eMiniFlush With Fault Output Setup Instructions
1. Ensure that the fault output link has been wired between the eMiniFlush and AC Power Board. (As
shown below)
Note: The voltage free fault output is located on the bottom right of the AC Power Board. A Normally
Closed and a Normally Open Contact is provided and can be connected either to a fault alert system or to
stop a pump.
When setup as per these instructions the dry contact coil will energize when a fault occurs. For example,
in fault, the NC will open and the NO will close. Depending on the type of pump controller you have, you
may need to use the NO or NC. If it’s a simple interruption of a pump contactor coil then NC should be
used.
2. Wire the filter flush solenoids between Output Common and Output 2, Output 3, Output 4, Output 5
NOTE: Software output names and labels on circuit board are different. In software Output 1 is the
Master Output on the board e.g. Software Output 1 = Circuit Board Output M and Software Output
2 = Circuit Board Output 1 and etc…).
Output Common
Output 5 –Filter Valve 4
Output 4 –Filter Valve 3
Output 3 –Filter Valve 2
Output 1 –Fault Output
Output 2 –Filter Valve 1
Flush Valves Valve
Power DC Power
Supply
Digital Inputs
AC Power board
eMiniFlush
Controller
Board
Wiring required
to enable
voltage free
output relay to
operate.
3. Wiring the Techsys back flush flow switch
Connect the Brown wire from the flow switch to Input Common on the eMiniFlush
Controller Board and connect the Black wire to Input 2.
Note: If an external DP switch is in use then the switch contacts should already be
connected between Input 1 and Input Common.
The NC flow switch contacts will open when flow increases.
Common = Brown, N.C. = Black, N.O. = Blue
4. Setup Controller
a) Power up controller.
b) Using the up and down buttons navigate until “Access Code” is shown on the screen.
c) Press the “*” enter button to enter the access code screen.
d) Using the up and down buttons make the valve on the screen equal to 21.
e) Press the “*” button to lock in the access code.
f) Using the up and down buttons navigate until “ASSIGN INPUTS” is shown on the screen.
g) Enter the submenu by pressing the “*” key.
h) Using the down button navigate to Input 1
i) Check that Input 1 is set to “Ext-DP Flush”. If not change using procedure outlined in step k.
j) Using the down button navigate to Input 2
k) Check that Input 2 is set to “B-F Flow SW N/C”. If not change by first pressing “*” to begin editing,
then change the value using the up/down keys. After selecting the required value use the “*” key
to save the setting.
l) Navigate by pressing down until the screen shows “ASSIGN OUTPUTS”.
m) Press the “*” to enter the submenu.
n) Check that Output 1 is set to “Fault”. If not change by using procedure outlined in step k.
o) Check that Output 2 is set to “Filter Valve 1”. If not change by using procedure outlined in step k.
p) Check that Remaining outputs are set correctly based on the number of solenoids connected. If
an output isn’t used select “Disabled”
5. Flow Switch Tuning
a. After entering the access code navigate to the timing menu and press the “*” button to enter
the timing submenu. (see 4b)
b. Using the down button find the setting “Ex B-F Flow Dly”
c. This setting controls the acceptable amount of time that flow is allowed to continue after a
backflush.
d. If the system is faulting and nothing is wrong with the backflush valve increase this setting.
This will allow a longer timer for flow to stop after a backflush.
e. The default value is 10 seconds, which should be enough for most installations.
f. To edit press the “*” key then use the up and down buttons to adjust the value. After selecting
a new value press the “*” key again to save the setting.
Troubleshooting
a) System is faulting and no backflush has occurred. Ether the Input settings are incorrect or the
flow switch wiring is incorrect.
b) System doesn’t flush when the external dp switch is triggered. Ether faulty DP Switch,
incorrect Input settings, or incorrect DP switch wiring.
c) System won’t fault when the backflush flush flow switch is held open. Incorrect input settings
or incorrect flow switch wiring.
Input 1
Input Common
Input 2

Other Techsys Control System manuals

Techsys SWORDFISH+ User manual

Techsys

Techsys SWORDFISH+ User manual

Techsys FILTERFLUSH-001 User manual

Techsys

Techsys FILTERFLUSH-001 User manual

Popular Control System manuals by other brands

HBX HydroBloc 0110 installation manual

HBX

HBX HydroBloc 0110 installation manual

Fike 10-2539 Assembly, installation and operation instructions

Fike

Fike 10-2539 Assembly, installation and operation instructions

Bosch rexroth HS5E instruction manual

Bosch

Bosch rexroth HS5E instruction manual

TECSYSTEM NT311 ETH instruction manual

TECSYSTEM

TECSYSTEM NT311 ETH instruction manual

Crestron 4 Series product manual

Crestron

Crestron 4 Series product manual

Siemens SINUMERIK 840DE Operation & programming manual

Siemens

Siemens SINUMERIK 840DE Operation & programming manual

Briggs & Stratton 71013 Installation and operator's manual

Briggs & Stratton

Briggs & Stratton 71013 Installation and operator's manual

Norac RG11 isntallation manual

Norac

Norac RG11 isntallation manual

Balboa 300F manual

Balboa

Balboa 300F manual

Tigo TS4-R Installation & quick start guide

Tigo

Tigo TS4-R Installation & quick start guide

Adtech ADT-DK300A Manufacturer's manual

Adtech

Adtech ADT-DK300A Manufacturer's manual

Magnetic Autocontrol MHTM operating instructions

Magnetic Autocontrol

Magnetic Autocontrol MHTM operating instructions

TouchTronics PowerTouch 1000 owner's manual

TouchTronics

TouchTronics PowerTouch 1000 owner's manual

Julabo Presto LH 45 operating manual

Julabo

Julabo Presto LH 45 operating manual

BERGHOF B-Fortis CC-Slim Series user manual

BERGHOF

BERGHOF B-Fortis CC-Slim Series user manual

Mitsubishi Electric MELDAS C6 Maintenance manual

Mitsubishi Electric

Mitsubishi Electric MELDAS C6 Maintenance manual

Bosch rexroth SYDFE1 2X Series operating instructions

Bosch

Bosch rexroth SYDFE1 2X Series operating instructions

CAME Barriere GARD quick start guide

CAME

CAME Barriere GARD quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.