Instruction Manual
MVR Molded Vacuum Reclosers
*4t*4.73

2
Section 1: Overview
*4t*4.73
Introduction
Elastimold®MVR Molded Vacuum Reclosers
Thank you for your purchase of the Elastimold®Molded Vacuum Recloser (MVR).
This state-of-the-art recloser incorporates several design features that will assure
you of many years of reliable, trouble-free service.
Features and innovations include:
tA lightweight, maintenance-free, fully
modular design allowing individual pole
replacement or shed replacement in the
event of external damage
tSpecially formulated molded EPDM main
body with overlapping silicone sheds for
improved dielectric, weatherability and
UV performance
tIntegral CT and load-side voltage
sensors with option to add source-side
voltage sensors
tElectrically linked operation so single-
phase trip provides three-phase lockout
with mechanically linked manual trip
mechanism
tHighly visible position indicator
tFully solid-dielectric design incorporating
unique diaphragm technology to isolate
high voltage from the grounded housing
tState-of-the-art magnetic actuator
mechanism

3
Table of Contents
Elastimold®.73.PMEFE7BDVVN3FDMPTFSTSECTION 1: Overview
Introduction..........................................................................2–3
Ordering Information ................................................................4
Ratings and Specifications .......................................................4
SECTION 2: Instruction Manual and Drawings
Elastimold®MVR Single-Phase and Three-Phase
Instruction Manual .............................................................5–12
Safety Instructions.............................................................5
Acceptance and Inspection................................................6
Lifting ...............................................................................6
Set-Up and Mounting ....................................................7–9
Voltage Sensor Set-Up ....................................................10
Grounding and Testing ..............................................10–11
Operation and Maintenance.............................................12
Outline Drawings..............................................................13–20
Single-Phase 15/27kV – 3188C0110.........................13–14
Single-Phase 38kV – 3188C0111..............................15–16
Three-Phase 15/27kV – 3188C0112 .........................17–18
Three-Phase 38kV – 3188C0113 ..............................19–20
Schematic Drawings ........................................................21–23
Single-Phase 15/27/38kV – 3188C0115 .........................21
Three-Phase 15/27/38kV – 3118C0114 ..........................22
Power Module (for use with SEL®351R) – 3118C0116....23
SECTION 3: Design Test Data
Elastimold®MVR Test Data Summary.....................................24
Description
of Operation
The single-phase Elastimold®MVR is controlled and
operated by the SEL®351RS Kestrel control via a 10-pin
interconnecting cable. The three-phase Elastimold®MVR
can be controlled either directly with the SEL®651Rx2
control via a 32-pin interconnecting cable or by a SEL®
351R or 351R Falcon control via a 14-pin cable connected
to an MVR power module, which then connects to the
recloser. This manual will cover the set-up and installation
of your new Elastimold®MVR Recloser. For information
on SEL®controls and their operation, please refer to
their respective manuals.
SEL is a registered trademark of Schweitzer Engineering Laboratories, Inc.

