TATAREK RT-08G-BUF-SOLAR User manual

Zakład elektroniczny TATAREK Jerzy Tatarek
USER MANUAL
Program version 3.0 ( )30.07.2012
1
FIREPLACE LUX (RT-08G-BUF-SOLAR)
CONTROL UNIT OF THE HEATING SYSTEM
WITH THE FIREPLACE CONTROLLED
BY THE AIR DAMPER
16
RT08G_BUF_SOLAR/2012/v.3.0/ANG
The RT-08G-BUF -SOLAR control unit controls the heating system based on the water jacket
fireplace that is a heat source, in which the combustion process is controlled by the air damper. The
heat receivers is the buffer container (BUF), which is additionally loaded up from the solar collector
(KSL).
! The control unit is equipped with its own emergency power source - breaks in power
supplying up to 8 secs do not interrupt its operation (over the time the emergency buffering
power source is activated).
1.Basic technical parameters
Power 230V/50Hz
Power consumption without load 5W
Max connection power 750W
Operation conditions 0-50 C, humidity 10-90%
(no condensation)
Housing protection class IP41
Fuse 6,3A/250V
Number of outputs to control pumps 3 * 250W/230V/50Hz
Number of nonvoltage outputs 1
Number of outputs to control the air damper drive 1 * 5V/500mA/DC
Number of water temperature sensors 3 * PT1000 (-50...+200 C )
Temperature measurement precision 2 C
Temperature measurement resolution 0,5 C
o
o
o
o
WARNING!!!
WE INFORM THAT THE OFFERED CONTROL UNIT
CAN BE ONLY APPLIED TO THE FITTING DEVICES.
THE REQUIREMENTS OF THE TECHNICAL AND
BUILDING STANDARDS CONCERNING THE
CORRECTNESS OF
WRONG USAGE OF THE CONTROL UNIT CAN LEAD
BOTH TO ITS DAMAGE AND IN EXTREME CASES TO THE
DAMAGE OF THE FIREPLACE INPUT AND HEATING
SYSTEM CONTROLLED BY THE FIREPLACE AS WELL ,
ALONG WITH THE DEVICES THAT COOPERATE WITH
THE HEATING SYSTEM.
STOVE-FITTER AND HEATING
SYSTEMS HANDLING THE FIREPLACE INPUTS MUST
BE MET.
Zakład elektroniczny TATAREK Jerzy Tatarek
50-559 Wroclaw, 75 Swieradowska st.
ph. (071) 367-21-67, 373-14-88, fax 373-14-58; Tax index number 899-020-21-48;
Bank account: BZ WBK S.A. WROCLAW 6910901522-0000-0000-5201-9335

215
2. Principle of Operation
The main function of the control unit is to keep temperature in the water jacket at the preset
value. The task is realized by measuring temperature (T3) and controlling the cold air choke valve
(PP) properly. Fireplace operation temperature is defined by the
parameter (see PARAMETERS LEVEL 1).
If the fireplace temperature (T3) is higher than the parameter the
choke valve is gradually shut off limiting air supply, and if the temperature (T3) is lower than the
parameter the choke valve is gradually opened up.
The second function is control the loading pump of the BUF container (P2). The pump P2 runs if the
fireplace temperature exceeds “ ” and is above the buffer temperature (T1) by the
parameter (see see PARAMETERS LEVEL 1).
The third function is controlling the loading pump of the BUF container from the solar collector KSL
(P1). The pump of the collector P1 runs if the temperature of the collector (T2) exceeds the
temperature of the buffer (T1) by the parameter value "<64>DeltaKSL".
The next function is to control the circulating pump (P3) of central heating system. The pump
works if the buffer temperature exceeds the value.
<20> “FIREPLACE Temp.”
<20> “FIREPLACE Temp.”
<20> “FIREPLACE Temp.”
