Taik T250 User manual

T250
1
10 10 10
100 100 100
50 50 50
2
3
Power Meter T250
IV F P PF H E
OK
PROG
TAIK
Instruction Manual

1 2
2. Installation /Wiring:
Front View
Cut-Out Size
Side View
3
1
2
1. Hardware Structure:
1.1 Display Screen:
Auxiliary power supply and voltage inputs
1.2 Terminals Configuration:
Extended modules
Current inputs
91 +0.5
-0.5
91 +0.5
-0.5
96
96
96
1
2
3
17 46 18 20
81
101
1K 1L 2K 2L 3K 3L
L1 L2 L3 NP2 P1
14 rows of 4 digits
2Inductive/capacitive load or positive/
negative value
3Values in line-neutral or line-line voltage
1
:L1 Value
1 2
-
:L1-2 Voltage (line to lin)
4Measured electrical parameters
:Voltage :Current :Watt
:PF :Var :VA
5Measured units
6Load in current (%)
7
:System Value
8:RS 485 module :Flashing
99 digits, the unit in measured
energy, and decimal point
AMeasured energy
: Import WH or Ind VarH
: Export WH : Cap VarH
BIndividual harmonic rate (%)
CActual demand
DMax.memorized values
EConnecting status for the extended modules
F5 push buttons
2.1 Dimension and Panel Cut-out (Unit: mm)
System frequency
as the communication is in progress
1
2
3
4
5
6
Power Meter T250
IV F P PF H E
OK
PROG
TAIK
12
-
10 10 10
120 120 120
100 100 100
50 50 50
-
23
-
31
I/O
1RY
2
3
4
1
2
3
4
5
6
3 2 1
5
6
7
8
9
F
B
4
C
D
E
A

3 4
2.2 Connection Diagrams:
1K 1L 2K 2L 3K 3L
L1 L2 L3 NP2 P1
Aux. Power
1K 1L 2K 2L 3K 3L
L1 L2 L3 NP2 P1
Aux. Power
1K 1L 2K 2L 3K 3L
L1 L2 L3 NP2 P1
Aux. Power
1K 1L 2K 2L 3K 3L
L1 L2 L3 NP2 P1
Aux. Power
P
N
1K 1L 2K 2L 3K 3L
L1 L2 L3 NP2 P1
Aux. Power
L1
L2
N
1K 1L 2K 2L 3K 3L
L1 L2 L3 NP2 P1
Aux. Power
3 Phase 4 Wire (3 PTs, 3 CTs)
3 Phase 4 Wire (Only 3 CTs)
3 Phase 3 Wire (2 PTs, 3 CTs)
1 Phase 3 wire (Only 2 CTs)
1 Phase 2 Wire (Only 1 CT)
3 Phase 3 Wire (2 PTs, 2 CTs)

3. Functions of Buttons:
3.1 Keys Programming
Display
Current demand and max. current demand
5 6
I
V F
P PF
H
OK
E
PROG
Display
Frequency, voltage and max. voltage
Display
Apparent power, active power, reactive power, power factor,
watt demand and max. watt demand
Display
Press once:Displaying values in VAH, WH and VarH
Hold:Access to set up mode (Refer to 4.1)
THD voltage and THD current
At the presence of THD display mode, press two buttons simultaneously:
Hold
H
OK
I
or
H
OK
V F
to select individual harmonic
distortion rate
At the presence of individual harmonic distortion rate:
H
OK
to return THD display mode
Display: 4 digits at the maximum figures up to 9999
Decimal point position of The M/K unit: The position of the
decimal point in the M/K unit will automatically be varied with
the rated inputs (CT and PT ratio set-up)
Symbols:
0
。
90
。
180
。
270
。
12
34
The angle lain between a base of
measured voltage and the current
is divided into 4 quadrants.
3.1.1 Symbols of Phase Sequence (Refer to 1.1)
:L3 values in line-neutral; 3-1: L3-L1 line-line voltage
1
2
3
:System Values
Values in line-neutral or line-line voltage:
:Inductive load
:Capacitive load
:Negative watt (Reverse current flow)
Hold simultaneously
H
OK
to change by either default formula
Formulation of THD
P PF
Temporarily displayed legends
Temporarily displayed legends
Hold
Vrms: The RMS Volt waveform
V rms: The RMS Volt on fundamental
frequency waveform
:L2 values in line-neutral; 2-3: L2-L3 line-line voltage
:L1 values in line-neutral; 1-2: L1-L2 line-line voltage

3.2 Display in 3P4W:
Current
7 8
I
1
10 10 10
100 10 0 10 0
50 50 50
2
3
V F
1
10 10 10
100 10 0 10 0
50 50 50
2
3
1
10 10 10
100 10 0 10 0
50 50 50
2
3
N
1
10 10 10
100 10 0 10 0
50 50 50
2
3
12
-
10 10 10
100 10 0 10 0
50 50 50
-
2
-
3 1
3
1
10 10 10
100 10 0 10 0
50 50 50
2
3
12
-
10 10 10
100 10 0 10 0
50 50 50
-
2
-
3 1
3
12
-
10 10 10
100 100 100
50 50 50
-
2
-
3 1
3
1
10 10 10
100 10 0 10 0
50 50 50
2
3
P PF
1
10 10 10
100 10 0 10 0
50 50 50
2
3
10 10 10
100 10 0 10 0
50 50 50
1
10 10 10
100 10 0 10 0
50 50 50
2
3
Volt/Frequency VA/W/Var/PF/Demand
1
10 10 10
100 10 0 10 0
50 50 50
2
3
1
10 10 10
100 10 0 10 0
50 50 50
2
3
1
10 10 10
100 10 0 10 0
50 50 50
2
3
1
10 10 10
100 10 0 10 0
50 50 50
2
3
H
OK
Individ. harmonic rate/THD
3. Display Mode and Button Functions : Appearing the bargraph rate at % for the measured current on each display
phase/system currents
phase/ neutral currents
phase/ system max.
memorized currents
phase/system voltage
system/line-line voltage
phase voltage/frequency
line-line voltage/ frequency phase/ system apparent power
phase/ system reactive power
phase/ system power factor
system watt demand/ max.
memorized watt demand
phase/ system max.
memorized watt
10 10 10
100 10 0 10 0
50 50 50
system current demand/ max.
memorized current demand
phase/ system THD voltage
phase/ system THD current
I
I
V F
V F
V F
V F P PF
P PF
P PF
P PF
P PF
H
OK
E
PROG
Energy
THD display mode, press two buttons
simultaneously:
Hold
H
OK
I
or
H
OK
V F
to select individual harmonic distortion rate :
At the presence of individual harmonic
distortion rate:
Hold to return THD display mode
H
OK
1
10 10 10
100 10 0 10 0
50 50 50
2
3
phase voltage 3rd harmonic
distortion rate
1
10 10 10
100 10 0 10 0
50 50 50
2
3
phase current 3rd harmonic
distortion rate
system KWH
1
10 10 10
100 10 0 10 0
50 50 50
2
3
system KVarH
1
10 10 10
100 10 0 10 0
50 50 50
2
3
1
10 10 10
100 10 0 10 0
50 50 50
2
3
system KVAH
E
PROG
E
PROG
*Set-up Flowchart
In sub-menus mode, access to
Hour Hour i_E :(set to YES)
can be shown as follows
Import/ Export KWH
Ind/Cap KVarH
I
EEEEE
system/ line-line max.
memorized voltage
phase/ system active power