4
Section 1: Overview
*4t*4.73
Section 1: Overview
Ordering Information/Ratings and Specifications
Molded Vacuum Recloser Catalog Numbering System
.733 - 15 - 12 - 3 2 X X X X X
1 2 3 4 5 1 2 3 4 5
4."35/6.#&344&26&/5*"-/6.#&34Notes:
UÊ-}i«>ÃiÊÀiVÃiÀÃÊvÕVÌÊÜÌÊÌiÊ-®ÊÎx£,-ÊiÃÌÀiÊVÌÀ°Ê
/Àii«>ÃiÊÀiVÃiÀÃÊvÕVÌÊÜÌÊ-®651Rx2, SEL®351R or
SEL®ÊÎx£,Ê>VÊVÌÀðÊ/iÊ6,Ê«ÜiÀÊ`ÕiÊÕÃÌÊLiÊëiVwi`Ê
ÜiÊÕÃ}Ê>Ê-®ÊÎx£,ÊÀÊÎx£,Ê>VÊVÌÀ°ÊUÊ>`Ã`iÊÛÌ>}iÊÃiÃÀÃÊ>ÀiÊÃÌ>`>À`ÊÊ>ÊÕÌÃÊ>`ÊvÕVÌÊÜÌÊ>ÞÊ-®ÊVÌÀÊ>Û}Ê
>ÌÊi>ÃÌÊÌÀiiÊn6ÊÊÛÌ>}iÊ«ÕÌÃÊÊÛÌ>}iÊ«ÕÌÃÊ>ÀiÊÌÊÕÃi`ÊÜÌÊ>Ê-®351R or
Îx£,Ê>VÊVÌÀ®°ÊÊÕÌÃÊ>ÀiÊÕ«}À>`i>LiÊÌÊÃÕÀViÃ`iÊÛÌ>}iÊÃiÃ}ÊLÕÌÊÀiµÕÀiÊ>Ê
SEL®ÊÈx£,8Ó8ÊVÌÀÊÜÌÊÃÝÊn6ÊÊ«ÕÌðNotes:
UÊ-«iVvÞÊ-®ÊVÌÀÊV>Ì>}ÊÕLiÀUÊ-«iVvÞÊV>LiÊi}ÌÊÕ«ÊÌÊ£ääÊv̰
-Ì>`>À`Êi}ÌÃ\ÊÓä]ÊÎx]Ê{äÊ>`ÊxäÊv̰UÊ-«iVvÞÊ«Ì>Ê>VViÃÃÀiÃ]ÊÃÕVÊ>ÃÊÌiÊ6,Ê«ÜiÀÊ`Õi]ÊÃÕÀ}iÊ>ÀÀiÃÌiÀÃÊÀÊëiV>Ê«>V>}}MVR 3 15 12 3 2
Phase
1
1= One
Phase
3= Three
Phase
7PMUBHF$MBTT2
15 = 15kV
Class
27 = 27kV
Class
38 = 38kV
Class
*OUFSSVQUJOH3BUJOH3
12 = 12.5 kA
-= Future
Source-Side
7PMUBHF4FOTJOH4
/= No
1= One Voltage
Sensor
3= Three Voltage
Sensors
$POUSPM.PEFM5
1= SEL® 351R, SEL®
351R Falcon
(14-Pin
Connector)
2= SEL® 651R
(32-Pin
Connector)
3= SEL® 351RS
Kestrel (Single-
Phase MVR Only)
$POUSPM$BCMF-FOHUI0UIFS"DDFTTPSJFT
Sequential Numbers
Ratings and Specifications
Description 15kV 27kV 38kV*
Nominal System Voltage (kV RMS) 14.4 25 35
Rated Maximum Voltage (kV RMS) 17.1 29.3 38
Nominal Frequency (Hz) 50 or 60 50 or 60 50 or 60
Phase Spacing on 3-Phase Units (Inches) 15.5 15.5 15.5
BIL (kV) 150 150 170
Power Frequency Withstand – Dry (kV) 50 60 70
Power Frequency Withstand – Wet (kV) 45 50 60
Continuous Current (A RMS) 800 800 800
Eight-Hour Overload Current (A RMS) 960 960 960
CT Ratio 1000 to 1 1000 to 1 1000 to 1
Interrupting Current (kA RMS Symmetrical) 12.5 12.5 12.5
Making Current (kA Asymmetrical Peak) 32.5 32.5 32.5
Creepage Distances – Inches (Line to Ground)
41.5 41.5 51
Arc-Extinction Medium Vacuum Vacuum Vacuum
Insulation Medium EPDM/Silicone
Rubber
EPDM/Silicone
Rubber
EPDM/Silicone
Rubber
Mechanical Operations 10,000 10,000 10,000
Operating Temperatures
-40º C to 65 º C -40º C to 65 º C -40º C to 65 º C
Voltage Sensor Accuracy (Load/Line) 3% / 1% 3% / 1% 3% / 1%
CT Accuracy Class 1 Class 1 Class 1
Weight (Single-Phase/Three-Phase) 57/208 lbs. 57/208 lbs. 58/211 lbs.