BUFF ON <61>
DeltaBUF
CH ON
Fig. 1 Basic operation configuration of the control unit
WAW- Warm Applicable Water container (boiler)
FIREPLACE- Water jacket fireplace
BUF- Buffer container
KSL- Solar collector (or another heat source)
CH- Central heating system
T1- Temperature sensor of the BUF buffer container
T2- Temperature sensor of the KSL solar collector
T3- Temperature sensor of the FIREPLACE fireplace water jacket
P1- Pump loading the BUF from KSL
P2- Pump loading the BUF from FIREPLACE
P3- Circulating pump CH
PP- Electronically controlled air damper of the fireplace
Admission
date
Realization
date Signature Remarks
CH
FIREPLACE

14 3
2.1 Air damper operation
The air damper regulates an air supply to the combustion chamber, which allows the temperature of
the fireplace water jacket to be kept at the preset value. The task is realized by comparing the
temperature of the water jacket(T3) and preset temperature (the <20>
parameter) and then by gradual opening/shutting the air damper. The change of the air damper
position is done every 20secs
The shutdown of the control unit automatically causes the air damper to be set at the rest position
defined by the <50> parameter (Default setting is 0% - full shut-off).
C (
) and higher than temperature in the container by 1 C (parameter
).
Turning off the pump below the parameter causes a faster heating of the
water jacket above the dew point and as a result the longer life time of the fireplace.
After the loading the BUF pump still runs for 1min (parameter " ")
The control unit protects the system from freezing, automatically turning on the circulating pump if
the measured temperature is below 4 C.
The control unit realizes the after season rundown of the pump by switching it on for 1 min if it
doesn’t operate for a week.
5 C (parameter ).
The control unit realizes the after season rundown of the pump by switching it on for 1 min if it
doesn’t operate for a week.
If the buffer temperature exceeds the preset value of 45 C (the <31>
parameter) the CH pump turns on.
The control unit protects the system from freezing, automatically turning on the circulating pump if
the measured temperature is below 4 C.
The control unit realizes the after season rundown of the pump by switching it on for 1 min if it
doesn’t operate for a week.
Turning off the heating system in summer time (the CH pump doesn’t
operate). Fireplace only works in the function of loading the BUF buffer.
tandard operation
SUMMER-
”FIREPLACE Temp.”
ChokeV State OFF
parameter <60>
PumpBUFtemp.ON
“<61>DeltaBUF”
<60> PumpBUFtemp.ON
<63>RundownTimeBUF
"<64>DeltaKSL"
Switch-on Temp. of PUMPS
2.2 Operation of the loading pump of the buffer (P2)
CH pump operation (P3)
o
o
o
0
o
o
2.3 Operation of the KSLpump (P1)
2.4
2.5 Summer mode CH
The collector pump P1 runs if the collector temperature (T2) exceeds the buffer temperature (T1) by
the value
! Exceeding the maximum collector temperature (parameter " ") causes the
KSL pump (P1) to be switched on in order to protect the solar collector against overheating. The KSL
protection has a higher priority than limiting the BUF temperature.
- s
<26> ALARM Temp KSL
ON
The control unit controls the pump loading the buffer. The BUF pump (P2) can be switched on if
water temperature in the fireplace is above the preset threshold 48
You can select "ModeCH"=SUMMER setting, in which the CH pump doesn't run.
CE CONFORMITY DECLARATION
Ref. No. 58.RT.01.2007/1/B
We, ZAKŁAD ELEKTRONICZNY TATAREK Jerzy Tatarek
75 Swieradowska St. , 50-559 Wroclaw
declare under our sole responsibility that
the following product:
the control unit of the heating system with the fireplace controlled by the air damper
model:
PN-EN 55022: 2000 - (EMC)- IT devices
Characteristics of radioelectric noises. Acceptable levels and measurement methods
:
Laboratory IASE 51-618 Wroclaw, 1 Wystawowa st.
Test report No. 39/DL/I/07 of 22.06.2007
41/DL/I/07 of 03.07.2007
Place of issue: Manufacturer representative:
Wroclaw Mirosław Zasępa
Date of issue: Position:
08.2007 Konstruktor
RT-08G-BUF-SOLAR
is in conformity with the basic requirements included in Directive EMC 2004/108/WE of 15.12.2004 (the
electromagnetic compatibility law of 13.04.07) and Directive LVD 2006/95/WE of 21.08.07 (Laws Journal
of 2007 No. 155 pos. 1098) regarding the requirements for electric devices.
