System air FRQS-4 User manual

FRQS-4/10/16A
Frequency inverter with sine lter for 3 ~ fans
Operating Instructions
Speed controller with 0...10 V input for presetting the fan speed
Software version: D2732A from Version 1.03
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
english

Content
1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Structure of the operating instructions . . . . . . . . . . . . . . . . . . . . 4
1.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Exclusion of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Copyright . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Explanations of symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Product safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Requirements placed on the personnel / due diligence . . . . . . . 6
2.5 Start-up and during operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.6 Working on device / Hazards through “residual voltage” . . . . . . 6
2.7 Modifications / interventions in the device . . . . . . . . . . . . . . . . . 7
2.8 Operator’s obligation of diligence . . . . . . . . . . . . . . . . . . . . . . . . 7
2.9 Employment of external personnel . . . . . . . . . . . . . . . . . . . . . . . 8
3 Product overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1 Operational area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 Functional description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.4 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.5 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.6 Disposal / recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4.2 Minimum space requirement . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.3 Outdoor installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.4 Installation location for agriculture . . . . . . . . . . . . . . . . . . . . . . . 10
4.5 Temperature influences during commissioning . . . . . . . . . . . . . . 10
5 Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1 Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2 EMC-compatible installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2.1 Motor cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2.2 Control cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Operating Instructions FRQS-4/10/16A
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
2/27

5.2.3 Harmonics current for devices ≤ 16 A . . . . . . . . . . . . . . . 12
5.3 Mains connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.1 Line voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.2 Required quality attributes for the mains voltage . . . . . . . . . 12
5.3.3 Leakage current, securely attached, protective earth conductor
12
5.4 Residual-current-operated protective device . . . . . . . . . . . . . . . . 12
5.5 Inverter output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.5.1 Motor connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.5.2 Disconnection between controller and motor (repair switch) 13
5.5.3 U/f-characteristic curve . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.6 Motor protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.7 Analog input “E1” for setting fan speed . . . . . . . . . . . . . . . . . . . 15
5.8 Output voltage “10 V” ................................ 16
5.9 Voltage supply for external devices (+24V, GND) . . . . . . . . . . . . 17
5.10 Enable, Device ON / OFF (Digital In 1 D1) . . . . . . . . . . . . . . . 17
5.11 Relay outputs (K1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.12 Bypass circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.13 Potential at control voltage connections . . . . . . . . . . . . . . . . . . . 17
6 Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.1 Prerequisites for commissioning . . . . . . . . . . . . . . . . . . . . . . . . . 18
7 Diagnostics / Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
8.1.1 Max. load dependent on ambient temperature and line voltage.
24
8.2 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
8.2.1 Connection suggestion for several motors with motor protection
unit type STDT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.3 Dimensions [mm] . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.4 Manufacturer reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Operating Instructions FRQS-4/10/16A
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
3/27

1 General notes
1.1 Structure of the operating instructions
Before installation and start-up, read this manual carefully to ensure correct use!
We emphasize that these operating instructions apply to specific units only, and
are in no way valid for the complete system!
Use these operating instructions to work safely with and on the device. They contain
safety instructions that must be complied with as well as information that is required for
failure-free operation of the device.
Keep these operating insturctions together with the device. It must be ensured that all
persons that are to work on the device can refer to the operating instructions at any time.
Keep the operating instructions for continued use. They must be passed-on to all
successive owners, users and final customers.
1.2 Target group
The operating instructions address persons entrusted with planning, installation, com-
missioning and maintenance and servicing and who have the corresponding qualifica-
tions and skills for their job.
1.3 Exclusion of liability
Concurrence between the contents of these operating instructions and the described
hardware and software in the device has been examined. It is still possible that non-
compliances exist; no guarantee is assumed for complete conformity. To allow for future
developments, construction methods and technical data given are subject to alteration.
We do not accept any liability for possible errors or omissions in the information con-
tained in data, illustrations or drawings provided.
We accept no liability for damage caused by misuse, incorrect use, improper use or as a
consequence of unauthorized repairs or modifications.
1.4 Copyright
These operating instructions contain copyright protected information. The operating
instructions may be neither completely nor partially photocopied, reproduced, translated
or put on data medium without previous explicit consent. Infringements are liable for
damages. All rights reserved, including those that arise through patent issue or registra-
tion on a utility model.
2 Safety instructions
This chapter contains instructions to prevent personal injury and property damage.
These instructions do not lay claim to completeness. In case of questions and problems,
please consult our company technicians.
Operating Instructions FRQS-4/10/16A General notes
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
4/27