IÊÊ-}i«>ÃiÊÎn6ÊÕÌÃÊ>ÀiÊÀ>Ìi`ÊvÀÊÕÃiÊÊ}ÀÕ`i`ÊÃÞÃÌiÃÊÞ°Ê/Àii«>ÃiÊÎn6ÊÕÌÃÊV>ÊLiÊÕÃi`ÊvÀÊÃ}i«>ÃiÊÌÀ««}ÊÊ}ÀÕ`i`ÊÃÞÃÌiÃÊÞ°ÊÀÊÕ}ÀÕ`i`ÊÃÞÃÌiÃ]ÊÌÀii«>ÃiÊÌÀ««}ÊÃÊÀiµÕÀi`°Controls
Control Type 1-Phase 3-Phase
SEL®351RS Kestrel 10-pin cable X
SEL®351R X 14-pin cable
SEL®651RX2 X 32-pin cable
Notes:
£°Ê1ÃiÊÜÌÊÌiÊÎx£,ÊÀÊÎx£,Ê>VÊVÌÀÊÀiµÕÀiÃÊViVÌÊÛ>Ê6,Ê«ÜiÀÊ`Õi°Ê/iÊ«ÜiÀÊ`ÕiÊÃÊViVÌi`ÊÌÊÌiÊÀiVÃiÀÊÛ>Ê>ÊÈÊv̰Ê
ÎÓ«ÊV>Li°Ó°Ê6Ì>}iÊÃiÃÀÃÊÀiµÕÀiÊn6ÊÊ«ÕÌðSEL is a registered trademark of Schweitzer Engineering Laboratories, Inc.

5
Section 2: Instruction Manual and Drawings
*4t*4.73
Section 2: Instruction Manual and Drawings
Instruction Manual
Safety Instructions
The following are general caution and warning statements that apply to this equipment. Additional statements related to specific
tasks and procedures are located throughout this manual.
WARNING: 3FGFSTUPIB[BSETPSVOTBGFQSBDUJDFTXIJDIDPVMESFTVMUJOEFBUITFWFSFQFSTPOBMJOKVSZPSTJHOJGJDBOU
FRVJQNFOUEBNBHF
CAUTION:
3FGFSTUPIB[BSETPSVOTBGFQSBDUJDFTXIJDIDPVMESFTVMUJOEBNBHFUPFRVJQNFOUPSJOQFSTPOBMJOKVSZSEL is a registered trademark of Schweitzer Engineering Laboratories, Inc.
WARNING:
Before installing, operating,
maintaining or testing this equipment,
carefully read and understand the contents
of this manual. Improper operation, handling
or maintenance can result in death, severe
personal injury or equipment damage.
WARNING:
Hazardous voltage. Contact
with high voltage will cause serious
personal injury or death. Follow all locally
approved safety procedures when working
around high-voltage lines and equipment.
WARNING:
Hazardous voltage. Do not
rely on the contact position indicator
to determine that the line has been
de-energized. Always establish a visible
disconnect and establish person grounds
when performing de-energized line work.
Failure to follow proper safety practices can
result in contact with high voltage, which
can cause death or severe personal injury.
WARNING:
Hazardous voltage. Recloser
and control must be solidly grounded.
Improper grounding can result in contact
with high voltage, which will cause severe
personal injury or death and equipment
damage. Disconnecting the control cable
when the recloser is energized could result
in high voltage on the pins if the recloser
tank is not grounded as specified.
WARNING:
When testing at high voltage,
the MVR and high-voltage test equipment
should be in a test cage or similar
protective area to prevent accidental
contact with the high-voltage parts. All
equipment needs to be solidly grounded.
Failure to comply can result in death,
severe personal injury and equipment
damage.