3.3 Display in 3P3W:
9 10
Current
I
1
10 10 10
100 10 0 10 0
50 50 50
2
3
V F
Volt/Frequency
Appearing the bargraph rate at % for the measured current on each display
phase/ system currents
12
-
10 10 10
100 10 0 10 0
50 50 50
-
2
-
3 1
3
line-line/ system voltage
12
-
10 10 10
100 10 0 10 0
50 50 50
-
2
-
3 1
3
line-line voltage/ frequency
10 10 10
100 10 0 10 0
50 50 50
system current demand/ max.
memorized current demand
I
I
V F
V F
1
10 10 10
100 10 0 10 0
50 50 50
2
3
phase/ system max.
memorized currents
12
-
10 10 10
100 10 0 10 0
50 50 50
-
2
-
3 1
3
line-line/ system max.
memorized voltage
EE
1
10 10 10
100 10 0 10 0
50 50 50
2
3
P PF
1
10 10 10
100 100 100
50 50 50
2
3
10 10 10
100 100 100
50 50 50
1
10 10 10
100 100 100
50 50 50
2
3
VA/W/Var/PF/Demand
1
10 10 10
100 100 100
50 50 50
2
3
1
10 10 10
100 100 100
50 50 50
2
3
phase/ system apparent power
phase/ system reactive power
phase/ system power factor
system watt demand/ max.
memorized watt demand
phase/ system max.
memorized watt
P PF
P PF
P PF
P PF
P PF
E
phase/ system active power
1
10 10 10
100 100 100
50 50 50
2
3
1
10 10 10
100 100 100
50 50 50
2
3
H
OK
Individ. harmonic rate/THD
phase/ system THD voltage
phase/ system THD current
H
OK
E
PROG
Energy
THD display mode, press two buttons
simultaneously:
Hold
H
OK
I
or
H
OK
V F
to select individual harmonic distortion rate :
1
10 10 10
100 100 100
50 50 50
2
3
phase voltage 3rd harmonic
distortion rate
1
10 10 10
100 100 100
50 50 50
2
3
phase current 3rd harmonic
distortion rate
system KWH
1
10 10 10
100 100 100
50 50 50
2
3
system KVarH
1
10 10 10
100 100 100
50 50 50
2
3
1
10 10 10
100 100 100
50 50 50
2
3
system KVAH
E
PROG
E
PROG
*Set-up Flowchart
In sub-menus mode, access to
Hour Hour i_E :(set to YES)
can be shown as follows
Import/ Export KWH
Ind/Cap KVarH
EE
At the presence of individual harmonic
distortion rate:
Hold to return THD display mode
H
OK

3.4 Display in 1P3W:
11 12
1
10 10
100 100
50 50
2
10 10
100 100
50 50
1
10 10
100 100
50 50
2
1
10 10
100 100
50 50
2
1
10 10
100 100
50 50
2
1
10 10
100 100
50 50
2
1
10 10
100 100
50 50
2
1
10 10
100 100
50 50
2
1
10 10
100 100
50 50
2
1
10 10
100 100
50 50
2
1
10 10
100 100
50 50
2
1
10 10
100 100
50 50
2
1
10 10
100 100
50 50
2
1
10 10
100 100
50 50
2
10 10
100 100
50 50
1
10 10
100 100
50 50
2
Current
IV F P PF
Volt/Frequency VA/W/Var/PF/Demand
H
OK
Individ. harmonic rate/THD
Appearing the bargraph rate at % for the measured current on each display
phase/system currents line-neutral/ system voltage phase/system active power phase/system THD voltage
E
PROG
Energy
system KWH
1
10 10 10
100 10 0 10 0
50 50 50
2
3
system KVarH
1
10 10 10
100 10 0 10 0
50 50 50
2
3
1
10 10 10
100 10 0 10 0
50 50 50
2
3
system KVAH
E
PROG
system current demand/max.
memorized current demand
I
I
phase/system max.
memorized currents line-neutral/ frequency
V F
V F
line--neutral/ system max.
memorized voltage
phase/system apparent power
phase/system reactive power
phase/system power factor
system watt demand/ max.
memorized watt demand
phase/system max.
memorized watt
P PF
P PF
P PF
P PF
P PF
E
PROG
phase/system THD current
H
OK
phase voltage 3rd harmonic
distortion rate
phase current 3rd harmonic
distortion rate
EEEEE
*Set-up Flowchart
In sub-menus mode, access to
Hour Hour i_E :(set to YES) can
be shown as follows
Import/ Export KWH
Ind/Cap KVarH
At the presence of individual harmonic
distortion rate:
Hold to return THD display mode
H
OK
THD display mode, press two buttons
simultaneously:
Hold
H
OK
I
or
H
OK
V F
to select individual harmonic distortion rate :

13 14
1
10
100
50
current
1
10
100
50
1
10
100
50
電壓及頻率顯示
1
10
100
50
1
10
100
50
1
10
100
50
1
10
100
50
1
10
100
50
1
10
100
50
1
10
100
50
1
10
100
50
1
10
100
50
1
10
100
50
10
100
50
10
100
50
IV F P PF H
OK
voltage/frequency active power THD voltage
E
PROG
KWH
1
10 10 10
100 100 100
50 50 50
2
3
KVarH
1
10 10 10
100 100 100
50 50 50
2
3
1
10 10 10
100 100 100
50 50 50
2
3
KVAH
E
PROG
current demand/max.
memorized current demand
I
I
max.memorized current
V F
max. memorized voltage
apparent power
reactive power
power factor
watt demand/max.
memorized watt demand
max. memorized watt
P PF
P PF
P PF
P PF
P PF
E
PROG
THD current
H
OK
voltage 3rd harmonic
distortion rate
current 3rd harmonic
distortion rate
EEEE
E
*Set-up Flowchart
In sub-menus mode, access to
Hour Hour i_E :(set to YES) can
be shown as follows
Import/ Export KWH
Ind/Cap KVarH
At the presence of individual harmonic
distortion rate:
Hold to return THD display mode
H
OK
THD display mode, press two buttons
simultaneously:
Hold
H
OK
I
or
H
OK
V F
to select individual harmonic distortion rate :
Current Volt/Frequency VA/W/Var/PF/Demand Individ. harmonic rate/THD Energy
3.5 Display in 1P2W:
Appearing the bargraph rate at % for the measured current on each display