2.1 Intended use
The equipment is to be used solely for the purposes specified and confirmed in the
order. Other uses which do not coincide with, or which exceed those specified will be
deemed unauthorised unless contractually agreed. Damages resulting from such unau-
thorised uses will not be the liability of the manufacturer. The user will assume sole
liability.
Reading these operating instructions and complying with all contained instructions -
especially the safety notifications contained therein - are considered part of intended
use. To consider is also the manual of attached components. Not the manufacturer,
rather the operator of the device is liable for any personal harm or material damage
arising from non-intended use!
2.2 Explanations of symbols
Safety instructions are highlighted with warning triangles and are depicted
according to the degree of hazard as follows.
Attention!
General hazardous area. Death or severe injury or significant property damage can
occur if the corresponding precautions are not taken!
Danger due to electric current
Danger by dangerous, electric voltage! Death or severe injury can occur if the
corresponding precautions are not taken!
Information
Important additional information and advice for user.
2.3 Product safety
The device conforms to the state of the art at the time of delivery and is fundamentally
considered to be reliable. The device and its accessories must only be used in a flawless
condition and installed and operated in compliance with the assembly instructions and/or
operating instructions. Operating outside the device's technical specifications (
name
plate and attachment / technical data) can lead to a defect in the device and additional
damage!
In the case of a malfunction or a failure of the equipment check all functions with
alarms in order to prevent injury to persons or property. Note possibility of back-
up operation. If used in intensive animal environments, any malfunctions in the air
supply must be detected as soon as possible to prevent the development of a life-
threatening situation for the animals. The design and installation of the system
must comply with local regulations and directives. In Germany these include
DIN VDE 0100, the animal protection and the keeping of working animals ordi-
nance and the pig-keeping ordinance etc. Also note the instructions of AEL, DLG,
VdS.
Operating Instructions FRQS-4/10/16A Safety instructions
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
5/27

2.4 Requirements placed on the personnel / due diligence
Persons entrusted with the planning, installation, commissioning and maintenance and
servicing in connection with the frequency inverter must have the corresponding qual-
ifications and skills for these jobs.
In addition, they must be knowledgeable about the safety regulations, EU directives,
rules for the prevention of accidents and the corresponding national as well as regional
and in-house regulations. Personnel to be trained or instructed and apprentices are only
permitted to work on the device under the supervision of an experienced person. This
also applies to personnel undergoing general training. Comply with the legal minimum
age.
This device is not intended to be used by people (including children) who have restricted
mental, sensory or intellectual abilities or who have a lack of experience and/or knowl-
edge.
2.5 Start-up and during operation
Attention!
•During commissioning, unexpected and hazardous conditions can arise in the entire
installation due to defective adjustments, defective components or incorrect electrical
connections. Remove all persons and objects from the hazardous area.
•During operation, the device must be closed or installed in a control cabinet. Fuses
may only be replaced by new ones and must not be repaired or bypassed. The data
for the maximum line fuse are to be considered absolutely (
Technical data). Use
only fuses specified in schematic diagrams.
•Any faults detected in the electric system/modules/operating equipment must be
corrected immediately. If these faults are not corrected, the device/system is poten-
tially very dangerous. The device/system must therefore not be operated when it is
faulty.
•Pay attention to smooth, low vibration running of the motor/fan, the appropriate
instructions in the drive documentation must be observed!
2.6 Working on device / Hazards through “residual voltage”
Information
Mounting, electrical connection, and start-up operation may only be carried out by an
electrical specialist in accordance with electrotechnical regulations (e.g. EN 50110 or
EN 60204)!
Danger due to electric current
•It is generally forbidden to carry out work on electrical live parts. Protection class of
the device when open is IP00! It is possible to touch hazardous voltages directly.
•The safe isolation from the supply must be checked using a two-pole voltage
detector.
•Even after disconnecting the mains voltage, life-threatening charges can appear
between the protective ground “PE” and the mains connection.
•The protective earth is conducting high discharge currents (dependent on the switch-
ing frequency, current-source voltage and motor capacity). Earthing in compliance
Operating Instructions FRQS-4/10/16A Safety instructions
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
6/27