CAUTION:
All MVRs are sealed and leak
tested prior to shipment to prevent moisture
ingress. Do not open the lower cover as it is
possible that the MVR will not reseal when
the cover is closed. While the diaphragm
will keep moisture from ever entering the
high-voltage chamber, excessive moisture
ingress
could cause damage to the magnetic
actuator
mechanism and misoperation.
CAUTION:
Do not remove and replace
the side terminal in the field. The MVR
incorporates a unique diaphragm
technology that fully encapsulates the
high-voltage chamber in the MVR. The side
terminal must be vented during installation
and then sealed to prevent pressure
build-up against the diaphragm during the
installation process. Improper installation
may cause equipment damage and possible
personal injury.
CAUTION:
Rotating the terminal connector
without properly loosening the connector
will apply excessive force on the terminal
stud and could damage the interrupter
assembly.
CAUTION:
The complete recloser
system, including control, requires routine
inspection and maintenance if damage is
found to ensure proper operation. If it is not
maintained, it may fail to operate properly.
Improper operation may cause equipment
damage and possible personal injury.
CAUTION:
Follow approved safety
practices when lifting and mounting the
MVR. Use lifting rings on three-phase units
and lift smoothly, limiting shifting to avoid
damage. Do not lift three-phase MVRs by
the side terminals as damage could result.
CAUTION:
Do not energize the recloser for
service until all control settings have been
properly programmed and verified. Refer
to the appropriate SEL®control manual
for programming procedures. Failure to
comply may result in control and recloser
misoperation.
"EEJUJPOBM*OGPSNBUJPO
These instructions
are not intended to cover all details or
variations in the equipment, procedures or
processes described. Nor are they designed
to provide directions for meeting every
possible contingency during installation,
operation or maintenance. When additional
information is desired to satisfy a problem
not covered sufficiently for the user’s
purpose, please contact your local
Thomas & Betts representative.

6
Section 2: Instruction Manual and Drawings
*4t*4.73
Instruction Manual
Acceptance and Initial Inspection
Each MVR is shipped completely assembled, pretested and in the closed position from the factory.
Upon arrival, uncrate the unit (refer to Crate Removal and Visual Inspection section). Check the unit does not have
missing parts and it is in the closed position. Also check the unit for any damage that may have occurred during
shipping. Should any damage be found, file a claim with the shipping carrier and contact the factory or your local
Thomas & Betts representative.
Crate Removal and Visual Inspection
Packaging may differ depending on the units being shipped. Carefully remove the MVR from its packaging. In the case of
units shipped in crates, remove the outer crate top by removing the screws or bolts attaching it to the skid. Then unbolt the
recloser from the skid. It is then possible to lift the unit directly off the skid with a hoist. Take care when opening packaging
not to nick or cut the EPDM/silicone insulation on the MVR.
After uncrating, visually inspect the MVR for any shipping damage, including the insulation, bushings, trip lever, mounting
frame, etc. If damage has occurred, please file a claim with the shipping carrier immediately and contact your local Thomas
& Betts representative. Do not attempt to install the equipment with damages or missing parts.
Lifting
Single-phase units can be lifted and moved by
hand or by fastening a loop around the main
body. Three-phase units must be lifted using
the lifting rings.
Follow all approved safety practices when making
hitches and lifting the equipment. Lift the MVR
smoothly by using the four lifting rings on the
recloser as shown. Do not allow the unit to shift.
Be careful that the lifting sling exerts no forces
on the side terminals or on the individual poles.
CAUTION:
Follow approved safety practices when lifting and mounting the MVR. Use lifting rings on three-phase units and
lift smoothly, limiting shifting to avoid damage. Do not lift three-phase MVRs by the side terminals as damage could result.
Lifting Rings
Four Lifting Ring Detail

7
Section 2: Instruction Manual and Drawings
*4t*4.73
Set-Up
WARNING:
Before installing, operating, maintaining or testing this equipment, carefully read and understand the
contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury
or equipment damage.