4. Set-up Flowchart/ Buttons:
4.1 Set-up Flowchart:
Password isn’t set to 0
Password is set to 0
Main menus/Set-up Main menus/Clear
Wiring configuration
CT Ratio
15 16
E
Functions:
Main menus:
Advance to the next menus
Disable
Sub-menus :
Access to values set-up
Advance to next sub-menus
Return to main menus
Values Set-up:
Increased value
Decreased value
E
※
※
4.2 Buttons:
Access to sub-menus
Vary digits position
Return to measured values
E
OK
PROG
OK
PROG
Energy values
Max. memorized values
Max. memorized demand values
PT Ratio
Demand average time
PROG
Hold
PROG
OK
Disable
PROG
OK
PROG
Disable
Confirm then return to
sub-menus
OK
Note1
Note 1: At the presence of PT ratio set-up, press
simultaneously for setting the decimal
point position.
Import/Export energy
Backlit energy saving mode
00: keep lighting up
Passcode setup
1000: All-purpose password
Main menus/RS 485
OK
PROG
Address
Baud rate
Data frame
Two Words transmission
E
Extended module ordered will
be shown on the screen
Advance to next sub-menus
Disable
Default value by factory setting to 1000
Incorrect set-up returns the measured values
and consequentially appears

※Having an associated module can be shown on the screen, the I/O module is unavailable
shown on the screen.
4.3 Relay Contact & Analog Output (Extended modules) :
E
Main menus/Relay 1 & 2
OK
PROG
Relay 1 type
Relay 2 type
Pulse 1 output
※ Relay 1 set to Pulse
will be shown, and
the pulse rate shall
be set to the secondary
value.
Pulse 2 output
Same function but different defined code
※ Relay 1 is set to
PULSE 1 or
ALARM 1
ALARM 1 parameters
※ Relay 1 set to Alarm,
which the corresponding
parameters will be shown.
Alarm 1 values
Alarm 1 Hi & Lo
Alarm 1 delay time
※ Realy 1 set to Alarm,
which the corresponding
parameters will be shown.
※ Relay 1 set to Alarm,
which the corresponding
parameters will be shown.
※ Relay 1 set to Alarm,
which the corresponding
parameters will be shown.
4 digit values set-up; The
unit and decimal point
will be set automatically.
Alarm 2 parameters
Alarm 2 values
Alarm 2 Hi & Lo
Alarm 2 delay time
Relay module
17 18
DC OUT主功能表
OK
PROG
Output 1 parameters
Output 1 values
Output 2 parameters
Output 2 values
Analog module
※ Relay 2 is set to
PULSE 2 or
ALARM 2
※ Relay 2 set to Pulse
will be shown, and
the pulse rate shall
be set to the secondary
value.
※ Relay 2 set to Alarm,
which the corresponding
parameters will be shown.
※ Relay 2 set to Alarm,
which the corresponding
parameters will be shown.
※ Relay 2 set to Alarm,
which the corresponding
parameters will be shown.
※ Relay 2 set to Alarm,
which the corresponding
parameters will be shown.
4 digit values set-up; The
unit and decimal point
will be set automatically.
4 digit values set-up; The
unit and decimal point
will be set automatically.
4 digit values set-up; The
unit and decimal point
will be set automatically.
Same function but different defined code

Wiring configuration
4.4 The reminders of Sub-Menus Set-up :
:The electrical connection shall correspond
with the set wiring configuration
Import/Export energy
:WH :Import/Export values
VarH : Ind/Cap values
: Import WH or Ind VarH
: Export WH : Cap VarH
Backlit energy saving mode
:Time set-up for backlit energy saving .
After a touch on any of buttons, the
backlit will automatically be lit up
00:keep lighting up
19 20
Output 1 parameters
:system voltage (3P3W line-line voltage)
:system current
:system active power
(unidirectional 4-20mA)
:system power factor
(bidirectional 4-12-20mA)
:system frequency
:system reactive power
(bidirectional 4-12-20mA)
Alarm 1 parameters :system voltage (3P3W line-line voltage)
:system current
:system watt
:system watt demand
:system current demand
:system frequency
:system power factor
:system THD voltage
:system THD current
* Adopting “absolute value” for comparison
Pluse 1 output
Example: Setting the pulse rate as P100
which corresponds to the secondary value.
Two Words transmission
:Hi word is set ahead, Low word is set behind
It is defined as “Swapped Float”
Being applied to Double Words” transmission
PT ratio
At the presence of PT ratio set-up, press
simultaneously for setting the decimal point position.
OK
:Low word is set ahead, Hi word is set behind
It is defined as “Float”

5. Specifications:
5.1 Measured Parameters and Accuracy:
5.2 Characteristics:
Accuracy performance range:
Voltage 0.6 ~ 120%
Power energy 0.2 ~ 120%
Volt: , Amp:
0.6 ~ 120%
Current 0.2 ~ 120%
Power factor
Frequency 45 ~ 70Hz
Distortion level 31st
Input Voltage:
Line-line Voltage 3 ~ 500V
Maximum overload 750V
Line-neutral Voltage 2 ~ 288V
Input impedance
Power consumption
Input Current:
Current 5A,1A(Option)
Power consumption
Isolation Phase to phase 600V
Starting current 0.2%F.S.
Power supply:
Auxiliary power supply AC/DC85~265V
Power consumption
Frequency Range 45 ~ 65Hz
Display screen:
Format LCD blue backlit
3 rows of 4 digits
Digit height 0.39",10.0mm
Communication:
Interface RS485
Protocol MODBUS ,RTU frame
Baud rate 1200 ~ 38400 programmable
Address 1 ~ 255 progtammable
4.5VA(Without extended module)
<
Data format
Parallel connection 32 meters
Installation of pluggable modules:Max. 4 modules
Relay contacts 2 modules
RS 485 1 module
Set-up/Memorized Value:
Memory method FRAM
Memory time 20 years at least
21 22
9VA(All extended modules)
<
One row of 9 digits accumulative values
Digital inputs
Analog outputs
DC 20~60V (OPTION )
THD % display:
Current
Voltage 10% F.S.
<
1% F.S.
<
N,8,1 /N,8,2 O,8,1 E,8,1
/ / programmable
0.1VA
<
0.1VA
<
800KW
>
Display
SYS L1 L2 L3 Accuracy
L-L volt l* l l l 0.2%
L-N volt l* l l l 0.2%
Current l* l l l 0.2%
Active power l l l l 0.5%
Reactive power l l l l 0.5%
Apparent power l l l l 0.5%
Power factor l* l l l 0.5%
Frequency l 0.05Hz
Import (KWH) l l l l 0.5%
Ind (KVarH) l l l l 0.5%
Export (KWH) l l l l 0.5%
Cap (KVarH) l l l l 0.5%
THD l* l l l 2%
Demand l 0.5%
* Average Value Accuracy:F.S.%
2 modules
2 modules
COS (SIN ) 0.5 ~ 1
ΘΘ