To the conformity evaluation the following harmonized standards were used:
PN-EN 60730-2-1: 2002 - Automatic electric control units for house usage and the like. Part 2-1:
Specific requirements regarding electric control units for electric house
devices
PN-EN 60730-1: 2002 - Automatic electric control units for house usage and the like.
Part 1: General requirements.
Electromagnetic compatibility
Complementary information
Electronic Engineering Plant TATAREK
has initiated management system and complies with the following standard :
ISO9001: 2000 CERTIFICATE No. 133/2004 of 01.2004
Polish Foreign Trade Chamber
The last two digits of the year in which the CE marking was affixed: 07

413
2.6
3.
“CONTROL”output
Service of the control unit
The control unit is equipped with the CONTROL relay whose contacts can be used e.g. to switch off
another heat source when the fireplace works. The parameter defines the
function of the relay more precisely. (see PARAMETERS LEVEL 3)
CONTROL relay turned off
CONTROL relay turned on
There are elements on the control panel (fig. 2). In the turn-off state only the orange stanby state
LED (7) lights and the graphic display shows current temperature of the water jacket and current
time. The turn-on of the control unit follows by pressing the button ( ) ON/OFF . In order to turn
it off press once more the button ( )and at the same time hold it down for about 1sec. In case of
supply voltage decline the control unit comes back to the state before the decline.
The operation state is presented on the graphic display ( ). The screens inform about the operation of
devices, temperature of sensors; they make it possible to change the parameters etc..The change of
screen is done by pressing the CHOOSE button ( ). If this is the screen that is able to change a
parameter, press the CONFIRM button ( ) , which causes blinking of the parameter field to be
changed. By pressing “+”( )or “-”( ) one can alter its value.
If there are more parameter fields on the screen (e.g. setting the clock) then one will go among them
by pressing the CHOOSE button ( ). By clicking the CONFIRM button ( ) one confirms the changes
- the parameter field stops blinking.
The changed parameter not confirmed for 10 secs is not accepted by the control unit and it recalls a
previous value of the parameter.
The button F2-ESC (8) is for cancelling a current operation and going over to the screen of the
fireplace.
<12> CONTROL Relay
3
3
2
7
6
4 5
7 6
!
!
Fig.2 Control panel view
Connection cable of the control may be replaced only
by producer or his authorized service locations
WARRANTY
WARNING !
ANY MODIFICATION OF THE CONTROL UNIT MADE BY A USER CAN
BE THE CAUSE OF SAFETY CONDITIONS DETERIORATION AND CAN
EXPOSE THE USER TO ELECTRIC SHOCK OR DAMAGE DEVICES
SUPPLIED.
Date of sale Seller's signature and stamp
Zakład elektroniczny TATAREK Jerzy Tatarek
50-559 Wroclaw, 75 Swieradowska st
ph. (071) 367-21-67, 373-14-88, fax 373-14-58; tax index number 899-020-21-48;
Bank account : BZ WBK S.A. O/WROCŁAW 6910901522-0000-0000-5201-9335
1.Warranty is valid [24] months from the date of sale.
2.Producer does not take responsibility for any mechanical damages made by user.
3.MAKING REPAIRS OR MODYFYING THE DEVICE BY USER IS
FORBIDDEN AND CAUSES WARRANTY CANCELATION
4.Warranty card is valid only with date of sale, seller's signature and stamp
5.Warranty and after-warranty repairs should be done only by producer, damaged
regulators should be sent to producer in order to make all repairs needed.
6.Warranty protection includes the EU
7.Warranty does not exclude, not restrict and not suspend buyer’s rights coming from
the incompatibility of the article with the agreement (Laws Journal No. 141 Pos. 1176)
WARNING!