Set-up and testing of the recloser
can be performed at maintenance
facilities, test laboratories or directly
in the field once appropriate control
supply voltage is made available.
Connect the recloser to the
appropriate control:
tSingle-phase units — the MVR
should be connected to the
SEL®351RS Kestrel control via
a 10-pin interconnecting cable
tSEL®651Rx2 control — the
MVR should be connected
to the control via a 32-pin
interconnecting cable
tSEL®351R or 351R Falcon
control — the 14-pin cable
should be connected to the
MVR power module, and the
6-ft. 32-pin cable should be
used to connect the power
module to the MVR*
The recloser receives the necessary
signal to open and close from the
control circuitry. The control is
powered from an external supply
voltage but is also supplied with
a battery backup system that is
fully charged from the factory. The
battery backup system, located in
the control cabinet, is shipped in
the “off” or disconnected position.
For information on how to connect
the battery, please refer to the
appropriate SEL®control manual.
The figure at right shows a typical recloser, control and power supply interconnection layout.
I Ìi\Ê6,ÃÊÀ}>ÞÊ«ÕÀV>Ãi`ÊvÀÊÕÃiÊÜÌÊÌiÊ-®ÊÎx£,ÊÀÊÎx£,Ê>VÊVÌÀÃÊ>ÀiÊ`iÃ}i`ÊÌÊLiÊi>ÃÞÊÕ«}À>`>LiÊvÀÊÕÃiÊÜÌÊÌiÊ-®ÊÈx£,ÊVÌÀ°ÊÊ*i>ÃiÊVÌ>VÌÊÞÕÀÊV>Ê/>ÃÊEÊiÌÌÃÊÀi«ÀiÃiÌ>ÌÛiÊvÀÊÃÌÀÕVÌðÊ
SEL is a registered trademark of Schweitzer Engineering Laboratories, Inc.
POWER
MODULE
GROUND
CONTROL
SUPPLY
PT
LINE
NEUTRAL
GROUND
Line
Recloser
351R and 351R Falcon only;
Cable Plugs Directly into Recloser
on 351RS Kestrel and 651R
Utility
Pole
Recloser
Control
Protective
Shield around
Pole Ground
Control
Cable
System
Neutral
Pole
Ground Arresters
Typical Installation Detail

8
Section 2: Instruction Manual and Drawings
*4t*4.73
Instruction Manual
Mounting
Note: Use extreme care in handling the recloser so that no
force is exerted on the side terminals or on the individual
poles as damage may result.
4JOHMF1IBTF6OJUT
Attach the mounting bracket to the pole or structure
using a 3⁄4" lag or thru bolt (customer supplied). Hoist the MVR by creating
a sling around the main body and the side terminal on the recloser, and
lower it into the mounting bracket. Orient as desired and then lock in
place by torquing the two 3⁄8"-16 set screws to 20 ft.-lbs. The single-
phase recloser can be oriented from 0 to 180 degrees as shown at right.
5ISFF1IBTF6OJUT
Hoist the MVR by creating a sling that uses the
lifting rings provided on the recloser. Mount the recloser on the pole or
structure using two 3⁄4" lag or thru bolts (customer supplied) as specified
on the product drawings shown on QBHFTand 19. With the SEL®
351R or 351R Falcon control, mount the power module onto the pole
below the recloser, as shown at right. With the SEL®651R control, no
power module is needed and the 32-pin cable should be plugged directly
into the recloser.
CAUTION:
Follow approved safety practices when lifting and mounting
the MVR. Use lifting rings on three-phase units and lift smoothly, limiting
shifting to avoid damage. Do not lift three-phase MVRs by the side
terminals as damage could result.
High-Voltage Terminations
The terminal connectors supplied with each recloser are aluminum
alloy with standard NEMA two-hole drilling and the bolts/nuts are silicon
bronze. The electrical connection at the terminal pad must be treated
with Alcoa No. 2 joint compound or equivalent. Each terminal should
be wire brushed through the compound to improve the connection.