with EN specifications shall therefore be observed even for testing and trial conditions
(EN 50 178, Art. 5.2.11). Without earthing, dangerous voltages can be present on the
motor housing.
Waiting period at least 3 minutes!
Through use of capacitors, danger of death exists even after switching off the device
through directly touching the energized parts or due to parts that have become energized
due to faults.
It is only permitted to remove the housing cover after waiting for 3 minutes once the line
supply cable has been shut down. Should measurement or adjustment work be unavoid-
able on the opened unit while still powered, then this may only be performed by qualified
personnel acquainted with the thereby associated hazards.
Attention!
Automatically restart after a power failure or mains disconnection!
2.7 Modifications / interventions in the device
Attention!
For reasons of safety, no unauthorized interventions or modifications may be made on
the device. All planned modifications must be authorized by the manufacturer in writing.
Only use the manufacturer’s original spare parts / wearing parts / accessories. These
parts are specially designed for this device. If parts from other sources are used, there is
no guarantee that they are designed and produced for the proper loads and with the
required level of safety.
Parts and special equipment not supplied by the manufacturer are not approved for use.
2.8 Operator’s obligation of diligence
•The contractor or owner must also ensure that the electric systems and equipment
are operated and maintained in accordance with electro-technical regulations.
•The owner is obliged to ensure that the device is operated in perfect working order
only.
•The device may only be used as intended (
“Application”).
•You must periodically examine the safety equipment for their properly functioning
condition.
•The assembly instructions and/or operating instructions are always readily available
at the location where the device is being used, are complete and are in legible
condition.
•These persons are regularly instructed in all applicable questions regarding occupa-
tional safety and environmental protection and are knowledgeable regarding the
assembly instructions and/or operating instructions and, especially, are familiar with
the safety instructions contained therein.
Operating Instructions FRQS-4/10/16A Safety instructions
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
7/27

•All safety and warning notices attached to the device are never removed and remain
legible.
2.9 Employment of external personnel
Maintenance and service work are frequently carried out by external employees who
often do not recognize the specific situations and the thus resulting dangers.These
persons must be comprehensively informed about the hazards in their area of activity.
You must monitor their working methods in order to intervene in good time if necessary.
3 Product overview
3.1 Operational area
Frequency inverter designed for a stepless control of fans without additional (electro-
magnetic) motor noise.
By using the integrated all-pole effective Sine filter (phase to phase and phase to
ground), an absolute parallel control of fans without risk of damage for motors is
possible. Screened motor cables are not required!
Only suitable for drives with low set-off torque (e.g.: fans or pumps).
3.2 Functional description
The frequency inverters generate their 3~ output with variable voltage and frequency
from the three-phase mains on the input.
The devices are constructed in accordance with the general requirement in EN 61800-2
for adjustable speed electrical power systems and is intended for one-quadrantdrives.
The output frequency is set by an external signal (0 - 10 V, 0 - 20 mA, PWM).
3.3 Maintenance
The device must be checked for soiling and, if necessary, cleaned in periodic intervals.
3.4 Transport
•The device is packed ex factory to suit the transport method previously agreed.
•Always use the original packaging materials when transporting the device.
•Avoid shocks and impacts to the device during the transport.
•During manual handling the human lifting and carrying restrictions must be observed
and adhered to.
Operating Instructions FRQS-4/10/16A Product overview
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
8/27