1. Producer does not take the responsibility for damage
caused by atmospheric discharge
2. and overvoltage in the mains
3. Burnt fuses are not subject to warranty replacement
Register No.. GIOS: E 0002240WZ
Worn out electronic
and electric devices must be transfered to
the utilization collection place, where will
be accepted for free
ARGO-FILM
Recycling Plant No. 6
180 Krakowska st., 52-015 Wroclaw
ph.: 071 794 43 01,
0 515 122 142
“ON/OFF”
“CHOOSE”
“CONFIRM”

5
Załączony przekaźnik STEROWANIE
Wskazanie górnego czujnika CWU
Wskazanie dolnego czujnika CWU
Wskazanie czujnika kominka
CO *
KOM ?CWU
80 o
73 o68 o
12
1. Control unit status diode: alarm (red), standby (orange), operation (green), manual MAN
(blinking green)
2. Graphic display
3. Button F1: switch-on/off power supply
4. Increase button
5. Decrease button
6. Confirmation button
7. Parameter selection button
8. Button F2 (ESC - return to the main screen)
The control unit is equipped with the clock, which enables the automatic change of the control unit
operation at different times of day. 24 hrs are divided into 5 time zones ( ) . Each zone
has a start time FROM and an end time TO. The same start and end time means the zone isn’t active,
which doesn’t change the settings of the control unit. The time zones can overlap each other in that
case binding are the settings for the active zone of higher number.
is not seen till the following alarm situation takes place:
1. Damage of the T1(BUFFER) sensor. The text shows up.
2. Damage of the T2(KSL) sensor .The text shows up.
3. Damage of the T3 sensor of the fireplace. The text shows
up.
4. The exceeding of
The text shows up.
5. The exceeding of
The text shows up.
6. The exceeding of
The text shows up.
Time zones
$1, $2, $3, e4, e5
BUF temp. sensor (T1) damaged
KSL temp. sensor (T2) damaged
Fplace temp. sensor (T3) damaged
too high temp. of the fireplace
too high temp. of the buffer
too high temp. of the collector
Alarm screen “ALARM”
the limit temperature of the fireplace defined by the
parameter.
the limit temperature of the buffer defined by the
parameter.
the limit temperature of the collector defined by the
parameter.
<21> ALARM Temp.
<24> BUF ALARM
Temp.
<26> ALARM Temp
KSL
3.1
!
3.2 Screens
THIS SOFTWARE VERSION DOES NOT INCLUDE THE TIME ZONES.
Pump P1
230V/50Hz
Pump P2
230V/50Hz
Pump P3
230V/50Hz
+
+
+
0
0
0
VCC
STER
GND
Temperature
sensors
AIR DAMPER
T1
PP
PE
T2
T3
MAINS
230V/50Hz
NNNN
L1 2 3LLL
N
PE
L
RED
BLUE
BLACK
Fig.3 Electrical wiring diagram
PP Air damper
T1 Temperature sensor of the BUF container (buffer container)
T2 Temperature sensor of the KSL collector (solar collector)
T3 Temperature sensor of the fireplace water jacket FIREPLACE
P1 Pump loading the BUF container from KSL
P2 Pump loading the BUF container from FIREPLACE
P3 CH circulating pump
CONTROL
FUSE
Alarm
text
4 Installing the control unit
!
!
!
!
THE SHOULD NOT BE EXPOSED TO WATER AFFECTING. ITS
ENVIRONS OUGHT TO BE CLEAN.
THE PRODUCER DOESN'T TAKE ANY RESPONSIBILITY FOR DAMAGES CAUSED BY
WRONG USAGE OF THE .
Connection diagram of the elements of the control unit is presented on fig. 3
THE CONTROL UNIT IS SUPPLIED BY 230V/50HZ .
ANY MOVES REGARDING INSTALLATION SHOULD BE MADE AT
THE DISCONNECTED MAINS.
THE CONTROL UNIT HAS TO BE CONNECTED TO THE MAINS WITH THE ZERO-PIN.
CONTROLUNIT
CONTROLUNIT

6
11
Alarm situation is accompanied by a broken sound alarm that can be turned off by pressing the
CONFIRM button (6)
shows the current temperature of the fireplace and the level of
air damper opening.
In the emergency of exceeding the temperature the corresponding pumps start to run to
cool off the system. The KSL protection ha a higher priority than limiting the BUF
temperature.
!
Screen of the fireplace operation
It’s a stable state, that is, in order to change it you need to press the CHOOSE button (7)
During appearing this screen you can change the preset temperature of the fireplace (the
parameter). After pressing the CONFIRM button (6) the preset temperature
blinks whose value can be altered with the buttons “+”(4) or “-”(5) To confirm the changes you
need to press the CONFIRM button (6) once more.
