
6NT935-IR + TIR409
TECSYSTEM S.r.l ®
7) CONNECTION OF TIR409 SENSOR WITH THE NT935-IR MONITORING UNIT
4.20 mA output of each TIR409 sensor must be connected with 4.20 mA input of the
relevant NT935-IR monitoring unit input channel.
To wire the sensors it is sufficient a simple 4-wire cable for signal transport (from AWG24 to
AWG30), a pair for supply and the other one for 4.20mA output.
Please refer to figure 8 page 27.
8) DIAGNOSTIC OF IR TIR409 SENSORS
In case of breaking of one of the TIR409 sensors mounted on the machine to protect, output
positions on beginning or full scale values
• I<4mA: FLO message on the display
• I>20 mA: FHI message on the display
Verify the IR sensor connections and eventually replace the damaged TIR409.
9) ELECTRICAL CONNECTIONS FOR ALARMS AND FAN
Carry out the electrical connections on the removable rear terminals, after having removed
them from the meter. ALARM and TRIP relays just switch when the set temperature limits
are reached. FAULT relay (Fault) just switches when the meter is fed, while gets de-
energised when a fault occurs to the sensors, data memory fault (Ech) or when supply
voltage is lacking. FAN contact can be used to check the cooling fans or it can be inserted in
a transformer room conditioning circuit.
10) PROGRAMMED DATA DIAGNOSTIC
In case of breaking of the internal storage or corruption of programmed data, just after
switching on Ech indication appears with the relevant reporting of the Fault contact. In this
case, for safety reasons, the default parameters: Alarm Ch1-2-3= 90°C, Trip Ch1-2-3= 119°
C, Ch4= NO, Ch-Fan= 1-2-3, Fan-on= 70°, Fan-off= 60°, HFN= 000 are automatically
loaded. Eliminate Ech indication by pressing RESET and run programming to insert desired
values. Finally turn off and turn on again the unit to verify the correct memory working; in
case it is damaged and Ech still appears, please return the monitoring unit to TECSYSTEM
for repair.
11) TEMPERATURE DIAGNOSTIC
If one of the sensors detects a temperature higher than 1°C compared to set value as alarm
limit, after approximately 5 seconds ALARM relay switches together with turning on of
channel reference LED ALARM (CHn). When the release temperature limit is passed, TRIP
relay switches together with turning on of channel reference LED TRIP (CHn). As soon as
taken temperature returns to equal or lower values than set limit for ALARM and TRIP relay
switching, they de-energise with consequent turning off of relevant LED’s.
12) COOLING FAN CONTROL
NT935-IR Monitoring unit, if opportunely programmed, can control ON-OFF of fans
accompanying the transformer, according to set temperatures.
IMPORTANT NOTE: In case you have to replace an existing card with a new one, in
order to guarantee its safe and correct working, you must replace the sensor/relay/
supply connection terminals with the new terminals supplied, provided that they
are of a brand different from the previously mounted ones.