
MR05 Undercounter Laboratory Refrigerators Installation, Operation and Maintenance
3
3 Introduction
This manual provide
s installation, operation and maintenance
instructions for MR05 General purpose laboratory refrigerator
models.
The control system, standard on all models, includes:
•Preset temperature setpoint (+4°C), unless optional +5C
setpoint is ordered.
•Digital temperature display with 1°C resolution.
Other standard features include:
•Keyed door locks
•CFC-free refrigerant
•CFC-free foamed in-place urethane insulation
•Quiet, hermetically sealed refrigeration compressors.
4 Inspection for Damage
At delivery, examine the exterior for physical damage while the
carrier’s representative is present.
If there is no exterior damage, unpack and inspect the equipment
within five days of delivery. If you find any damage, keep the
packing materials and immediately report the damage to the carrier.
Do not return goods without written authorization. When
submitting a claim for shipping damage, request that the carrier
inspect the shipping container and equipment.
5 Installation Instruction
This product is a complete packaged unit ready to operate when
plugged into an electrical source. Read all the instructions before
proceeding with installation.
1. The cabinet will pass through a standard 30” door opening.
2. Move the cabinet into the desired location. Make sure the
bottom of the cabinet is evenly supported. Thin shims under
the points of rest can be used to equalize the distribution of
weight. If the cabinet sets on an uneven floor, a slight rocking or
vibration might result when the condensing unit is set in
operation.
3. Make certain the cabinet is located so the front grill is
unobstructed.
4. The unit is shipped in ready to operate condition. Adjustment
of operating temperatures or setpoint is not necessary and may
adversely effect unit performance.
5. Use of electrical supply, other than that specified on the serial
plate will cause permanent damage to the product.
6. Operate the unit for several hours to allow the cabinet to reach
normal operating temperatures before storing product.
7. Do not install temperature sensing cables using the front door
gasket. Instead, use the rear access ports.
6 Operating Instructions
6.1 Temperature Control
The temperature control system is preset by the factory to maintain
a cabinet temperature of 4°C. Adjustment of operating values are
possible, but may change unit performance. Consult a qualified
service technician if you have questions about settings.
An optional 5C factory setpoint can be ordered using part number
7508TA at time of purchase.
6.2 Automatic Defrost
The defrosting process on all models is primarily accomplished by
air circulated during off-cycle periods.
Under normal conditions, the temperature warm-up during defrost is
virtually unnoticeable. However, an occasional 2°C warm-up is
possible if usage is heavy and ambient conditions are extreme.
7 Maintenance Instructions
1. The cabinet interior should be cleaned frequently. Any spilled
liquid should be wiped off immediately. A mild detergent and
lukewarm water or a solution of bicarbonate of soda (1
tablespoon per gallon of water) is recommended for cleaning
the interior and exterior of the cabinet. All surfaces should be
rinsed and thoroughly dried.
2. Shelves and/or drawers should be removed from the cabinet
and thoroughly scrubbed. Clean door gasket periodically with
water.
3. The unit cooler fan operates continuously when the door is
closed and requires no lubrication. These models require no
manual defrosting. The cooling coil automatically defrosts
when the condensing unit is on the off cycle.
4. The condensing unit needs no oil or other lubrication. The
finned condenser can become clogged with lint or dust. The
openings between the fins should be kept clean. A vacuum
cleaner or small test tube brush works well for this purpose.
This should be accomplished on an annual basis. Failure to
keep the condenser fins free of dirt and lint will hamper
operation and may damage the refrigeration system.
5. Annual inspection of the mechanical refrigeration equipment
by a qualified service provider or factory direct technician is
recommended.
6. The refrigeration system is charged with refrigerant. If the
system is opened for any reason, extreme care should be taken
to prevent the entry of moisture-bearing air. A new drier should
be installed in the lines when the system is closed.
7. The condensate evaporator pan is located behind the
compressor fan, which is behind the base grill. This pan should
be cleaned at least once a year.
Intended Use of the MR05 Series Undercounter Laboratory
Refrigerator:
The MR05 series undercounter laboratory refrigerator described
in this manual is not intended for use as a medical device and is
not intended for in vitro diagnostic cases. This unit is intended
store non-flammable general laboratory products.