If the manual mode is set ( ) (the green LED diode (7) blinks.) you can
manually control the air damper-. The “+”button (4) causes the opening of the air damper (one step
10%) and the “+”button (5) causes its closing.
<20>
FIREPLACE Temp.
FIREPLACE MODE=MAN
There are the following operation modes of the fireplace:
MAN-
OFF-
AUTO-
ON-
Full automatic burning cycle in the fireplace (firing up - operation - burning
out).
Automatic control locked - only manual control of the air damper is
available. Green status diode blinks.
Setting the air damper to the rest position ( the
parameter).Green status diode doesn’t light.
The air damper is automatically controlled to stabilize temperature of
the water jacket. Green status diode does light.
(1)
<50> ChokeV State OFF
(1)
(1)
Automatic operation is controlled by pressing the button Green status
diode lights during the fireplace operation and goes out when the burnt-out state is detected.
At the end of the burning-out phase the air damper sets to the rest position ( ,
which prevents a room from cooling off and protects the water attachment against freezing.
(3) “ON/OFF”.
(1)
0%, full shut-off)
Temperature of
the water jacket
of the fireplace (T3)
Current
time
Time
zone
Operation mode
of
the fireplace
Preset
temperature
Air damper
opening
FIREPLACE
Password
The changes of important parameters are possible only at unlocked password. To unlock the password you
need to input proper sequence of digits with the buttons “+/-“. With the CHOOSE button (7) to change the
digits position and CONFIRM button (6) to acknowledge all and finish the procedure of changing the
password. The unlocked password is set to “0000”. Once again entering into the password change procedure
causes a new password to be set.
!
!
PASSWORD „9999”HAS CONSIDERABLE MEANING. IT CAUSES THE REACTIVATION OF THE PREVIOUS
PASSWORD IF PRESENT WITHOUT IT BEING EXPOSED.
PASSWORD OF PRODUCER'S SERVICE IS UNIQUE AND IS NOT DEPENDENT ON THE USER'S PASSWORD-
IT SHOUDN'T BE EXPOSED TO THE USER. INSTEAD OF THAT THE SERVICE CAN SET THE USER HIS OWN
PASSWORD.
Examples of passwords:
1.The control unit is installed with the unlocked password. The user can enter his own password e.g. “1234”.
From this moment the important parameters cannot be altered without the password being unlocked (that is,
resetting the password “1234”). After changing essential parameters the user can leave the control unit
unlocked, set any new password or enter “9999”, which activates the password “1234”
2. Producer gives the control unit with the set password. The user cannot alter the important parameters. The
servic can change the settings with its own secret password.At the end a serviceman enter the secret password or
“9999”, the user still hasn't access to the important parameters.
3. Producer gives the control unit with the set password. The user cannot alter the important parameters. The
servic can change the settings with its own secret password. At the end a serviceman leaves the control unit
unlocked, the user now has access to the important parameters. He can enter his own password like in example
No. 1.
4. Producer gives the control unit with the set password. The user cannot alter the important parameters. The
servic can change the settings with its own secret password. At the end a serviceman sets the password e.g.
“1234”and tells it to the user, the user has access to the important parameters but without knowing the password
the other persons cannot make the changes.
5. The user has the unlocked control unit or his own password. Serviceman decides, the user though oughtn't
have access to the important parameters. The serviceman locks the control unit with his secret password, which
removes the user's password and locks the control unit.
6. Serviceman doesn't have to know the user's password. Always he can use his own secret password and at
the end lock with the “9999”, which reactivates the user's password.
Demonstration change of the <50> ChokeV State OFF
<50> ChokeV State OFF
parameter defining the choke valve position after powering off
the control unit (Parameters level 3):
Press:
* Repeatedly the button “CHOOSE”till the parameter setting
screen appears.
* Button “CONFIRM”-> “0”blinks
* 3 times the button “+”-> “3”blinks
* Button “CONFIRM”-> “3”stops blinking (the has been chosen)
* Button “CHOOSE”-> current value of the parameter shows up
* Button “CONFIRM”-> current value, you want to change, starts blinking
* Buttons “+”and “-”-> you set the new value
* Button “CONFIRM”-> we confirm the new value
* Repeatedly the button “CHOOSE”till the “***”parameter end setting screen appears.