23 24
6.1 Communication protocol
6.COMMUNICATIONS
Utilizing MODBUS communication shall use a repeater as the meters are in parallel
connection more than 30pcs.
6.2 Transmission Mode
RTU
6.3 Transmission Method
RS 485 (Half-Duplex)
6.4 Modbus Frame
6.4.1 Basic Command Framing:Hexadecimal Code
Start of
frame
Address
Field
Function
Code
Data
Field
Error
Check
End of
Frame
St art of frame:The data is not transmitted by a silent period of at least
4 characters
Address field :The valid MODBUS address es are in the range of 1-255, the address 0 for
broadcast command is only valid for Func tion Code ð 06H,
but it doesn’t reply to any message
Function code :03HðRead Data
06HðWrite Date
Data field :The start address of a register. Reading N Words and Writing N values
Error check :A 16 bit CRC
End of frame :The dat a is not transmitted by a silent period of at least 4 characters
6.4.2 Bit Per Byte:Access to sub-menus for set-up
Start Bit Data Bit Parity St op Frame Setting values
1 8 None 2 N,8,2 0
1 8 Odd 1 O,8,1 1
1 8 Even 1 E,8,1 2
1 8 None 1 N,8,1 3
6.5 Reading Register Command:
Query:
Start of
Frame
Addr ess
Field
Function
Code
Star t
Address Hi
Star t
Addr ess
Lo
Number of
Word Hi
Number of
Word Lo Error Check End of
Frame
01H~FFH 03H 0~nnH 0 ~ nnH 0H 1~nnH CRC Lo CRC Hi
1 Byte 1 Byte 2Byte 2 Byte 2 Byte
Response:(Command is correct)
Start of
Frame
Addr ess
Field
Function
Code
Number of
Data Byte
Count
D0、D1.. Dn
(Hi,Lo,H i,Lo....)
Error
Check
End of
Frame
01H~FFH 03H CRC Lo CRC Hi
1 Byt e 1 Byte 1Byte 2 Byte
6.6 Writing Register Command: A single writing WORD command
Query:
Start of
Frame
Address
Field
Function
Code
Start
Addr ess
Hi
Start
Addr ess
Lo
Value
Hi..
Value
..Lo
Err or
Check
End of
Frame
01H~FFH 06H 0~nnH 0 ~ nnH Setting Value CRC Lo CRC Hi
1 Byte 1 Byte 2Byte 2 or 4 Byte 2 Byte
Response:(Response to the writing data if the command is correct)
Start of
Frame
Address
Field
Function
Code
Start
Addr ess
Hi
Start
Addr ess
Lo
Value
Hi..
Value
.. Lo
Err or
Check
End of
Frame
01H~FFH 06H 0~nnH 0 ~ nnH Setting Value CRC Lo CRC Hi
1 Byte 1 Byte 2Byte 2 or 4 Byte 2 Byte
6.7 Message Error: (A command is error)
Start of
Frame
Address
Field
Function
Code
Error
Code
Error
Check
End of
Frame
01H~FFH 83H or 86H CRC Lo CRC Hi
1 Byte 1 Byte 1 Byte 2 Byte
l Function Code:Response to the received Function Code but MSB is set to 1, it functions like
03Hð83H
l Error Code:
01:Error Function
02:Error Data Address
03:Error Data Value

static unsigned char auchCRCHi[]={
0x00,0xc1,0x81,0x40,0x01,0xc0,0x80,0x41,0x01,0xc0,
0x80,0x41,0x00,0xc1,0x81,0x40,0x01,0xc0,0x80,0x41,
0x00,0xc1,0x81,0x40,0x00,0xc1,0x81,0x40,0x01,0xc0,
0x80,0x41,0x01,0xc0,0x80,0x41,0x00,0xc1,0x81,0x40,
0x00,0xc1,0x81,0x40,0x01,0xc0,0x80,0x41,0x00,0xc1,
0x81,0x40,0x01,0xc0,0x80,0x41,0x01,0xc0,0x80,0x41,
0x00,0xc1,0x81,0x40,0x01,0xc0,0x80,0x41,0x00,0xc1,
0x81,0x40,0x00,0xc1,0x81,0x40,0x01,0xc0,0x80,0x41,
0x00,0xc1,0x81,0x40,0x01,0xc0,0x80,0x41,0x01,0xc0,
0x80,0x41,0x00,0xc1,0x81,0x40,0x00,0xc1,0x81,0x40,
0x01,0xc0,0x80,0x41,0x01,0xc0,0x80,0x41,0x00,0xc1,
0x81,0x40,0x01,0xc0,0x80,0x41,0x00,0xc1,0x81,0x40,
0x00,0xc1,0x81,0x40,0x01,0xc0,0x80,0x41,0x01,0xc0,
0x80,0x41,0x00,0xc1,0x81,0x40,0x00,0xc1,0x81,0x40,
0x01,0xc0,0x80,0x41,0x00,0xc1,0x81,0x40,0x01,0xc0,
0x80,0x41,0x01,0xc0,0x80,0x41,0x00,0xc1,0x81,0x40,
0x00,0xc1,0x81,0x40,0x01,0xc0,0x80,0x41,0x01,0xc0,
0x80,0x41,0x00,0xc1,0x81,0x40,0x01,0xc0,0x80,0x41,
0x00,0xc1,0x81,0x40,0x00,0xc1,0x81,0x40,0x01,0xc0,
0x80,0x41,0x00,0xc1,0x81,0x40,0x01,0xc0,0x80,0x41,
0x01,0xc0,0x80,0x41,0x00,0xc1,0x81,0x40,0x01,0xc0,
0x80,0x41,0x00,0xc1,0x81,0x40,0x00,0xc1,0x81,0x40,
0x01,0xc0,0x80,0x41,0x01,0xc0,0x80,0x41,0x00,0xc1,
0x81,0x40,0x00,0xc1,0x81,0x40,0x01,0xc0,0x80,0x41,
0x00,0xc1,0x81,0x40,0x01,0xc0,0x80,0x41,0x01,0xc0,
0x80,0x41,0x00,0xc1,0x81,0x40};
static unsigned char auchCRCLo[]={
0x00,0xc0,0xc1,0x01,0xc3,0x03,0x02,0xc2,0xc6,0x06,
0x07,0xc7,0x05,0xc5,0xc4,0x04,0xcc,0x0c,0x0d,0xcd,
0x0f,0xcf,0xce,0x0e,0x0a,0xca,0xcb,0x0b,0xc9,0x09,
0x08,0xc8,0xd8,0x18,0x19,0xd9,0x1b,0xdb,0xda,0x1a,
0x1e,0xde,0xdf,0x1f,0xdd,0x1d,0x1c,0xdc,0x14,0xd4,
0xd5,0x15,0xd7,0x17,0x16,0xd6,0xd2,0x12,0x13,0xd3,
0x11,0xd1,0xd0,0x10,0xf0,0x30,0x31,0xf1,0x33,0xf3,
0xf2,0x32,0x36,0xf6,0xf7,0x37,0xf5,0x35,0x34,0xf4,
0x3c,0xfc,0xfd,0x3d,0xff,0x3f,0x3e,0xfe,0xfa,0x3a,
0x3b,0xfb,0x39,0xf9,0xf8,0x38,0x28,0xe8,0xe9,0x29,
0xeb,0x2b,0x2a,0xea,0xee,0x2e,0x2f,0xef,0x2d,0xed,
0xec,0x2c,0xe4,0x24,0x25,0xe5,0x27,0xe7,0xe6,0x26,
0x22,0xe2,0xe3,0x23,0xe1,0x21,0x20,0xe0,0xa0,0x60,
0x61,0xa1,0x63,0xa3,0xa2,0x62,0x66,0xa6,0xa7,0x67,
0xa5,0x65,0x64,0xa4,0x6c,0xac,0xad,0x6d,0xaf,0x6f,
0x6e,0xae,0xaa,0x6a,0x6b,0xab,0x69,0xa9,0xa8,0x68,
0x78,0xb8,0xb9,0x79,0xbb,0x7b,0x7a,0xba,0xbe,0x7e,
0x7f,0xbf,0x7d,0xbd,0xbc,0x7c,0xb4,0x74,0x75,0xb5,
0x77,0xb7,0xb6,0x76,0x72,0xb2,0xb3,0x73,0xb1,0x71,
0x70,0xb0,0x50,0x90,0x91,0x51,0x93,0x53,0x52,0x92,
0x96,0x56,0x57,0x97,0x55,0x95,0x94,0x54,0x9c,0x5c,
0x5d,0x9d,0x5f,0x9f,0x9e,0x5e,0x5a,0x9a,0x9b,0x5b,
0x99,0x59,0x58,0x98,0x88,0x48,0x49,0x89,0x4b,0x8b,
0x8a,0x4a,0x4e,0x8e,0x8f,0x4f,0x8d,0x4d,0x4c,0x8c,
0x44,0x84,0x85,0x45,0x87,0x47,0x46,0x86,0x82,0x42,
0x43,0x83,0x41,0x81,0x80,0x40};
25 26
The CRC Checking:
The returned CRC register is as unsigned short int.
The star address and the field of the data are transmitted, the returned CRC
registered with the low and high byte has been swapped.
/*CRC Generation Function with ‘C’ language*/
/* Msg:*message to calculate CRC upon*/
/* usDatalen: number of bytes in message*/
unsigned int CRC16(char *Msg,unsigned char usDatalen)
{
unsigned char uchCRCHi=0xFF;/*CRC high byte*/
unsigned char uchCRCLo=0xFF; /*CRC low byte*/
unsigned char uIndex;
while(usDatalen--)/*pass through message buffer*/
{
uIndex=uchCRCHi^*Msg++;/*calculate the CRC*/
uchCRCHi=uchCRCLO^auchCRCHi[uIndex];
uchCRCLo=auchCRClo[uIndex];
}
}
return (uchCRCHi<<8|uchCRCLo);
6.8 The CRC Calculation:
The CRC is calculated on all bytes of a message from the address to the
last data byte inclusively. The CRC field is the result of a CRC calculation
performed on the message contents. The meter will not reply to
commands with a CRC in error and the host should re-transmit the
command after a preset time-out period. If the host receives a string with
a CRC in error, the transaction should be retransmitted. A message is
represented for being from the address field to the data field.
The calculation is performed as follows:
1.Load a CRC register with 0xFFFF
2.Exclusive-OR the first 8 bytes of the message with the low-order of the
CRC register. Put the result in the CRC register
3.Shift the CRC register one bit to the right, filling the MSB with a zero,
and comparing the bit shifted out
4. Repeat step 3 if the SLSB=0; Exclusive-OR the CRC register with the
value A001 Hex, and put the result in the CRC register if the SLSB=1
5. Repeat steps 3 and 4 until the 8 bits have been performed and tested
6. Repeat steps 2 to 5 until all bytes have been processed
7. Swap a message with the low and high order bytes after calculating the
CRC register