If the terminal pad is rotated, the connector bolt(s) must be loosened
before turning the pad. Retighten the bolt(s) to 25 ft.-lbs. after
repositioning.
CAUTION:
Rotating the terminal connector without properly loosening
the connector will apply excessive force on the terminal stud and could
damage the interrupter assembly.
SEL is a registered trademark of Schweitzer Engineering Laboratories, Inc.
Single-Phase
Orientations
Torque to 25 ft.-lbs.
Loosen prior to
repositioning.
Three-Phase Mounting
High-Voltage Terminal Connectors
180˚
32 PIN CABLE
14 PIN CABLE
POWER MODULE USED
WITH 351R ONLY. WHEN
USING A 651R, THE 32 PIN
CABLE IS CONNECTED DIRECTLY
TO THE RECLOSER.
32-Pin Cable
14-Pin
Cable
Power module used
with 351R and 351R
Falcon only. When
using a 651R, the 32-
pin cable is connected
directly to the recloser.

9
Section 2: Instruction Manual and Drawings
*4t*4.73
Line Arrester
Load Arrester
Three-Phase Surge
Arrester Mounting
Surge Arrester Mounting
Each single-phase recloser mounting ring has a provision for mounting an optional
bracket on either side of the recloser to support two customer-supplied arresters
(one line-side and one load-side). Refer to the supplied recloser drawings for specific
installation dimensions. Alternate configurations are shown at right.
Three-phase reclosers have provisions for mounting an optional front bracket to
support three load-side, customer-provided surge arresters. A rear mounting bracket
for three additional line-side arresters is also available as an option as well as an
option to mount multiple transformers. Refer to the supplied recloser drawings for
specific installation dimensions. See example at right.
Since arresters are designed to provide lightning overvoltage protection, they
should be mounted as close as practical to the recloser if the standard arrester
brackets are not used.
Control Wiring
Control power must meet the requirements stated on the drawings supplied with the
recloser control. Please refer to the appropriate SEL®control manual. Each recloser and
control cabinet assembly comes with standard interconnection cables that are keyed at
each end to assure proper installation. Please see figures below for descriptions of the
receptacle pins.
A – CT AØ H – NOT USED R – VLINE CØ Y – CLOSE AØ f – CLOSE BØ
B – CT BØ J – VLOAD AØ S – VNEUTRAL Z – TRIP AØ g – TRIP BØ
C – CT CØ K – VLOAD BØ T – NOT USED a – NOT USED h – CLOSE CØ
D – CT NEUTRAL L – VLOAD CØ U – MONITORED TRIP AØ (52a) b – NOT USED j – TRIP CØ
E – NOT USED M – VNEUTRAL V – MONITORED TRIP BØ (52a) c – NOT USED
F – 12VDC N – VLINE AØ W – MONITORED TRIP CØ (52a) d – NOT USED
G – GND P – VLINE BØ X – MONITORED MANUAL TRIP (69) e – NOT USED
A – 24VDC F – MONITORED CLOSE PT L – NOT USED
B – MONITORED TRIP PT G – CT AØ M – GND
C – TRIP H – CT BØ N – CAP HEALTHY STATUS (OPTIONAL)
D – MONITORED TRIP PT J – CT CØ P – CAP HEALTHY STATUS (OPTIONAL)
E – CLOSE K – CT NEUTRAL
A – MONITORED TRIP (52a) F – NOT USED
B – MONITORED MANUAL TRIP (69) G – GND
C – CT H – 12VDC
D – CT NEUTRAL J – TRIP
E – NOT USED K – CLOSE
651Rx2
351R
351RS Kestrel
SEL is a registered trademark of Schweitzer Engineering Laboratories, Inc.