PARAMETERS LEVEL
Parameters Level 3

7
Automatic operation is activated by pressing the “ON/OFF”button (3) The air damper is
fully opened. In 2hrs the fireplace ought to heat itself and reach the preset temperature stabilized by
air damper movements. From that moment the temperature fall to the preset temperature by more
than 10 C (the parameter) existing for 30mins is treated as a burnout of
the fireplace. The control unit ends the operation cycle setting the air damper to the rest position.
Pressing the “ON/OFF”button (3) once more starts another operation cycle.
The green status diode (1) lights during the fireplace operation and goes out after recognizing the
burnout state of the fireplace.
operation icon in waiting for the start of a new cycle (that is, before its start or after
its end
operation icon during the cycle
It’s a stable state, that is, in order to change it you need to press the CHOOSE button.
It’s a stable state, that is, in order to change it you need to press the CHOOSE button.
AUTO
<23> FPLACE OFF Temp.
AUTO
AUTO
o
i
Operation screen of the whole system
10
Screen of pumps operation for the basic operation configuration
Screen of the operation modes enables changing the operation mode of the fireplace
and WAW container.
Possible operation modes of the fireplace are as follows (described above):
Possible operation modes of the WAW container are as follows (described above):
MAN/OFF/AUTO/ON
SUMMER/ON
Icon of the
current mode
Selection of the mode
from the list (+/-)
Temperature of the
water jacket (T3)
KSL pump
runs KSL temperature
T2
Relay CONTROL
Operation mode
of the CH pump
BUF pump
runs
BUF temperature
T1
CH pump doesn't
run
24
21
PARAMETERS LEVEL 3
PARAMETERS CAN BE CHANGED AT THE UNLOCKED PASSWORD
No NAME RANGE DEFAULT SETTING FUNCTION
Buffer limit temperature (T1) at which the alarm generates.
75...95 oC 85 oC
Fireplace temperature (T3) at which the alarm turns on.
5...25 oC 10 oC
Decreasing fireplace temperature in relation to preset temperature
at whose exceeding the countdown of 30mins begins up to the
switch-off of fireplace (stop condition at )FIREPLACE MODE=AUTO
BUF ALARM
Temp.
ALARM
Temp.
FPLACE OFF
Temp.
23
0...6 2
Switch-on of the relay ifCONTROL
2
KSL temperature is higher than “ControlRelayTemp”
3
4
5
6
BUF pump (P2) runs
CONTROL
Relay
1...2 2
1
2
ChokeV
Mode
Control type of the air damper
Dynamic control - servomotor of the is active
only if the position change of the valve is needed.
air damper
Continuous control - servomotor of the air damper is always
active.
12
51
!Parameter number (No.) is of auxiliary role - it helps to identify the name e.g. for different
language versions
63
Rundown
Time
-
BUF
0..30mins 1min
Rundown time of the BUF pump. Extending the run time of
the pump after ending the loading of the BUF
75...95 oC 85 oC
0
1
fireplace temp. higher than “ControlRelayTemp”
Buffer temp. higher than “ControlRelayTemp”
KSL pump (P1) runs
CH pump (P3) runs
ALARM is turned on (see “Alarm screens”)
16
Control-
RelayTemp
5..195oC 60 oC
Limit temperature at which the CONTROL relay turns on.
(Depending on the <12> CONTROL Relay parameter.)
64
DeltaKSL
Minimal temperature difference between BUF and KSL
required for the KSL pump P1 to run.
0...20 oC 5 oC
26
KSL (solar collector) limit temperature (T2) at which
the alarm generates.
ALARM Temp.
KSL
80..200oC 175oC
PARAMETERS LEVEL 4
OFF/ON OFF Setting the value of “ON”causes the recall of all parameters to
their default pre-sets and restarts the control unit
RESET
FUNCTION
NAME RANGE
DEFAULT
90
91
No
ProdNo. 0.....n 1
Number of the parameters set - dependent on fireplace producer
99 Service
Screen
OFF OFF The ON value causes diagnostics screen to be added
for servicing.
92 PASSWORD 0…9999 0000 „0000”PASSWORD OFF
----”PASSWORD ON
PUMPS
MODE

8
9
Screen of the clock
The screen shows the current time and the number of the activated time zone.