3.5 Storage
•The device must be stored in its original packaging in a dry and weather-proof room.
•Avoid exposure to extreme heat and cold.
•Avoid prolonged storage; we recommend a maximum of one year (consult the
manufacturer before starting if stored for longer).
3.6 Disposal / recycling
Disposal must be carried out professionally and environmentally friendly in accordance
with the legal stipulations.
4 Mounting
4.1 General notes
Attention!
The following points must be complied with during the mechanical installation to avoid
causing a defect in the device due to assembly errors or environmental influences:
•Before installation remove the device from the packing and check for any possible
shipping damage!
•Assemble the device on a clean and stable base. Do not distort during assembly! Use
the appropriate mounting devices for proper installation of the unit!
•A mounting on vibrating base is not permissible, if no data to the vibration strength is
made (
Technical data)!
•When mounted onto lightweight walls, there must be no impermissibly high vibrations
or shock loads. Any banging shut of doors that are integrated into these lightweight
walls, can result in extremely high shock loads. Therefore, we advise you to decouple
the devices from the wall.
•Do not allow drilling chips, screws and other foreign bodies to reach the device
interior!
•Maintain the stated minimum clearances to ensure unobstructed cooling- air feed as
well as unobstructed outgoing air discharge (
minimum space requirement)!
•The device should be installed in a location where it will not be disturbed, but at the
same time can be easily accessed!
•Depending on the housing model cut off necessary cable inlets respectively to the
cable diameter. Or alternative use cable inlet for cable glands. Metal sheet housings
are supplied with stoppers. Any cable ducts openings not used must be sealed!
•Care must be taken to avoid direct radiation from the sun!
•The device is designed for vertical installation (cable inlet down). A horizontal or
reclined installation is only permissible after technical release of the manufacturer!
•Be sure to observe proper heat dissipation (
Technical data, heat dissipation).
Operating Instructions FRQS-4/10/16A Mounting
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
9/27

4.2 Minimum space requirement
In order to ensure sufficient ventilation of the device, clearance on all sides of at least
50 mm has to be maintained to the housing walls, switch cabinet doors, wiring ducts, etc.
The same clearance applies to the installation of several devices next to each other.
When installing several devices on top of each other, the danger of reciprocal heating
exists. This layout is only then permissible when the air suctioned from the upper unit
does not become warmer than the permissible ambient temperature (
Technical data).
I.e., a correspondingly larger clearance or thermal shielding is required.
4.3 Outdoor installation
Outdoor installation is possible up to -20 °C when the controller supply is not switched
off. Installation must be protected from the effects of weather as much as possible,
including protection from direct sunlight!
4.4 Installation location for agriculture
In order to avoid damage caused by ammoniac vapours, the controller shall not be
installed in the stable, but rather in an outhouse wherever possible.
4.5 Temperature influences during commissioning
Avoid condensation in the controller and functional faults attributable to condensation by
storing the controller at room temperature!
Operating Instructions FRQS-4/10/16A Mounting
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
10/27

