eMiniFlush With Fault Output Setup Instructions
1. Ensure that the fault output link has been wired between the eMiniFlush and AC Power Board. (As
shown below)
Note: The voltage free fault output is located on the bottom right of the AC Power Board. A Normally
Closed and a Normally Open Contact is provided and can be connected either to a fault alert system or to
stop a pump.
When setup as per these instructions the dry contact coil will energize when a fault occurs. For example,
in fault, the NC will open and the NO will close. Depending on the type of pump controller you have, you
may need to use the NO or NC. If it’s a simple interruption of a pump contactor coil then NC should be
used.
2. Wire the filter flush solenoids between Output Common and Output 2, Output 3, Output 4, Output 5
NOTE: Software output names and labels on circuit board are different. In software Output 1 is the
Master Output on the board e.g. Software Output 1 = Circuit Board Output M and Software Output
2 = Circuit Board Output 1 and etc…).
Output Common
Output 5 –Filter Valve 4
Output 4 –Filter Valve 3
Output 3 –Filter Valve 2
Output 1 –Fault Output
Output 2 –Filter Valve 1
Flush Valves Valve
Power DC Power
Supply
Digital Inputs
AC Power board
eMiniFlush
Controller
Board
Wiring required
to enable
voltage free
output relay to
operate.
3. Wiring the Techsys back flush flow switch
Connect the Brown wire from the flow switch to Input Common on the eMiniFlush
Controller Board and connect the Black wire to Input 2.
Note: If an external DP switch is in use then the switch contacts should already be
connected between Input 1 and Input Common.
The NC flow switch contacts will open when flow increases.
Common = Brown, N.C. = Black, N.O. = Blue
4. Setup Controller
a) Power up controller.
b) Using the up and down buttons navigate until “Access Code” is shown on the screen.
c) Press the “*” enter button to enter the access code screen.
d) Using the up and down buttons make the valve on the screen equal to 21.
e) Press the “*” button to lock in the access code.
f) Using the up and down buttons navigate until “ASSIGN INPUTS” is shown on the screen.
g) Enter the submenu by pressing the “*” key.
h) Using the down button navigate to Input 1
i) Check that Input 1 is set to “Ext-DP Flush”. If not change using procedure outlined in step k.
j) Using the down button navigate to Input 2
k) Check that Input 2 is set to “B-F Flow SW N/C”. If not change by first pressing “*” to begin editing,
then change the value using the up/down keys. After selecting the required value use the “*” key
to save the setting.
l) Navigate by pressing down until the screen shows “ASSIGN OUTPUTS”.
m) Press the “*” to enter the submenu.
n) Check that Output 1 is set to “Fault”. If not change by using procedure outlined in step k.
o) Check that Output 2 is set to “Filter Valve 1”. If not change by using procedure outlined in step k.
p) Check that Remaining outputs are set correctly based on the number of solenoids connected. If
an output isn’t used select “Disabled”
5. Flow Switch Tuning
a. After entering the access code navigate to the timing menu and press the “*” button to enter
the timing submenu. (see 4b)
b. Using the down button find the setting “Ex B-F Flow Dly”
c. This setting controls the acceptable amount of time that flow is allowed to continue after a
backflush.
d. If the system is faulting and nothing is wrong with the backflush valve increase this setting.
This will allow a longer timer for flow to stop after a backflush.
e. The default value is 10 seconds, which should be enough for most installations.
f. To edit press the “*” key then use the up and down buttons to adjust the value. After selecting
a new value press the “*” key again to save the setting.
Troubleshooting
a) System is faulting and no backflush has occurred. Ether the Input settings are incorrect or the
flow switch wiring is incorrect.
b) System doesn’t flush when the external dp switch is triggered. Ether faulty DP Switch,
incorrect Input settings, or incorrect DP switch wiring.
c) System won’t fault when the backflush flush flow switch is held open. Incorrect input settings
or incorrect flow switch wiring.
Input 1
Input Common
Input 2

Other Techsys Control System manuals

Techsys SWORDFISH+ User manual

Techsys

Techsys SWORDFISH+ User manual

Techsys FILTERFLUSH-001 User manual

Techsys

Techsys FILTERFLUSH-001 User manual

Popular Control System manuals by other brands

ABB Relion REC670 Operator's manual

ABB

ABB Relion REC670 Operator's manual

Fancom LUMINA 41 instruction manual

Fancom

Fancom LUMINA 41 instruction manual

Motorola DOCKCONTROLLER DC-200 quick start guide

Motorola

Motorola DOCKCONTROLLER DC-200 quick start guide

Key Digital Compass Control Quick setup guide

Key Digital

Key Digital Compass Control Quick setup guide

STREETEC autoleveling installation guide

STREETEC

STREETEC autoleveling installation guide

MG Master LV Quick installation guide

MG

MG Master LV Quick installation guide

VIPA 300S SPEED7 - CP manual

VIPA

VIPA 300S SPEED7 - CP manual

Roger MCT80M installation manual

Roger

Roger MCT80M installation manual

RKC INSTRUMENT SR Mini HG Communication instruction manual

RKC INSTRUMENT

RKC INSTRUMENT SR Mini HG Communication instruction manual

Durablow TR1004 Installation & operating instructions

Durablow

Durablow TR1004 Installation & operating instructions

Trinity Highway QuadGuard II Assembly manual

Trinity Highway

Trinity Highway QuadGuard II Assembly manual

Pneumercator LC2000 Operation manual

Pneumercator

Pneumercator LC2000 Operation manual

DoorKing 1601-083 Installation

DoorKing

DoorKing 1601-083 Installation

Force America SSC6100 CAN ULTRA Calibration manual

Force America

Force America SSC6100 CAN ULTRA Calibration manual

Extron electronics TLI Pro 201 user guide

Extron electronics

Extron electronics TLI Pro 201 user guide

Pakedge Device & Software NP36 user manual

Pakedge Device & Software

Pakedge Device & Software NP36 user manual

iKarus C42 Maintenance manual

iKarus

iKarus C42 Maintenance manual

HEIDENHAIN TNC 620 user manual

HEIDENHAIN

HEIDENHAIN TNC 620 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.