1
ATTENTION: Read carefully this installation Instructions before installing the device!
This manual is subject to change without notice!
1. General Description
Natron SD is a wireless addressable fire alarm optical-smoke detector, designed for operation with Natron
series wireless expander modules*. The detector is equipped with 360˚visible LED indication and a built-in
buzzer for additional sound signalization in case for announcing of events –fire alarm and finding the place of
installation. The detector is compatible with a deep wireless fire base for ceiling mounting. For prevention of
unauthorized disassembling or removing, the detector can be locked to the fire base. The detector is equipped
also with a tamper switch for self-protection of the box.
Natron SD is designed for indoor installation.
* Refer to the installation manuals of Natron WE-C, Natron WE-A and Natron WE-A/C wireless expander modules for detailed
information about the programming menus and other details.
2. Technical Specifications
Communication range with expander module ...............1500m
Battery power supply......................................................3 x CR123A 3V
Battery life.......................................................................~10 years*
Radio frequency .............................................................868MHz
Communication type.......................................................Bidirectional
Communication Protocol................................................NATRON TTE
Radio signal modulation type.........................................GFSK
Number of frequency channels......................................6 pair channels
Radiated power..............................................................≤ 20 mW
Receiver category (EN300-220-1) .................................1.5
Trace attenuation ...........................................................≥ -90dBm (during the installation)
Test transmission message period ................................300s
Sensitivity (selectable from panel/module menus) ........High/Normal/Middle/Low
Built-in buzzer volume....................................................80dB/1m
Operation temperature...................................................-10°C to +55°C
Related humidity resistance...........................................(93±3)% @ 40°С (no condensation)
Enclosure box type, color...............................................ABS, White
Dimensions (including base)..........................................Ø106x76mm
Protection .......................................................................IP30
Weight (including base and batteries)............................227g
Mounting.........................................................................Ceiling, Indoor use
Standards.......................................................................EN 54-7; EN 54-25
* With disabled operation of the built-in buzzer. If the operation of the built-in buzzer is enabled, the battery life
will be shorter - ~6 years. By default, the operation of the built-in buzzer is disabled.