5 Electrical installation
5.1 Safety precautions
Danger due to electric current
•Work on electric components may only be carried out by trained electricians or
by persons instructed in electricity under the supervision of an electrician in
accordance with electrical engineering regulations.
•The 5 electrical safety rules must be observed!
•It is forbidden to carry out work on electrically live parts. Even after disconnec-
tion, the dc-link is still live. Always wait at least 3 minutes.
•Other measures may be necessary to achieve safe electrical isolation.
•A second person must always be present when working on energized parts or
lines who disconnects in case of emergency.
•Inspect electrical equipment periodically: retighten loose connections – imme-
diately replace damaged lines and cables.
•Always keep switch cabinets and all electrical supply facilities locked. Access
is only allowed for authorized persons using a key or special tool.
•Operating the device with the housing cover removed is prohibited because
energized, exposed parts are present inside the device. Disregarding this regu-
lation can lead to severe personal injury.
•For metal cable inlets the necessary protective earth connection to the bottom
of the housing is made by screws. The device may only be started up when
these screws are fitted properly.
•The device owner is responsible for the EMC of the entire plant according to the
locally applicable standards.
•Never clean electrical equipment with water or similar liquids.
Information
The respective connections are represented in the enclosure of this manual (
Connection diagram)!
5.2 EMC-compatible installation
5.2.1 Motor cable
The applicable standard for interference emissions is EN 61000-6-3. Compliance with
this standard is achieved through the use of an unscreened motor feed cable.
5.2.2 Control cables
Pay attention to sufficient distance from powerlines and motor wires to prevent interfer-
ences. The control cable may not be longer than 30 m. Screened control cables must be
used when the cable length is longer than 20 m. When using a shielded cable connect
the shielding to one side only, i.e. only to the control unit with the protective ground (keep
cable short and with as little inductance as possible!).
Operating Instructions FRQS-4/10/16A Electrical installation
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
11/27

5.2.3 Harmonics current for devices ≤ 16 A
According to EN 61000-3-2 these devices are to be classified as “professional” devices.
The application is therefore limited to use by trade, certain vocations or industries.
Connection to a low voltage supply (public networks) is allowed insofar as this has been
clarified with the respective energy supply company responsible.
5.3 Mains connection
5.3.1 Line voltage
Power from the mains is connected to terminals: PE, L1, L2, L3. Here, it must be strictly
observed that the mains voltage lies within the allowable tolerance specifications (
Technical data and nameplate affixed to the side).
Danger due to electric current
Not suitable for IT system!
5.3.2 Required quality attributes for the mains voltage
Danger due to electric current
The mains voltage must comply with the EN 50160 quality characteristics and the
defined standard voltages in IEC 60038!
5.3.3 Leakage current, securely attached, protective earth conductor
Danger due to electric current
The maximum leakage current depends on the type of device and the connected
mains voltage (
Technical Data). With regard to fixed connection and the type of
PE conductor connection, the specification for the leakage current must be ob-
served under consideration of the locally valid standards (for Europe
EN 50178
Section 5.2.11 or 5.3.2.1 etc.).
Minimum cross-section for PE conductor for fixed connection 1.5 mm
2
!
5.4 Residual-current-operated protective device
Danger due to electric current
For an installation of r.c.d. protection, it shall be observed that this must be of
“universal-current sensitivity” (Type B). In accordance with EN 50 178, Section.
5.2. other types of current-operated protective devices may not be used. To ensure
as high a degree of reliability as possible , we recommend a tripping current of
300 mA.
Operating Instructions FRQS-4/10/16A Electrical installation
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
12/27

5.5 Inverter output
5.5.1 Motor connection
The motor leads are connected to the terminals: PE, U, V, W. Several fans can be
connected to the controller-the maximum total current of all motors must not exceed the
current rating for the controller.
Information
•It is recommended that a separate motor protection unit be foreseen for each fan.
•For motors with thermistors “TP” (PTC thermistor) e.g. type U-EK230E
•For motors with thermostats “TB” (thermal contacts) e.g. type STDT16 or AWE-SK (
Enclosure: Circuit suggestion for several motors with motor protection unit type
STDT.)
5.5.2 Disconnection between controller and motor (repair switch)
Ideally, a repair switch should be installed before the controller (supply line discon-
nect).
In the case of complete disconnection (entire load) after the controller, the enable
(controller OFF / ON) must be disconnected simultaneously. I.e., an additional control
contact is needed. Switching on the motor while simultaneously issuing the enable (ON)
achieves secure energizing with low saturation of the controller.
Attention!
When switching on the motor plus existing release: under certain circumstances, this can
occur under full modulation of the controller.
Operating Instructions FRQS-4/10/16A Electrical installation
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
13/27