LINE ARRESTOR LINE ARRESTOR
LOAD ARRESTOR
Line Arrester Line Arrester
Load Arrester
Single-Phase Surge
Arrester Mounting
f
g
h
e
d
c
b
a
Z
j
Y
F
D
E
C
B
A
TS
R
P
N
M
L
K
J
H
G
X
W
V
U
N
F
E
D
C
M
L
B
A
K
J
P
H
G
B
A H
CJK
G
DE F

10
Section 2: Instruction Manual and Drawings
*4t*4.73
Instruction Manual
Grounding
To ensure the maximum amount of protection for internal
control components during possible power surge events,
the recloser and control cabinet need to be solidly grounded
together. The recloser ground conductor must be connected
to the supplied #10–2 AWG ground lug located on the
recloser’s frame base. All separate grounds should be
connected to the main ground wire. All connections to the
SEL®control (including the control cable, which contains a
ground) must be routed in close proximity to and parallel to
the main ground paths and should be approximately equal
in length. When using a power module with a 351R or 351R
Falcon, the power module box must also be grounded. See
Set-Up on QBHFfor a visual representation.
WARNING:
Hazardous voltage. Recloser and control must
be solidly grounded. Improper grounding can result in
contact with high voltage, which will cause severe personal
injury or death and equipment damage. Disconnecting the
control cable when the recloser is energized could result in
high voltage on the pins if the recloser tank is not grounded
as specified.
Voltage Sensor Set-Up
All Elastimold®MVRs come with pre-calibrated, load-
side capacitive voltage sensors that are capable of
measuring amplitude and phase angle with an accuracy
of approximately 3% under normal operating conditions
(-10˚ C to 45˚ C) and +/-5% at extreme conditions
(-40˚ C to 65˚ C).
For 3-phase MVRs, optional pre-calibrated line-side
resistive voltage sensors are also available and are
capable of measuring the voltage with a higher accuracy
of approximately 1%. All sensors require an 8VAC LEA
voltage sensor input on the SEL®651Rx2 control. Refer
to the Elastimold®Source Side Voltage Sensor (ESSVS)
Installation Instructions for mounting details. The ESSVS
are not used with the SEL®351R, 351R Falcon or 351RS
Kestrel Controls.
Electronic Operation Test
Using the controller, open and close the MVR electrically by
pressing the marked open and close buttons. Confirm that
the selected button is in agreement with the position indicator
on the control panel as well as the recloser position indicator.
The recloser position indicator is located on the bottom of the
recloser as shown below.
MVRs are designed to operate with a total circuit resistance
of 6.5–7.3 ohms across the TRIP/CLOSE pins on the SEL®
control interface.
SEL is a registered trademark of Schweitzer Engineering Laboratories, Inc.
CAUTION:
Do not energize the recloser for service until all
control settings have been properly programmed and verified.
Refer to the appropriate SEL®control manual for programming
procedures. Failure to comply may result in control and recloser
misoperation.
WARNING: Hazardous voltage. Do not rely on the contact
position indicator to determine that the line has been
de-energized. Always establish a visible disconnect and
establish grounds when performing de-energized line work.
Failure to follow proper safety practices can result in
contact with high voltage, which can cause death or
severe personal injury.
Individual Pole Position
Indicator (Side View)
Open Position
Closed Position
Open Position
Closed Position
Individual Pole Position
Indicator (Bottom View)

11
Section 2: Instruction Manual and Drawings
*4t*4.73
Vacuum Interrupter Tests
Every recloser is quality checked and tested before leaving the factory to assure
it meets all design specifications. In order to verify proper operating condition after
shipment and before installation, two tests should be performed to evaluate the
vacuum contacts. These tests should be performed across each module separately
and can be performed again, as desired, throughout the life of the recloser.
WARNING:
When testing at high voltage, the MVR and high-voltage test equipment
should be in a test cage or similar protective area to prevent accidental contact
with the high-voltage parts. All equipment needs to be solidly grounded. Failure
to comply can result in death, severe personal injury and equipment damage.
"$)JHI1PUFOUJBM5FTULoss of vacuum results in complete breakdown across open vacuum contacts at
voltages below 30kV RMS. Only AC high potential testing is meaningful. With the
recloser in the OPEN position, apply 30kV RMS across each individual contact for
15 seconds. To avoid possible generation of X-rays, do not apply more than 30kV RMS.