27 28
6.9 Data Address: (Integers)
6.9.1 Set-up:
Address (Hex) Contents Format Word Access Range & Unit
0042 002AH
0055 0037H Modbule status RY 3-4 Integer 1 0 - 3
0054 0036H Module status RY 1_2 Integer 1 0 - 3 (Note)
0053 0035H
0052 0034H
0046 002EH
0045 002DH
0044 002CH
0043 002BH
0057 0039H Integer 1 0 - 7
0051 0033H
0050 0032H
0049 0031H
0048 0030H
0047 002FH
0056 0038H Integer 1
Modbule D/I status IO 1-3 0 - 7 (Note)
R
R
R
R
Address (Hex) Contents Format Word Access Range & Unit
0000 0000H Display Page Integer 1 0 - n (Note)
0013 000DH CT Ratio Integer 1 1 - 9999
0012 000CH 485 Case (HiLo||LoHi) Integer 1 0 - 1 (Note)
0011 000BH 485 Frame Integer 1 0 - 3
0010 000AH 485 Baud Rate Integer 1 0 - 5
0004 0004H Reserve Integer 1
0003 0003H Power on Item Integer 1 R/W 0 - n (Note)
0002 0002H Power on Page Integer 1 R/W 0 - n (Note)
0001 0001H Display Item Integer 1 0 - n (Note)
0015 000FH Password Integer 1 0 - 9999
Reserve
0009 0009H Integer 1
0008 0008H Integer 1
0007 0007H Integer 1
0006 0006H Integer 1
0005 0005H Integer 1
485 Address 1-255
Demand Average Times 1 - 60 (Note)
System Net 0 - 3 (Note)
Reserve
0014 000EH Integer 1
PT Ratio 1 - 9999
0016 0010H Reset High Integer 1 0 - 1 (1:Clear)
0017 0011H Reset Energy Integer 1
0018 0012H Reset Demand High Integer 1
0019 0013H Display High Function Integer 1 0 - 1 (1:YES)
0020 0014H Display Hour I,E Integer 1 0 - 1 (1:YES)
0021 0015H Screen Save Integer 1 0 - 99 (Note)
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
0022 0016H Out1 Type Integer 1 0 - 5 (Note)
0023 0017H Out1 Hi Set Integer 1 0 - 9999 (Note)
0024 0018H Out2 Type Integer 1 0 - 5
0025 0019H Out2 Hi Set Integer 1 0 - 9999
0026 001AH Out3 Type Integer 1 0 - 5
0027 001BH Out3 Hi Set Integer 1 0 - 9999
0028 001CH Out4 Type Integer 1 0 - 5
R/W
R/W
R/W
R/W
R/W
R/W
R/W
0029 001DH Out4 Hi Set Integer 1 0 - 9999
R/W
0030 001EH RY1 Type Integer 1 0 - 1 (Note)
0031 001FH RY2 Type Integer 1 0 - 1
0032 0020H PUL1 Pulse Numbers Integer 1 0 - 3 (Note)
0033 0021H
PUL2 Pulse Numbers
Integer 1
0 - 3
0034 0022H
Alarm1 Type
Integer 1
0 - 8 (Note)
0035 0023H
Alarm2 Type
Integer 1
0 - 8
0036 0024H
Alarm1 Set
Integer 1
0 - 9999 (Note)
R/W
R/W
R/W
R/W
R/W
R/W
R/W
0037 0025H
Alarm2 Set
Integer 1
0 - 9999
R/W
0038 0026H
Alarm1 HiLo Set
Integer 1
0 - 1 (Note)
0039 0027H
Alarm2 HiLo Set
Integer 1
0 - 1
0040 0028H
Alarm1 Delay Sec.
Integer 1
0 - 99 sec.
0041 0029H Alarm2 Delay Sec. Integer 1 0 - 99 sec.
R/W
R/W
R/W
R/W
The extended modules correspond to the variables
Ry3 Type Integer 1 0 - 1
Ry4 Type Integer 1 0 - 1
PUL3 Pulse Numbers Integer 1 0 - 3
PUL4 Pulse Numbers
Integer 1
0 - 3
Alarm3 Type
Integer 1
0 - 8
Alarm4 Type
Integer 1
0 - 8
Alarm3 Set
Integer 1
0 - 9999
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Alarm4 Set
Integer 1
0 - 9999
R/W
Alarm3 HiLo Set
Integer 1
0 - 1
Alarm4 HiLo Set
Integer 1
0 - 1
Alarm3 Delay Sec.
Integer 1
0 - 99
Alarm4 Delay Sec. Integer 1 0 - 99
R/W
R/W
R/W
R/W
Display Page 0:V,1:A,2:P,3:THD
Contents Description
Display Item Corresponding the displayed parameters and wiring configuration
Remarkable descriptions:
485 Baud Rate
0:V,1:A,2:W,3:Var,4:PF,5:HZ
485 CASE
0:n,8,2,1:o,8,1,2:e,8,1,3:n,8,1
Power On Page
Power On Item
The desired parameters in system as the meter is powered on:V,1:A,2:P,3:THD
Corresponding the displayed parameters
System nEt : Wiring configuration, 0:3P4L,1:3P3L,2:1P3L,3:1P2L
The average demand time setting: 1-60 min.
Two Words for transmission (Float/Long) 0:Lo_Hi,1:Hi_Lo
System Net
Demand Average Times
485 Frame
Screen Save Backlit energy saving mode 00:Keep lighting up 1-99: Backlit disabled
Out x Type
Out x Hi Set
RY x Type
PUL x Pulse Numbers
Alarm x Type
Alarm x Set
Alarm x HiLo Set
0:1200,1:2400,2:4800,3:9600,4:19200,5:38400
Corresponding the parameter unit and decimal point digit.
Example:240V-->240.0, the values as 2400
0:PULSE,1:ALARM
0:P 1,1:P 10,2:P 100,3:P1000
0:V,1:A,2:W,3:DMDW,4:DMDA,5:PF,6:HZ,7:THDV,8:THDA
Corresponding the parameter unit and decimal point digit.
Example:240V-->240.0, the values as 2400
0:LO,1:HI
Module RY1_2 Status
Module IO1_3 Status
0: All in normal open,1:RY1 Close,2:RY2 Close,3:RY1_2 Close
0:All in normal open,1:IO1 Close,2:IO2 Close,4:IO3 Close
0 - 1 (1:Clear)
0 - 1 (1:Clear)
Modbule D/I status IO 4-6