5.5.3 U/f-characteristic curve
Diagram setting signal and U/f curve (quadratic)
Fout [Hz]
Fmax = 50 Hz
01.02.2013
v_u_f_fcon_basic_setsig.vsd
1 2 34 5 6 7 8 910
Analog In 1
045 50
403530
25
2015
10
5
2 4 68 10 12 14 16 18 20
0...10 V
0...20 mA
10 20 30 40 50 60 70 80 90 100 0...100 % PWM
Fedge = 48.5 Hz
Uout
100 %
0.5
1
5
Ustart = 0 %
Foff
Fon
Analog In: Speed setting signal (0 - 10 V, 0...20 mA, 0...100 % PWM)
Fout: Output frequency
Uout: Output voltage
Ustart: Start-up voltage
Foff: Shutdown Freq.
Fon: Switch on Freq.
Fedge: Edgefrequency
Fmax: Maximum frequency
5.6 Motor protection
Motor protection is possible by connecting thermostats “TB” or thermistors “TP”.
The jumper “J1” in the connection space must be plugged according to the used thermal
protectors.
Motor with thermistors “TP”
For motor with thermistors “TP” jumper plugged at top (factory setting).
A maximum of six individual thermistors (DIN 44081 or DIN 44082) may be connected
in series to a single device.
J1
TP
Motor with thermostats “TB”
For motor with thermostats “TB” the jumper “J1” must be plugged at the bottom.
J1
TB
Operating Instructions FRQS-4/10/16A Electrical installation
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
14/27

When a connected thermostat or thermistor responds (interruption between the two
terminals “TB/TP”) the device switches off and does not switch back on.
Relais “K1” is de-energized, terminals “13” - “14” interrupted. The internal signal lamp
flashes in code
|
15
|
(
Diagnostics / faults).
Possibilities for re-starting after the drive has cooled down (terminals “TB/TP”
bridged) by:
•By switching the mains voltage off and then on again.
•Via a digital input for remote control (ON/OFF enable).
Danger due to electric current
An outside voltage may never be connected to the terminals “TB/TP” and/or!
5.7 Analog input “E1” for setting fan speed
The device has an analog input for setting the fan speed. Connection “E1” / “GND”
(Analog In 1).
The internal jumpers “E1.1” and “E1.2” are factory set in the position for a 0...10 V speed
setting signal.
The appropriate jumper positions must be observed for a 0...20 mA signal or a PWM
signal.
Possibilities for speed setting
0...10 V (factory setting)
Control via external setting signal 0...10 V
or
Speed setting by external potenziometer (10 kΩ) at terminals “+10 V” and “GND” pick of-off at
terminal “E1”.
E1 D1 GND
0...10 V
+
Analog In 1
E1,1 E1,2
VE1 D1 GND 10V
Analog In 1
10 V DC Out
10 kΩ
30.08.11
i_jumper_if_basic_0_10v.eps
Operating Instructions FRQS-4/10/16A Electrical installation
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
15/27

0...20 mA
Control via external setting signal 0...20 mA
E1 D1 GND
0...20 mA
+
Analog In 1
E1,1 E1,2
mA
31.01.12
i_jumper_if_basic_0_20
0...100 % PWM
Control via external setting signal PWM
E1,1 E1,2
PWM E1 D1 GND 10V
Analog In 1
10 V DC Out
31.01.12
i_jumper_if_basic_pwm.eps
24V
24 V DC Out
24 V
15...28 V
+
-
GND
E1
E1,1 E1,2
PWM
(10 V)
E1 D1 GND 10V
Analog In 1
10 V DC Out
24V
24 V DC Out
PWM
f = 1...10 kHz
10 kΩ
Danger due to electric current
•Do not replug the jumper under voltage, observe the safety instructions!
•Make sure the signal has the correct polarity!
•Never apply line voltage to analog inputs!
5.8 Output voltage “10 V”
Voltage supply e.g. for speed setting by external potentiometer.
Connection: “10 V” - “GND” (max. load
Technical data und connection diagram).
It is not permissible to connect outputs of several devices to each other!
Operating Instructions FRQS-4/10/16A Electrical installation
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
16/27

