+
-Add. Pin2
-Bus B
-Bus A
-Gnd
-Add. Pin2
-Add. Pin2
-Bus B
-Bus A
-Gnd
-Add. Pin2
-V+
-Gnd
-Bus B
-Bus A
-Gnd
-V+
A
C
B
-
5. Electrical connections
5.1 Fan motor control system with integrated wiring terminals
For access, unscrew the bolts that secure the blue cover on the motor control system casing. Connect the hand-held
terminal to the motor control system's integrated wiring terminals, in Port “A“. Use the supplied bus cable.
6. Trouble shooting
Symptoms Cause Action
No values in the hand-held
terminal
– Display window off
The motor control system is switched off Start the motor control system
Modbus cable is defective Replace the Modbus cable
The RJ12 connector is not correctly connected Check the contact connections in both the hand-held termi-
nal and the motor control system.
Connect the RJ12 cable to Port "A" in the motor control
system.
5.2 Fan motor control system without integrated wiring terminals
Connect the hand-held terminal to contact “C“ in the junction box (installed on the side of the fan mounting frame).
Use the supplied bus cable.

EN.TBLZ475.190701
Swegon reserves the right to alter published specifications without notice.
6 www.swegon.com
Table of contents
Other Swegon Touch Terminal manuals
Popular Touch Terminal manuals by other brands

Bematech
Bematech SB8015A user manual

COBHAM
COBHAM Explorer 510 user manual

Pidion
Pidion BIP-5000 manual

Mitsubishi
Mitsubishi GOT MELSEC 800 Series user manual

Muller Elektronik
Muller Elektronik TRACK Guide II Installation and operating instructions

Beijer Electronics
Beijer Electronics X2 control 21 - B2 installation manual