manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. System Sensor
  6. •
  7. Smoke Alarm
  8. •
  9. System Sensor Filtrex FTX-P1A User manual

System Sensor Filtrex FTX-P1A User manual

Other System Sensor Smoke Alarm manuals

System Sensor 7251 User manual

System Sensor

System Sensor 7251 User manual

System Sensor DNRA User manual

System Sensor

System Sensor DNRA User manual

System Sensor 7251A User manual

System Sensor

System Sensor 7251A User manual

System Sensor PERTRONIC DNRW User manual

System Sensor

System Sensor PERTRONIC DNRW User manual

System Sensor DH200RPL User manual

System Sensor

System Sensor DH200RPL User manual

System Sensor BEAM200S User manual

System Sensor

System Sensor BEAM200S User manual

System Sensor 2WTR-B User manual

System Sensor

System Sensor 2WTR-B User manual

System Sensor FTX-P1 User manual

System Sensor

System Sensor FTX-P1 User manual

System Sensor D4P120 User manual

System Sensor

System Sensor D4P120 User manual

System Sensor 1012 Ionization User manual

System Sensor

System Sensor 1012 Ionization User manual

System Sensor PERTRONIC Innovair flex D4120 User manual

System Sensor

System Sensor PERTRONIC Innovair flex D4120 User manual

System Sensor 2100S User manual

System Sensor

System Sensor 2100S User manual

System Sensor 2151 User manual

System Sensor

System Sensor 2151 User manual

System Sensor DH100 Series User manual

System Sensor

System Sensor DH100 Series User manual

System Sensor B210LP User manual

System Sensor

System Sensor B210LP User manual

System Sensor FSB-200 User manual

System Sensor

System Sensor FSB-200 User manual

System Sensor 2112ж 24ATR User manual

System Sensor

System Sensor 2112ж 24ATR User manual

System Sensor 2WTR-B User manual

System Sensor

System Sensor 2WTR-B User manual

System Sensor Inovair Flex D4240 User manual

System Sensor

System Sensor Inovair Flex D4240 User manual

System Sensor 2100AT User manual

System Sensor

System Sensor 2100AT User manual

System Sensor OSI-RE-SS User manual

System Sensor

System Sensor OSI-RE-SS User manual

System Sensor B402B User manual

System Sensor

System Sensor B402B User manual

System Sensor Innovair flex D4120A User manual

System Sensor

System Sensor Innovair flex D4120A User manual

System Sensor WMSOU-RR-P01 User manual

System Sensor

System Sensor WMSOU-RR-P01 User manual

Popular Smoke Alarm manuals by other brands

Dyna-Glo DGY784BDP installation instructions

Dyna-Glo

Dyna-Glo DGY784BDP installation instructions

NOXE LUMENS Installation and user guide

NOXE

NOXE LUMENS Installation and user guide

Develco SMAZB-141 installation manual

Develco

Develco SMAZB-141 installation manual

Kidde PI2010CA user guide

Kidde

Kidde PI2010CA user guide

Honeywell 5800COMBO Installation and setup guide

Honeywell

Honeywell 5800COMBO Installation and setup guide

Gentex 7109CS installation instructions

Gentex

Gentex 7109CS installation instructions

FireAngel Thermoptek ST-622 user manual

FireAngel

FireAngel Thermoptek ST-622 user manual

teko Astra-42A user guide

teko

teko Astra-42A user guide

ELRO FS8110 instruction manual

ELRO

ELRO FS8110 instruction manual

Heiman SMOKI NS-626PHS user manual

Heiman

Heiman SMOKI NS-626PHS user manual

Siemens PE-11C installation instructions

Siemens

Siemens PE-11C installation instructions

Resolution Products RE612 CryptiX quick start guide

Resolution Products

Resolution Products RE612 CryptiX quick start guide

First Alert PC900V user manual

First Alert

First Alert PC900V user manual

Eminent EM6590 E-Domotica user manual

Eminent

Eminent EM6590 E-Domotica user manual

Ei Electronics Ei Ei168RC user manual

Ei Electronics

Ei Electronics Ei Ei168RC user manual

Carrier Kidde Quell Q301 user manual

Carrier

Carrier Kidde Quell Q301 user manual

Family Gard FG225 user manual

Family Gard

Family Gard FG225 user manual

Regin SDD-S65 instruction manual

Regin

Regin SDD-S65 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

D200-72-00 1 I56-1883-000
FTX-P1A Filtrex®Intelligent
Photoelectronic Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Before Installing
This detector must be installed in compliance with the con-
trol panel system installation manual. The installation must
meet the requirements of the Authority Having Jurisdiction
(AHJ). Detectors offer maximum performance when
installed in compliance with the CAN/ULC-S524.
General Description
Filtrex® uses a small air intake fan and a high density
replaceable filter. Air and smoke are drawn into a photo-
electric sensing chamber while airborne particulate and
water mist are removed. The addressable-analog detector
transmits an analog representation of smoke density over
a communication line to a control panel. Rotary-decade
switches are provided for setting the sensor’s address.
Two LEDs on the sensor are controlled by the panel to
indicate sensor status.
Filtrex smoke detector is intended for use in normal
environmental conditions, where dust and other air-
borne particulate are present at elevated levels. These
