Teknim TFD-3230 Troubleshooting guide

TFD-3230
Conventional Optical Somoke Detector
Installation & Operating Guide
Issue Date: 23/03/2018
Rev:01
Important Warnings
General
✓Before using the device read this manual carefully. Keep it just in case of necessity.
✓Abide all the rules and precautions stated in the manual. Follow all the instructions one by one.
✓Keep the devices away from water and moisture
Conditions
Do not energize the device above or below the given limits of extreme hot or cold conditions,
Temperature: Between -10°C and +55°C
Relative Humidity: %95 RH max
Service
Do not try to fix the device on your own. Removal of cover may end up with electricity shock.
In case of any defect or malfunction, contact with your dealer or with authorized service. All the technical
interventions have to be done by technicians of company.
Malfunctions that require technical service
In case of any malfunction or below conditions contact with your authorized service,
✓When Mains cable or the plug is harmed,
✓Contact of device with a fluid,
✓Exposure of rain and water,
✓Fell down of device or harmed outer cover,
✓Serious performance fall on the device,
✓Depending on the instructions stated in manual, if your device not working properly
Contact with your authorized service in such terms.
Maintenance on your own
Do not try to fix the device on your own. Removal of cover may end up with electricity shock. In case of any
defect or malfunction, contact with your dealer or with authorized service. All the technical interventions have
to be done by technicians of company. Device must be cleaned up with a dry fabric. No-chemicals are
allowed for cleaning
Transportation
Device must be carefully transported avoiding all physical bump, stroke and possible fluid entry. Malfunctions
that caused by improper transportation is not under warranty.
Human and Environmental Health
This device contains no chemical or biological elements that could harm human condition.
General Features
✓Advanced smoke detection algorithm that minimizes false alarms
✓Rejection of transient signals that can be detected as alarms
✓Adaptive intelligent protection by constantly sampling the environment
✓Dust algorithm and warning to understand that it is getting polluted and unable to detect
✓Easy to clean smoke chamber
✓Ability to connect an remote indicator
✓Two leds used for status indicators
✓15s start time
✓Compatible with TFA-0120 Universal Detector Base
Technical Features
Power Input
18V(min) –30V(max)
Average Current Consumption
30uA (@24V)
Maximum Alarm Current
50mA (@24V) –(470ohm resistance limited)
Maximum External Device Current
10mA (@24V) –(2K2 resistance limited)
Operating Temperature Range
-10C ~ +70C (14F ~ 158F)
Humidity
95% RH (max)
Dimensions (mm)
Ø110, h42
Housing Material
White Color, ABS Plastic
Used Cable Cut
0.4mm ² ~ 1.5mm ²
Weight (incl. Base / excluding base)
183 gr / 125 gr
Startup Time
15 sec
Indicator Leds
Blue Led
Red Led
When the unit is first energized for
15 s, while sampling the
environment
Blinks for 5s period
X
Any error condition
(dust or power failure)
Blinks for 1s period
X
In normal operating condition
Blinks for 20s period
X
In alarm condition
X
It is constantly lit
Terminals
Number 1
Negative (-) power input
Number 2
Negatif(-) input of the remote indicator
Number 3
Positive supply out and Positive (+) input of remote indicator
Number 4
Positive (+) power input
Number 5
Earth connection
Warning: Do not attempt to remove the electronic board from its plastic case. The electronic board is
closed for your safety. Users should avoid from interference.
Mounting and Connection
1. Remove the head of the detector by pulling it upwards (2) by turning it (1) up to the short line in the
direction of the counterclockwise direction as seen from the base.
2. Mount the base using the 2 mounting locations shown.
3. Make the cable connection according to the following diagram. Make a connection with pole 4 + pole and
pole 1 - by taking pole + number 3 from pole 3 of the next detector.
4. Use the 3 (+) and 2 (-) connections for the remote indicator.
5. Replace the detector head. Make sure the line on the head matches the long line on the base
6. Give the detector power from alarm panel. In the absence of an alarm, the LED on the detector indicates
that it is operating with a blue color for approximately 20 seconds. (the first 15 seconds a blue LED lights
up in the detector for 5 seconds).
Test
Smoke Test:
For the smoke test, allow the smoke to enter the smoke detection chamber for at least 1 minute with a
flammable material or a test aerosol. When enough amount of smoke enters the chamber, the LED
illuminates and reports the alarm.
1. Remove the smoke source when the alarm condition is reached.
2. Check that the red LEDs are lit continuously. Reset the detector on the panel.
3. If the detector does not give an alarm within 1 minute, the detector should go to service.
4. The system can be activated after the test has been performed.
1922
Bilgi Elektronik San. ve Tic. A.Ş.
Dudullu OSB 1. Cad. İsmet Tarman İş Merkezi
No:1 Kat:2 No:32 Ümraniye / İstanbul
17
1922-CPD-0874
EN 54-7:2000; EN 54-7:2000/A1:2002; EN 54-7:2000/A2:2006
Point type smoke detector (Ionization)
TFD-3230
Technical data: see BİLGİ-TEC-170731-2 held by the manufacturer.
Manufacture
* 2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted
municipal waste in the European Union. For proper recycling, return this product to your local supplier upon
the purchase of equivalent new equipment, or dispose of it at designated collection points. For more
information see: www.recyclethis.info.
Bilgi Elektronik San. ve Tic. A.Ş.
Dudullu Organize Sanayi Bölgesi 1. Cadde İsmet Tarman İş Merkezi
No:1 Kat:2 No:32 Ümraniye / İstanbul / Türkiye
Telephone: +90 216 455 88 46 Fax: +90 216 455 99 06
Sales: sa[email protected]
Technical Support: [email protected]