5.9 Voltage supply for external devices (+24V, GND)
A voltage supply is integrated for external devices e. g. a sensor (max. current load
technical data).
In case of overload or short circuit (24 V – GND), the external power supply is shut down
(multi-fuse). The device performs a “Reset” and continues operation.
It is not permissible to connect outputs of several devices to each other!
5.10 Enable, Device ON / OFF (Digital In 1 D1)
Electronic disconnection and Reset after motor fault via floating contact at terminals
“D1”- “24V” (input resistance and voltage range
Technical data).
•Device “ON” for closed contact.
•Controller “OFF” with opened contact.
Activation via floating contacts, a low voltage of approx. 24 V DC is connected.
Danger due to electric current
•No disconnection (isolation) when turned off by remote, in accordance with VBG4 §6)!
•Never apply line voltage to the digital input!
5.11 Relay outputs (K1)
An operating message or activation of a damper control motor is possible via the
potential-free contacts of the relay “K1” (max. contact load
technical data and
connection diagram).
At a modulation above 5 Hz the relay energizes, i.e. the terminals “13” and “14” are
bridged.
At low modulation (below 3 Hz), switch off by the enable, switch off of line voltage or in
case of a fault, the relay de-energizes.
5.12 Bypass circuit
Please observe the following during bypass switching (controller shunt with mains
voltage):
•Mutual locking of mains contactor and bypass protection.
•Time delay of at least 1 second during switching.
•When the contactor is switched off at the inverter output, the “enable” (ON / OFF)
must also be opened and closed again when it is switched back on. When switching
off, wait at least 90 seconds before switching back on!
•Never apply line voltage to the inverter output!
5.13 Potential at control voltage connections
The control voltage connections (< 50 V) relate to the joint GND potential (Exception:
Relay contacts are potential free). There is a potential separation between the control
voltage connections and the protective earth. It must be ensured that the maximum
external voltage at the control voltage connections cannot exceed 50 V (between “GND”
terminals and “PE” protective earth). If necessary, a connection to the protective earth
potential can be established, install bridge between “GND” terminal and the “PE”
connection (terminal for screening).
Operating Instructions FRQS-4/10/16A Electrical installation
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
17/27

6 Start-up
6.1 Prerequisites for commissioning
Attention!
1. You must mount and connect the device in accordance with the operating instructions.
2. Double check that all connections are correct.
3. The mains voltage must match the information on the rating plate.
4. The rated current on the rating plate will not be exceeded.
5. Make sure that no persons or objects are in the hazardous area.
7 Diagnostics / Faults
Operating conditions are indicated by the status LED with flashing code.
10.01.2014
v_flash_explain_1_17.vsd
ON
OFF
1 x
16 x
15 x
14 x
13 x
12 x
11 x
10 x
9 x
8 x
7 x
6 x
5 x
4 x
3 x
2 x
17 x
Code Relay
K1 Explanation Reaction of Controller
Adjustment
OFF de-energized, 13 - 14
interrupted No line voltage
In the event of a mains interruption
the unit switches “OFF” and auto-
matically “ON” when the voltage
has been restored.
Check line voltage and pre-fusing.
ON
Energized at modula-
tion above 5 Hz (termi-
nals 13 - 14 bridged).
De-energized at modu-
lation below 3 Hz (13 -
14 interrupted).
Normal operation without fault
Operating Instructions FRQS-4/10/16A Start-up
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
18/27