6.9.2 Values: Floating Point, Word transmission refers to 485 CASE for set-up
Address (Hex) Contents Format Word Access Range & Unit
4096 1000H I_R L1 Float R A
4122 101AH R
4120 1018H R
4118 1016H R
4116 1014H R
4114 1012H R
4112 1010H R
4110 100EH R
4108 100CH PF_RR
4106 100AH Var_RR
4104 1008H W_RR W
4100 1004H V_RS R
4098 1002H V_RN RV
V
Var
PF
A
V
V
VA
W
Var
PF
4102 1006H R
VA_RVA
4134 1026H R
4132 1024H R
4130 1022H R
4128 1020H R
4126 101EH R
4124 101CH RA
V
V
VA
W
Var
4146 1032H R
4144 1030H R
4142 102EH R
4140 102CH R
4138 102AH R
4136 1028H R
4148 1034H R
4160 1040H
R
4158 103EH
R
4156 103CH
R
4154 103AH
R
4152 1038H
R
4150 1036H R
4170 104AH
R
4168 1048H
R
4166 1046H
R
4164 1044H
R
4162 1042H
R
4178 1052H
R
4176 1050H
R
4174 104EH
R
4172 104CH
R
A
V
V
VA
W
Var
PF
PF
VAH
WH
WH
WH
VarH
VarH
VarH
A
A
V
W
A
V
W
I_S L2
PF_S
Var_S
W_S
V_ST
V_SN
VA_S
I_T L3
PF_T
Var_T
W_T
V_TR
V_TN
VA_T
Maximum I_R L1
Maximum V_RS
Maximum W_R
Maximum I_S L2
Maximum V_ST
Maximum W_S
4184 1058H
R
4182 1056H
R
4180 1054H
RA
V
W
Maximum I_T L3
Maximum V_TR
Maximum W_T
RHZ
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
4186 105AH
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
29 30
Address (Hex) Contents Format Word Access Range & Unit
4188 105CH Float 2 R A
4214 1076H R
4212 1074H R
4210 1072H R
4208 1070H R
4206 106EH R
4204 106CH R
4202 106AH R
4200 1068H Maximun Demand R
4198 1066H Demand R
4196 1064H R W
4192 1060H R
4190 105EH R V
W
A
A
%
4194 1062H R
Demand W
4222 107EH R
4220 107CH R
4218 107AH R
4216 1078H R
I_R THD L1
V_RS THD
V_RN THD
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
Float
2
2
Maximum
Maximum VL
Maximum W
Maximun Demand
I_S THD L2
V_ST THD
V_SN THD
I_T THD L3
V_TR THD
V_TN THD
%
%
%
%
%
%
%
%
%
%
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
SA (SaSYS)
SVF
SVL
SVA
SW
SVar
SPF
SVAH
SHZ
SVarH(Total)
SVarH(Ind)
SWH(Total)
SWH(Export)
SWH(Import)
SVarH(Cap)
SAn
S
SV THD
SA THD (SaSYS)
S (Sa
S
S
S
S
S