elevated levels tend to cause false alarms and high
maintenance in standard detectors. Filtrex provides a
protective enclosure for a photoelectric smoke detec-
tor chamber and allows smoke detection in areas that
tended to use exclusively heat detection.
Filtrex requires compatible addressable communica-
tions to function properly. Connect this detector to
listed-compatible control panels only.
Spacing
System Sensor recommends spacing detectors in com-
pliance with CAN/ULC-S524. In low air flow applications
with smooth ceilings, space detectors 30 feet apart. For
specific information regarding sensor spacing, placement,
and special applications, refer to CAN/ULC-S524 or the
System Sensor Guide For Proper Use of System Smoke
Detectors, available from System Sensor (P/N I56-407-
XX).
WARNING
Filtrex is not designed to operate in explosive
environments.
Specifications
Operating Voltage Range: 15 to 32 VDC
Detector Current: 230 µA @ 24 VDC (without communication)
285 µA @ 24 VDC (one communication every 5 sec. with LED enabled)
Auxiliary Power Supply Voltage: 15 to 30 VDC filtered; Ripple voltage may not drop below 15 volts.
Auxilary Power Supply Current –
Peak: 123 mA max.
Average: 27 mA max.
Operating Humidity Range: 10% to 93% Relative Humidity, noncondensing
Operating Temperature Range: 0° to 50°C (32° to 122°F)
Height: 2.8 inches (43 mm)
Diameter: 6.1 inches (155 mm) installed in B501B-FTXA
Weight: 7.3 oz. (207 g)
Compatibility: Backwards compatible with 200 and 500 series products’ protocol
Mounting Base: Requires B501B-FTXA
6581 Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5
1-800-SENSOR2, FAX: 905-812-0771
www.systemsensor.ca
D200-72-00 2 I56-1883-000
Wiring Instructions
All wiring must be installed in compliance with the
Canadian Electrical Code, applicable local codes, and any
special requirements of the Authority Having Jurisdiction.
Proper wire gauges should be used. The installation wires
should be color-coded to limit wiring mistakes and ease
system troubleshooting. Improper connections will prevent
a system from responding properly in the event of a fire.
Remove power from the communication line
before installing detectors.
All wiring must conform to applicable local codes, ordi-
nances, and regulations.
1. Wire the sensor base per the wiring diagram, please
see Figure 1.
2. Set the desired address on the sensor address switch-
es, please see Figure 2.
3. Insert 5-wire connector on mounting base into 5-pin con-
nector on Filtrex unit. Install the detector into the sensor
base. Push the detector into the base while turning it
clockwise to secure it in place. (Please see Figure 5 and
INSTALLING FILTREX INTO BASE on page 4 for spe-
cific directions.
4. After all detectors have been installed, turn on the aux-
iliary power supply, then apply power to the control unit
and activate the communication line.
5. Test the detector(s) as described in the TESTING sec-
tion of this manual.
CAUTION
Dust cover must be removed before the detector
can sense smoke.
LISTED COMPATIBLE CONTROL PANEL
AUX.
POWER
SUPPLY
+
+
–
–
AUX+
AUX–
AUX+
AUX–
2(–) 3(RA)4(S)
1(+)
1(+)
2(–) 3(RA) 4(S)
Testing
Before testing, notify the proper authorities that the system
is undergoing maintenance, and will temporarily be out of
service. Disable the system to prevent unwanted alarms.
All detectors must be tested after installation and periodi-
cally thereafter. Testing methods must satisfy the Authority
Having Jurisdiction (AHJ). Detectors offer maximum per-
formance when tested and maintained in compliance with
CAN/ULC-S536.
The sensor can be tested in the following ways:
A.
Functional: Magnet Test (P/N M02-04-01 or M02-09-
00)
This detector can be functionally tested with a test mag-
net. The test magnet electronically simulates smoke in
the sensing chamber, testing the detector electronics
and connections to the control panel.
1. Hold the test magnet in the magnet test area as
shown in Figure 3.
2. The detector should alarm the panel. Two LEDs on
the detector are controlled by the panel to indicate
sensor status. Coded signals, transmitted from the
panel, can cause the LEDs to blink, latch on, or latch
off. Refer to the control panel technical documenta-
tion for detector LED status operation and expected
delay to alarm.
B. Smoke Entry: Aerosol Generator
Aerosol generators for smoke entry testing are avail-
able from a number of third party manufacturers (e.g.,
Gemini Scientific). Following the manufacturer’s instruc-
tions, apply aerosol until the panel alarms.
Figure 1. Wiring diagram:
D200-72-00 3 I56-1883-000
TEST MAGNET
MARKER
Cover is keyed to
fit into 4 matching
size slots.
456
3
7
8
2
19
0
456
3
7
8
2
19
0
A78-2460-00
Figure 2. Rotary decade address switches:
Figure 3. Test magnet position:
Figure 4. Replacing the filter cover:
A detector that fails any of these tests should be retested.
If the detector still fails any test, have its filter replaced
(see instructions below) and retested. Finally, if the detec-
tor continues to fail after replacing the filter, it must be