Time correction is possible after pressing the CONFIRM button (6) and the minutes field begins
blinking. The blinking value can be altered with the buttons “+”or “-”Pressing the CHOOSE
button (7) you come to the hours field that can be set also with the buttons “+”or “-”.
Pressing the CONFIRM button (6) confirms the changes (the clock field will stop blinking).
Normally the equals to “0”namely the parameters aren’t available.
After changing the level to “1”,“2”,“3”or “4”successive screens show the values of the
parameters.
The last screen contains “****”after which it comes back to the above mentioned screens.
Screen of setting the parameters
parameters level
PARAMETERS
Parameter
name
Unit
Upper and
lower thershold
of the changes
Parameter value
(change with +/-)
!PARAMETERS ADJUST THE CONTROL UNIT TO THE PROPERTIES OF
THE FIREPLACE AND CENTRAL HEATING SYSTEM. THEIR CHANGE
OUGHT TO BE CONSULTED WITH THE FIREPLACE PRODUCER.
ILL-CONSIDERED MODIFICATIONS CAN CAUSE UNSTABLE AND
INEFFICIENT OPERATION OF THE SYSTEM
PARAMETERS LEVEL 1
No NAME RANGE SETTING FUNCTION
20 FIREPLACE
Temp.
45...85 oC 55 oCPreset temperature of the fireplace kept by the control
unit
31
Switch-on Temp.
of PUMPS
30...75 oC 45 oCMinimal temperature of the buffer at which
the CH pump P3 can be activated.
10 Signal ON +
ALARM
OFF turns off sound signal
ON turns on sound signal
ON+ALARM turns on sound and alarm
11 Language Polish/
English/
Deutsch
Polish
DEFAULT
OFF/ON
/ON+
ALARM
PARAMETERS LEVEL 2
No NAME RANGE
DEFAULT
SETTING FUNCTION
70 Zone1 from 0:00...23:4
5
6:00 Start of the 1st time zone
71 Zone1 to 0:00...23:4
5
8:00 End of the 1st time zone
72 0:00...23:4
5
14:00
73 0:00...23:4
5
17:30
74 0:00...23:4
5
20:00
75 0:00...23:4
5
22:30
76 ECO4 from 0:00...23:4
5
23:00 Start of the 4th time zone - economic
77 ECO4 to 0:00...23:4
5
5:00 End of the 4th time zone - economic
78 0:00...23:4
5
8:00 Start of the 5th time zone - economic
79 0:00...23:4
5
13:30 End of the 5th time zone - economic
13
LCD backlight
OFF/ON OFF
OFF - backlight is active for 2mins from the last pressing
of the button
ON -backlight is active when the control unit
is switched on.
Turning off the backlight means it equals to <15>.next
14 Time zones OFF
OFF
Selection of the language version
Zone2 from Start of the 2nd time zone
Zone3 from Start of the 3rd time zone
Zone2 to End of the 2nd time zone
Zone3 to End of the 3rd time zone
ECO5 from
ECO5 to
60
PumpBUF
temp.ON
-
30...75 oC 48 oCMinimal temperature of the fireplace at which
the buffer pump P2 (BUF) can be activated.
15
LCD backlight
minimum
0...25% 10%
Minimal backlight level of the LCD (it’s vital with negative
LCD). The value 0% means a full turn-off
OFF - time zones are disabled
50 ChokeV
State OFF
0...100% 0% Position of the choke valve in the state
turned off (0%-full shut-off, 100% - full opening)
power supply
PARAMETERS LEVEL 3
PARAMETERS CAN BE CHANGED AT THE UNLOCKED PASSWORD
No NAME RANGE DEFAULT SETTING FUNCTION
33 Hysteresis
of PUMPS 1...10 oC1
oC
Temperature hysteresis of turning on/off the pumps CH/WAW.
The temperature difference between turning on
and turning off the pumps. It prevents from often
switchovers, especially if there's another heat source
in the heating system.
61 DeltaBUF -10...+10oC1
oC
Minimal temperature difference between fireplace and buffer
required for the BUF pump (P2) to run. Negative values have
application for big buffers with the temperature sensor mounted in
the upper zone
CLOCK