31 32
6.9.4 Value: Integers
Address (Hex) Contents Format Word Access Range & Unit
504 1F8H V Unit Integer 1 R
511 1FFH R
510 1FEH R
509 1FDH R
508 1FCH R
506 1FAH R
505 1F9H R
507 1FBH R
1
V Dot
A Unit
A Dot
Power_Unit
Power_Dot
Energy Unit
Energy Dot
6.9.3 Values: Long Integers, Word transmission refers to 485 CASE for set-up
Address (Hex) Contents Format Word Access Range & Unit
256 100H Hour Scale Long R
270 10EH R
268 10CH R
266 10AH R
264 108H R WH
260 104H R
258 102H R VAH
WH
VarH
VarH
VarH
262 106H R WH
Long
Long
Long
Long
Long
Long
Long
2
2
2
2
2
2
2
2
Integer 1
Integer
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
512 200H R A
I_R L1 Integer 1
525 20DH R
524 20CH R
523 20BH R
522 20AH R
521 209H R
520 208H R
519 207H R
518 206H PF_RR
517 205H Var_RR
516 204H W_RR W
514 202H V_RS R
513 201H V_RN RV
V
Var
PF/1000
A
V
V
VA
W
Var
PF/1000
515 203H R
VA_RVA
531 213H R
530 212H R
529 211H R
528 210H R
527 20FH R
526 R A
V
V
VA
W
Var
537 219H R
536 218H R
535 217H R
534 216H R
533 215H R
532 214H R
538 21AH R
540 21CH
539 21BH R
A
V
V
VA
W
Var
PF/1000
PF/1000
I_S L2
PF_S
Var_S
W_S
V_ST
V_SN
VA_S
I_T L3
PF_T
Var_T
W_T
V_TR
V_TN
VA_T
RHZ/100
See 6.9.5
See 6.9.5
See 6.9.5
See 6.9.5
See 6.9.5
See 6.9.5
See 6.9.5
See 6.9.5
Integer 1
1
Integer 1
Integer
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
1
Integer 1
Integer
Integer 1
1
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
1
Integer 1
Integer
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
544 220H
R
543 21FH
R
542 21EH
R
541 21DH
R
R
548 224H
547 223H
R
546 222H
R
545 221H
R
VAH
VAH
WH
WH
WH
WH
WH
WH
VAH Hi Word
WH (Import) Hi Word
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
VAH Lo Word
WH (Import) Lo Word
WH (Export) Hi Word
WH (Export) Lo Word
WH (Total) Hi Word
SWH(Total) Lo Word
Hour Scale:The values will be re-calculated if the ratio of primary to secondary has
been changed.
Value=Received Data * 10 ^ (Hour Scale - 3 )。
Example:The address 132H is represented as 12345678,and the Hour Scale is 5, thus the
hour reading is calculated as follows.
SWH = 12345678 * 10 ^ ( 5 - 3 ) = 12345678 * 10 ^ 2
= 12345678 * 100 = 1234567800。
= 1234567800 WH = 1234567.800 KWH = 1234.5678 MWH。
If Hour scale = 5,put 5 in the given formula then get (5-3 = 2),and the unit for energy register
is programmed as WH, so (2-3 = -1) is represented as 0.1KWH,or (2-6 = -4) as 0.0001
MWH.
SVarH(Ind)
SWH(Total)
SWH(Export)
SWH(Import)
SVarH(Cap)
SVarH(Total)
SVAH (SaSYS)
20EH Integer
SA (SaSYS)
SVF
SVL
SVA
SPF
SVar
SW
SHZ
S
S
S
S
S
S
S

Address (Hex) Format Word Access Range & Unit
549 225H Integer 1 R
556 22CH R
555 22BH R
554 22AH R
553 229H R
551 227H R
550 226H R
552 228H R
1
Integer 1
Integer
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
557 22DH R V
Integer 1
570 23AH R
569 239H R
568 238H R
567 237H R
566 236H R
565 235H R
564 234H R
563 233H R
562 232H R
561 231H R W
559 22FH R
558 22EH RW
A
A
V
W
A
V
W
W
W
A
560 230H R V
576 240H R
575 23FH R
574 23EH R
573 23DH R
572 23CH R
571 23BH R A
0.1%
582 246H R
581 245H R
580 244H R
579 243H R
578 242H R
577 241H R
VarH
Integer 1
1
Integer 1
Integer
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
1
Integer 1
Integer
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
1
Integer 1
Integer
Integer 1
Integer 1
Integer 1
Integer 1
VarH (Ind) Hi Word
VarH (Cap) Hi Word
VarH (Ind) Lo Word
VarH (Cap) Lo Word
VarH (Total) Hi Word
VarH (Total) Lo Word
VarH
VarH
VarH
VarH
VarH
An
Maximum I_R L1
Maximum V_RS
Maximum W_R
Maximum I_S L2
Maximum V_ST
Maximum W_S
Maximum I_T L3
Maximum V_TR
Maximum W_T
Maximun Demand A
Demand A
Demand W
I_R THD L1
V_RS THD
V_RN THD
Maximum
Maximum VL
Maximum W
Maximun Demand W
I_S THD L2
V_ST THD
V_SN THD
I_T THD L3
V_TR THD
V_TN THD
V THD
A
A
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
33 34
6.9.4 Value: Integers
Data Address
Contents Descriptions
1FAH V Unit Display unit in volt. 0:None,3:K,6:M, 9:G .
1FBH V Dot The decimal point position for voltage. 0:None,1:One, others for
analogy.
The displayed voltage includes phase volt, line volt, max/min values and so on.
1FCH A Unit Display unit in amp. 0:None, 3:K , 6:M, 9:G .
1FDH A Dot Display decimal point position for amp. 0:None,1:One, others for
analogy.
The displayed current includes current, neutral current, max/min values, current demand and so on.
1FEH Power Unit Display unit in power. 0:None, 3:K , 6:M, 9:G .
1FFH Power Dot The decimal point position for power. 0:None,1:One, other for
analogy.
The displayed power includes VA, Watt, Var, Max/Min Watt, Demand Watt and Var and so on.
S
S
S
S
S
S
S
SA THD (SaSYS)
SA (SaSYS)
S
S
S
S
S
S
S
6.9.5 Unit and Decimal Point
The received integer data as the primary values. And the set-up in unit and decimal point must be
completed after receiving data.
* *The received values will be correct after the set-up in CT & PT ratio has completed. **
Others:
PF:Fixed decimal point position at 3 digits.
H z:Fixed decimal point position at 2 digits.
* * If the Unit set to 6 represents M, and the Dot set to 3 represents 000, and then it can also be
regarded as Unit=K and Dot=0. The other collocation can be analogized as well.**
E xamples:11.4KV/114V、100/5A. 3P4W.
PT Ratio:100times, CT Ratio:20 times.
V Unit:3. V Dot:2. A Unit:0. A Dot:2. Power Unit:6. Power Dot:3.
If the fed volt is at 11.4kV, the fed amp is at 65A, the fed power factor is at 0.95, and the fed
frequency is at 60, and therefore, the values in VA derives from 11.4KVx65Ax3=2223000=2.223MVA
=2223kVA. And the values in W derives from VAxPF=223000x0.95=2111850.
The RS485 receives the following values:
V:1140. A:6500. HZ:6000.
Detailed explanations for the above values are below:
V:11.4KV, Unit in K (V unit=3), Decimal point at 2 digits (V Dot=2)
A:65.00A (A Unit=0), Decimal point at 2 digits (A Dot=2)
V A: 2.223 MVA or 2223 KVA
Unit in M (decimal point at 3 digits) or Unit in K (without decimal point)
W :2.111MW or 2111KW. Please refer to the description of VA
Unit in K (Energy Unit=3), without decimal point (Energy Dot=0)
P F:0.950. Decimal point at 3 digits
Hz:60.00Hz. Decimal point at 2 digits
Notice:The Unsigned Int is non-symbol, but the Signed Int is a value with positive/negative.
The values will be measured correctly if the corresponsive signals are matched.
Furthermore, some parameter units (kW, Var, Pf) display positive or negative.
Examples:PF=0.95:RS 485 values:950;PF= -0.95:RS 485 values:-(65536-64586)= -950