Other Teknim Smoke Alarm manuals

Teknim TFD-1250 Instruction Manual

Teknim

Teknim TFD-1250 Instruction Manual

Teknim TSD-5135 Troubleshooting guide

Teknim

Teknim TSD-5135 Troubleshooting guide

Teknim TFD-1250 Instruction Manual

Teknim

Teknim TFD-1250 Instruction Manual

Teknim TSD-5154 User manual

Teknim

Teknim TSD-5154 User manual

Teknim TFD 1430 User manual

Teknim

Teknim TFD 1430 User manual

Teknim TFD-1250 Troubleshooting guide

Teknim

Teknim TFD-1250 Troubleshooting guide

Teknim TSD-5124 User manual

Teknim

Teknim TSD-5124 User manual

Teknim TFD-1251 Instruction Manual

Teknim

Teknim TFD-1251 Instruction Manual

Teknim TFD-1270 User manual

Teknim

Teknim TFD-1270 User manual

Popular Smoke Alarm manuals by other brands

Mircom FA-1025U Installation and operation manual

Mircom

Mircom FA-1025U Installation and operation manual

System Sensor BEAM200A Installation and maintenance instructions

System Sensor

System Sensor BEAM200A Installation and maintenance instructions

minirookmelder.be MR5120 installation instructions

minirookmelder.be

minirookmelder.be MR5120 installation instructions

Kidde KN-COB-B-LP user manual

Kidde

Kidde KN-COB-B-LP user manual

Bellman & Symfon BE1281 quick start guide

Bellman & Symfon

Bellman & Symfon BE1281 quick start guide

COP-USA SDDVR-WF user guide

COP-USA

COP-USA SDDVR-WF user guide

AirSense Stratos Micra 10 Installer's handbook

AirSense

AirSense Stratos Micra 10 Installer's handbook

Air Products MSR-50A installation guide

Air Products

Air Products MSR-50A installation guide

Lifesaver 6000 manual

Lifesaver

Lifesaver 6000 manual

First Alert PC910 user manual

First Alert

First Alert PC910 user manual

A-Collection 6302618 installation instructions

A-Collection

A-Collection 6302618 installation instructions

Vega Absolute SMART-SS0102 user manual

Vega Absolute

Vega Absolute SMART-SS0102 user manual

Polon-Alfa DUR‐4046 Installation and maintenance manual

Polon-Alfa

Polon-Alfa DUR‐4046 Installation and maintenance manual

Eminent EM8690-R1 user manual

Eminent

Eminent EM8690-R1 user manual

Brooks firetracker FT1020G3 FDCIE Operation manual

Brooks

Brooks firetracker FT1020G3 FDCIE Operation manual

Firex FADC230 user manual

Firex

Firex FADC230 user manual

i4Home SM-3S quick start guide

i4Home

i4Home SM-3S quick start guide

Quell Q4000DCS-WCB user guide

Quell

Quell Q4000DCS-WCB user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.