User Interface7.
Critical Settings8.
For a full list of settings and operational details, please refer to the thermostat Installation and Operation Manual
(D528) included with compatible tekmarNet®controls or download the brochure from www.tekmarcontrols.com
Display Range Access Description Set to
°F or °C
Default = °F
Installer
User
TEMPERATURE UNITS
Press the or the button to change from °F to
°C and vice versa.
On or Off
Default = On Installer
ROOM SENSOR
Select whether the built-in air temperature sensor is
on or off.
Available when:
A floor sensor or room sensor is installed on the
auxiliary sensor input.
Off, Room,
Outdoor,
Floor, Floor
dSP
Installer
AUXILIARY SENSOR
Select the type of auxiliary sensor.
Floor dSP = Show floor sensor reading in upper
number field.
Available when:
Auxiliary sensor automatically detected.
OFF, dLy
(delay), On
Default = On Installer
HEATING SUPPLY PUMP
Select how the system supply pump should operate:
On = system pump on during a call for heat.
Delay = system pump delayed 3 minutes for thermal
motor (wax actuator) zone valves to open.
Off = system pump not turned on during a call for heat.
Use when a manifold uses a Zone Group Pump.
Available when:
A reset control is present on the tekmarNet®system.•
• Press and hold down both the and buttons for 2 seconds to change from one step to the next.
• Release both buttons once the step has been reached.
• Press the or the button to change the setting, if available.
• Press and hold down both the and buttons for 2 seconds to go to the next step, OR
• After 10 seconds of no button activity, the display goes back to normal operation.
Press
+
Together
The following settings are essential to the successful operation of the system.
Important
Note: Set switch setting #4 and tekmarNet
®
system control to Unlock to change Access level to Installer. Return to Lock
setting once installation has been completed.