35
6.9.6 Value: Common integers
Address (Hex) Contents Format Word Access Range & Unit
V Unit Integer 1 R
1023 3FFH R
1022 3FEH R
1021 3FDH R
1020 3FCH R
1018 3FAH R
1017 3F9H R
1019 3FBH R
1
V Dot
A Unit
A Dot
Power_Unit
Power_Dot
Energy Unit
Energy Dot
Integer 1
Integer
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
1024 400H R V
V_RN Integer 1
1037 40DH R
1036 40CH R
1035 40BH R
1034 40AH R
1033 409H R
1032 408H R
1031 407H R
1030 406H I_RR
1029 405H V_TR R
1028 404H V_ST R V
1026 402H V_TN R
1025 401H V_SN RV
V
V
A
A
A
W
PF/1000
WH
WH
W
1027 403H R
V_RS V
1043 413H R
1042 412H R
1041 411H R
1040 410H R
1039 40FH R
1038 40EH R W
A
A
HZ/100
V
V
1049 419H R
1048 418H R
1047 417H R
1046 416H R
1045 415H R
1044 414H R
1050 41AH R
VA
Var
VAH
VAH
VarH
VarH
A
I_S
I_T
A
VL
VA
Var
HZ
See 5.9.5
See 5.9.5
See 5.9.5
See 5.9.5
See 5.9.5
See 5.9.5
See 5.9.5
See 5.9.5
Integer 1
1
Integer 1
Integer
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
1
Integer 1
Integer
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
1
Integer 1
Integer
Integer 1
Integer 1
Integer 1
Integer 1
Integer 1
VAH Hi Word
VAH Lo Word
WH (Total) Hi Word
WH (Total) Lo Word
PF
Maximun Demand A
Demand A
Demand W
Maximun Demand W
VarH (Total) Hi Word
VarH (Total) Lo Word
** Energy/Hour: Lo Wordis set ahead, Hi Word is set behind.
6.9.7 Values:THD Current
Address (Hex)
HR
1280 500H
02' HR
1287 507H
1286 506H
1285 505H
1284 504H
1282 502H
1281 501H
1283 503H
03' HR
04' HR
05' HR
06' HR
07' HR
08' HR
09' HR
1288 508H
10' HR
1301 515H
1300 514H
1299 513H
1298 512H
1297 511H
1296 510H
1295 50FH
1294 50EH
16' HR
1293 50DH
15' HR
1292 50CH
14' HR
1290 50AH
12' HR
1289 509H
11' HR
1291 50BH
13' HR
1307 51BH
1306 51AH
1305 519H
1304 518H
1303 517H
1302 516H
1309 51DH
1308 51CH
17' HR
18' HR
30' HR
28' HR
29' HR
31' HR
19' HR
27' HR
22' HR
21' HR
20' HR
26' HR
25' HR
23' HR
24' HR
Format Word:1 Access:R Unit:0.1%
:Integer
Contents
IR
Address (Hex)
Contents
IS
Address (Hex)
Contents
IT
1310
51FH
1317
526H
1316
525H
1315
524H
1314
523H
1312
521H
1311
520H
1313
522H
1318
527H
1331
534H
1330
533H
1329
532H
1328
531H
1327
530H
1326
52FH
1325
52EH
1324
52DH
1323
52CH
1322
52BH
1320
529H
1319
528H
1321
52AH
1337
53AH
1336
539H
1335
538H
1334
537H
1333
536H
1332
535H
1339
1338
53BH
1340 53CH
1347 543H
1346 542H
1345 541H
1344 540H
1342 53EH
1341 53DH
1343 53FH
1348 544H
1361 551H
1360 550H
1359 54FH
1358 54EH
1357 54DH
1356 54CH
1355 54BH
1354 54AH
1353 549H
1352 548H
1350 546H
1349 545H
1351 547H
1367 557H
1366 556H
1365 555H
1364 554H
1363 553H
1362 552H
1369 559H
1368 558H
51EH
36
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
IR IS IT
S
S
S
S
SS
S
S
S
S
S
SVF
S
S
S
S
S
S
SW (SaSYS)
3F8H
1016

Address (Hex)
HR
1370 55AH
02' HR
1377 561H
1376 560H
1375 55FH
1374 55EH
1372 55CH
1371 55BH
1373 55DH
03' HR
04' HR
05' HR
06' HR
07' HR
08' HR
09' HR
1378 562H
10' HR
1391 56FH
1390 56EH
1389 56DH
1388 56CH
1387 56BH
1386 56AH
1385 569H
1384 568H
16' HR
1383 567H
15' HR
1382 566H
14' HR
1380 564H
12' HR
1379 563H
11' HR
1381 565H
13' HR
1397 575H
1396 574H
1395 573H
1394 572H
1393 571H
1392 570H
1399 577H
1398 576H
17' HR
18' HR
30' HR
28' HR
29' HR
31' HR
19' HR
27' HR
22' HR
21' HR
20' HR
26' HR
25' HR
23' HR
24' HR
Format Word:1 Access:R Unit:0.1%
:Integer
Contents
VR
Address (Hex)
Contents
VS
Address (Hex)
Contents
VT
1400
579H
1407
580H
1406
57FH
1405
57EH
1404
57DH
1402
57BH
1401
57AH
1403
57CH
1408
581H
1421
58EH
1420
58DH
1419
58CH
1418
58BH
1417
58AH
1416
589H
1415
588H
1414
587H
1413
586H
1412
585H
1410
583H
1409
582H
1411
584H
1427
594H
1426
593H
1425
592H
1424
591H
1423
590H
1422
58FH
1429
1428
595H
1430 596H
1437 59DH
1436 59CH
1435 59BH
1434 59AH
1432 598H
1431 597H
1433 599H
1438 59EH
1451 5ABH
1450 5AAH
1449 5A9H
1448 5A8H
1447 5A7H
1446 5A6H
1445 5A5H
1444 5A4H
1443 5A3H
1442 5A2H
1440 5A0H
1439 59FH
1441 5A1H
1457 5B1H
1456 5B0H
1455 5AFH
1454 5AEH
1453 5ADH
1452 5ACH
1459 5B3H
1458 5B2H
578H
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
VR VS VT
37
6.9.8 Value:THD Voltage
Other manuals for T250
1
Other Taik Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

GW Instek
GW Instek GFC-8131H user manual

PRECISION DIGITAL
PRECISION DIGITAL pd663 user manual

GE
GE Power Quality Meter Series instruction manual

Schwaiger
Schwaiger 661576 user guide

CODEL
CODEL Energy Tech 301 Installation, Commissioning, Operating & Maintenance Manual

Chauvin Arnoux
Chauvin Arnoux MAP COMPACT Installation and operating manual