Code Relay
K1 Explanation Reaction of Controller
Adjustment
1de-energized, 13 - 14
interrupted
No enable OFF
Terminals “D1” - “24 V” (Digital In
1) not bridged.
Switch off by external contact (
enable, device ON / OFF).
2
Energized at modula-
tion above 5 Hz (termi-
nals 13 - 14 bridged).
De-energized at modu-
lation below 3 Hz (13 -
14 interrupted).
Active temperature manage-
ment
The device has an active temper-
ature management to protect it
from damage due to too high in-
side temperatures. In case of a
temperature rise above the fixed
limits, the modulation is reduced
linearly. To prevent the complete
system being switched off exter-
nally (in this operation permissible
for the controller) in case of re-
duced operation due to too high an
internal temperature, no fault mes-
sage is sent via the relay.
With a drop in temperature the
modulation rises again llinear.
Check cooling of the controller
4de-energized, 13 - 14
interrupted
line failure
The device is provided with a built-
in phase-monitoring function for
the mains supply. In the event of a
mains interruption (failure of a fuse
or mains phase) the unit switches
off after a delay (approx. 15 s).
Only functioning with an adequate
load for the controller.
Following a shutoff, a startup at-
tempt is made after approximately
5 seconds, if the voltage supply is
high enough. This keeps occurring
until all 3 supply phases are avail-
able again.
Check line voltage.
6de-energized, 13 - 14
interrupted
IGBT Fault
Earth fault or short-circuit at inver-
ter output.
The device switches off, renewed
attempt to start after about 60 s
Code 9.
Final switch off when error is de-
tected after the third start attempt
at an interval < 60 s.
Reset by enable or line voltage
ON/OFF.
7de-energized, 13 - 14
interrupted
DC over voltage
Intermediate circuit voltage below
a fixed limit for longer than 75 s.
The modulation is switched off im-
mediately at undervoltage, error
message after 75 s.
Automatic switching back on and
switching off of error message
when the voltage exceeds the
fixed limit for at least 5 s.
Check line voltage.
Operating Instructions FRQS-4/10/16A Diagnostics / Faults
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
19/27

Code Relay
K1 Explanation Reaction of Controller
Adjustment
8de-energized, 13 - 14
interrupted
DC over voltage
Intermediate circuit voltage above
fixed limit for longer than 75s.
Reason for excessively high line
voltage or alternator motor opera-
tion.
The modulation is switched off im-
mediately at overvoltage, error
message after 75 s.
Automatic switching back on and
switching off of error message
when the voltage drops below the
fixed limit for at least 15 s.
Check line voltage.
Prevent generator motor opera-
tion.
9de-energized, 13 - 14
interrupted
IGBT cooling down period
IGBT cooling down period for ap-
prox. 60 sec.
Final shutoff after 2 cooling-off in-
tervals
Code 6.
12 de-energized, 13 - 14
interrupted
Line voltage too low
Line voltage below a fixed limit for
longer than 75 s.
The modulation is switched off im-
mediately at undervoltage, error
message after 75 s.
Automatic switching back on and
switching off of error message
when the voltage exceeds the
fixed limit for at least 5 s.
Check line voltage.
13 de-energized, 13 - 14
interrupted
Line voltage too high
Line voltage above fixed limit for
longer than 75 s.
The modulation is switched off im-
mediately at overvoltage, error
message after 75 s.
Automatic switching back on and
switching off of error message
when the voltage drops below the
fixed limit for at least 15 s.
Check line voltage.
14 de-energized, 13 - 14
interrupted
Error Peak current
If the output current increases
above the specified limit (even in a
short time-frame) the device will
switch-off.
After a switch off the controller
waits for 30 seconds then the con-
troller attempt a start.
If 10 switch offs take place consec-
utively within 60 s (time to next
respective error), final switch off
takes place with an error message.
Should no further switch off be ex-
ceeded in 90 sec. the counter will
be reset.
15 de-energized, 13 - 14
interrupted
Motor fault
A connected thermostat or ther-
mistor has tripped the circuit or in-
terruption between both terminals
“TB / TP”.
Plug for “TB” or “TP” in wrong
position.
The unit cuts out and does not
switch on again.
Check motor and connection then
reset (
Motor protection).
Operating Instructions FRQS-4/10/16A Diagnostics / Faults
L-BAL-E196-GB 1445 Index 002 Part.-No. 00163410-42
20/27
This manual suits for next models
2
Table of contents