
16 Rev. 2.0 June 11, 2018
6-4. Output Over-Voltage Protection (OVP)
PFH series module is equipped with OVP protection function. The OVP function activates when Vo > the pre-set
OVP trip set-point. When the OVP triggers, the module output will be shut down either with latch or auto-recovery
depending on the option code specified. The standard option of PFH series modules has a latched OVP protection.
When the OVP function activates, first, cut off input ac line power. Afterwards, verify the boost bus voltage has
dropped below 10V. Check for any abnormal conditions. Then, recover output by cycling input line switch on.
The OVP latch can also be reset by turning off the module use of the On/Off pin or PMBus command.
The OVP set-point can be changed via PMBus if a full featured PFH series module is used. On the other hand, the
maximum allowed module output voltage is limited by the pre-set Boost converter bus voltage. Without increasing
this intermediate bus voltage setting, the OVP setting can only be lowered via PMBus. Otherwise, the module will
never be able to reach the OVP triggering point unless it is applied externally.
Care must be taken to avoid applying higher voltage externally to the output terminals of PFH series module.
Otherwise, it may cause the permanent damage to the module.
6-5. Boost (or Bus) Output Over-Voltage and Under-Voltage Protections (BOVP/BUVP)
PFH series module also monitors the Boost Bus voltage to protect it from the over-voltage and the under-voltage
operations. In case it reaches these pre-set points, the module will be shut down, and the PFC converter will also be
shutdown. The module will try to auto-restart after the shutdown. The inhibiting time depends on the value of the
bulk caps and bleeder resistor values used.
6-6. Output Over-Current Protection (OCP)
PFH series module is equipped with various OCP protection functions including input PFC over-current protection,
DC-DC primary side peak current cycle-by-cycle over-current protection, module over-load protection, and short
circuit protection. In normal operation condition as specified by the specification and derating curves, the OCP
protection will not be activated.
The module OCP function triggers when the output current exceeds 105% to 120% of maximum rated DC output
current of specification. The OCP triggering point is also module temperature dependent since the power module
PWB traces are used for the output current sensing. The OCP set-point is temperature compensated, and is also
calibrated during the manufacturing test process.
The module output will automatically recover when the over-load condition or the short circuit is removed.
For the module with non-latching OCP, the module will enter a 2-second hiccup retry sequence once an OCP
condition is detected. The module will try to re-start for 6 times at 2-second hiccup rate. If the over-load condition
remains after the module tried to re-start 6 times, then it will enter a 6-minute hiccup retry sequence. Once the
module enters the 6-minute hiccup mode, it will stay there until the over-load condition is removed, and the module
can operate for at least 7 minutes without any OCP alarms. After that, the module will reset back to a standard 2-
second hiccup time OCP protection mode in case an OCP alarm is detected again after 7 minutes.
When the PFH series module is operated outside the specified input voltage range, the input OCP function may also
be activated to protect the module from drawing excessive input current to damage the module.
PFH series module OCP set-point is fixed, but it can be lowered from its maximum value by PMBus if a full
featured module is used.
Note that continuous short circuit or overload condition might result in power supply over-heating or damage.