
2
2.1C In remote area, duct inlet & outlet.
It is often desirable, especially in pool rooms and
finished areas, to install the Santa Fe in an adjacent
equipment room or unfinished area. Air is transferred
between the humid room and the unit via ducting.
The factory mounted humidity control on the Santa Fe
cabinet may not sense the humidity in the humid room
accurately enough with this installation method. If so,
an additional humidity control can be mounted in the
humid room and wired to the Santa Fe. Local electrical
codes must be followed when wiring the control.
2.1D In remote area, duct outlet only.
A simpler remote installation method than the one
above uses ducting only between the Santa Fe
discharge and the humid room; the Santa Fe inlet
draws air from the room in which it's located. This
works well if there is an adequate air flow path between
the two rooms; e.g., high door undercut, louvered door
or wall grill. This eliminates the need to remote mount
the humidity control. There are several potential
disadvantages to using this method. First, humid air is
drawn into the room where the Santa Fe is located.
Second, to accurately sense humidity, the blower in the
Santa Fe may need to run continuously to draw air from
the humid room into the Santa Fe room. Third, a slight
negative pressure is created in the room with the Santa
Fe which could back draft open combustion devices
located there. If such devices are present, call the
factory for specific instructions before using this
installation method or consider the option below.
2.1E In remote area, duct inlet only.
When the Santa Fe is located in a room separate from
the main area to be dehumidified, it may be desirable
to dehumidify and/or slightly pressurize that room.
Pressurization assures that open combustion devices
do not back draft as would be the case if the room was
sufficiently depressurized. This can be accomplished
by installing a duct from the humid room to the Santa
Fe inlet and by allowing the Santa Fe to discharge the
dehumidified air into the room in which it's located. An
adequate air flow path must exist between the two
rooms for this method to work well. An additional
humidity control may need to be mounted in the humid
area and wired to the Santa Fe to accurately maintain
the desired humidity. Local electrical codes must be
followed when wiring the control.
2.2 Electrical Requirements
The Santa Fe plugs into a common grounded outlet on
a 15 Amp circuit. It draws between 6 and 7 Amps under
normal operating conditions. If used in a wet area
(pool, spa room, or basement prone to flooding), a
ground fault interrupter protected circuit is required.
If an extension cord is required, it must have a
minimum of 16 gauge conductors if less than 25 feet
long and 14 gauge if greater than 25 feet.
2.3 Condensate Removal
Condensate drains by gravity via the clear hose
extending from the unit. Route the hose to a floor drain.
Use care to keep the hose as flat to the floor as
possible. Excessive humps will prevent proper
drainage.
If the Santa Fe is located too far from a floor drain for
the attached hose to reach, inexpensive 1/2" PVC pipe
can be used to extend it. It is commonly available in 10'
lengths from building supply, plumbing and hardwares
stores. It will slide tightly inside the end of the drain
hose.
If more than one length of pipe is required, they can be
joined with a short piece cut from the end of the drain
hose.
2.4 Ducting
2.4A Optional Ducting
An inlet shroud with a 8" round collar and an 8" round
exhaust collar are available from the factory that will
allow round ducting to be attached to the inlet and/or
outlet of the Santa Fe.
2.4B Ducting for Dehumidification
Ducting the Santa Fe as mentioned in sections 2.1B-
2.1E requires consideration of the following points:
Duct Sizing: For total duct lengths up to 25 feet, use a
minimum 8" diameter round or equivalent rectangular.
For longer lengths, use a minimum 10" diameter or
equivalent. Grills or diffusers on the duct ends must not
excessively restrict air flow.
Isolated Areas: Effective dehumidification may require
that ducting be branched to isolated, stagnant areas.
Use 6" diameter branch ducting to each of two or three
areas, use 4" to each of four or more areas.