returned for repair or replacement.
When testing is complete, restore the system to normal
operation and notify the proper authorities that the system
is back in operation.
Cleaning
The unique design of Filtrex eliminates the need for typi-
cal detector cleaning. The only maintenance necessary is
replacing the filter, which is signaled by a trouble condition
at the panel (see below).
Filtrex has been designed to maximize the amount of time
before maintenance is required. Filtrex utilizes a replace-
able filter that may become clogged over time. Filtrex mon-
itors itself to insure that the filter has not become clogged.
Because environmental conditions can vary significantly,
the amount of time before maintenance could vary sig-
nificantly as well. To fully understand the maintenance
requirements of Filtrex in its installed location, it is recom-
mended that the following test program be conducted.
1. Install Filtrex in the desired location.
2. Connect Filtrex to the fire alarm control panel.
3. Maintain a record for at least 90 days of any mainte-
nance performed on or required by Filtrex.
4. At the end of the test period, use the record to develop
and schedule maintenance. Filtrex detectors should be
serviced at regular intervals to insure that the fire alarm
system provides continuous protection.
Replacing the Filter
IMPORTANT:
When the filter becomes too clogged to draw
adequate air into Filtrex, power is automatically
cut from the detector, sending a trouble signal
to the fire control panel. After 5 minutes, power
is restored to the detector for 72 hours. After 72
hours, power is cut again and the detector will
remain off-line until the filter is replaced.
Note: The unit has two filters. The replaceable filter is
inside the cover. A permanent filter is mounted to the unit.
1. Grasp the Filtrex housing with one hand and the cover
with the other. Turn the cover counterclockwise fully
(approx. 30 degrees) and remove cover by pulling it
away from detector unit (see Figure 4).
2.Replace with new filter and cover assembly. The cover
is keyed so it fits in place only one way. Turn the cover
clockwise until it stops.
NOTE: The base is equipped with an optional tamperproof
feature which can be used to prevent unintentional removal
of Filtrex while replacing the filter.
Alignment marks are
provided on the cap
and top of the per-
manent filter.
D200-72-00 4 I56-1883-000
©2004 System Sensor
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector to be free from defects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes
no other express warranty for this smoke detector. No agent, representa-
tive, dealer, or employee of the Company has the authority to increase
or alter the obligations or limitations of this Warranty. The Company’s
obligation of this Warranty shall be limited to the repair or replacement of
any part of the smoke detector which is found to be defective in materi-
als or workmanship under normal use and service during the three year
period commencing with the date of manufacture. After phoning System
Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: System
Sensor, Repair Department, RA #__________, 6581 Kitimat Rd, Unit# 6
Mississauga, Ontario L5N 3T5. Please include a note describing the mal-
function and suspected cause of failure. The Company shall not be obli-
gated to repair or replace units which are found to be defective because
of damage, unreasonable use, modifications, or alterations occurring
after the date of manufacture. In no case shall the Company be liable for
any consequential or incidental damages for breach of this or any other
Warranty, expressed or implied whatsoever, even if the loss or damage is
caused by the Company’s negligence or fault. Some states do not allow
the exclusion or limitation of incidental or consequential damages, so the
above limitation or exclusion may not apply to you. This Warranty gives
you specific legal rights, and you may also have other rights which vary
from state to state.
Figure 5: Installing Filtrex detector into base:
If a clogged filter was the cause of the trouble condition,
normal detector operation should resume automatically
within five minutes. If the trouble condition persists, the
detector must be returned for repair or replacement.
Installing Filtrex Into Base
1. Align the detector at a right angle to the base, with
the five wires and connector adjacent to the connector
receptacle as shown in Figure 5.
2. Plug the wired connector into the receptacle.
3. Rotate the detector into the base, making sure detec-
tor and base keyed fit is lined up. Turn the detector
clockwise until it snaps into place.
IMPORTANT: Filtrex will only operate with B501B-
FTXA.
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful inter-
ference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates,
uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interfer-
ence to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment
does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
Please refer to insert for the Limitations of Fire Alarm Systems