During the high potential testing, self-extinguishing, momentary breakdowns lasting only
a few seconds may occur. These breakdowns are not significant but can result in false
indication of vacuum loss if the test set uses a high-speed overload relay or breaker.
During normal operation with the recloser in service, loss of vacuum or a defective
module may be indicated by excessive AM radio noise with the recloser open or
by measuring a difference in surface temperatures (differential of more than 5º C
temperature rise above normal ambient) between poles on the same recloser.
When loss of vacuum occurs, contact resistance will typically increase.
$POUBDU3FTJTUBODF5FTUWith the recloser in the CLOSED position, measure the resistance across each module.
Resistance values should be less than 200 micro-ohms. If higher resistance values are
measured, contact your local Thomas & Betts representative.
SEL is a registered trademark of Schweitzer Engineering Laboratories, Inc.
Closed
Position
Open
Position
Line
Contact
Load Contact
Test
Equipment
Manual Trip Lever Test
With the switch closed, pull down the yellow trip lever as shown in center photo at right and
verify that the recloser opens. The position indicators located on the bottom of the recloser
will be GREEN for OPEN. The manual trip lever will remain in the down position until returned
to the up position. When in the down TRIPPED position, the manual trip will block all close
operations until it is manually restored to the up NORMAL position. When using the standard
SEL® 651Rx2, the control standard settings will also send a signal to open when the manual
trip handle is pulled. The recloser can be closed once the manual trip handle has been
restored to the normal position by pressing the close button on the control.
Manual Trip Lever –
Closed Position
Manual Trip Lever –
Open Position
Test Cable Set-Up Details

12
Section 2: Instruction Manual and Drawings
*4t*4.73
Operation
The recloser receives the
necessary signal to open and
close from the control circuitry.
For specific information
concerning the operation of
the control and how to change
settings, please refer the
appropriate SEL®control manual.
$5BOE7PMUBHF4FOTPSWhen
using standard SEL®settings files,
the CT ratio will already be preset
to 1000:1 and the voltage sensors
will come pre-calibrated (used
on the 651Rx2 only). If standard
settings files are not used, the
CT input in the SEL®control will
need to be adjusted to 1000:1. All
voltage sensors require an 8VAC
LEA input and are pre-calibrated
to a ratio of 10kV on the line to
1VAC into the SEL®control.
3FDMPTF4FRVFODFFor specific
information on how to adjust
settings and curves, please refer
to the appropriate SEL®control
manual. Note that certain SEL®
controls limit the number of
reclose sequences when AC
or battery is not present.
Please consult Schweitzer
Engineering Laboratories.
31PXFS.PEVMFFor
specifications, please refer to
the Power Module Box Installation
and Operation Instructions.
Maintenance
CAUTION:
The complete recloser system, including control, requires routine inspection
and maintenance if damage is found to ensure proper operation. If it is not maintained,
it may fail to operate properly. Improper operation may cause equipment damage and
possible personal injury.
The Elastimold®MVR is designed to be maintenance free under normal operating
conditions, and the EPDM/silicone insulation is not prone to the cracking or chipping
that sometimes occurs with porcelain or epoxy insulators. However, should damage
occur as a result of an external event, in most cases it is possible to replace the
damaged components due to the modular design of the recloser. Both the top and
bottom silicone shed, as well as the side terminal, can be removed and replaced if
damaged by external arcing, a knife cut, etc. If damage extends to the main body
of the pole, the pole in each phase can be replaced individually. If damage occurs,
please contact Thomas & Betts customer service. If it becomes necessary to clean
the main body or sheds, recommended cleaning agents are soap and warm water
or isopropyl alcohol.
SEL is a registered trademark of Schweitzer Engineering Laboratories, Inc.
Instruction Manual
TOP SHED
BOTTOM SHED
SIDE TERMINAL
Top Shed
Bottom Shed
Side Terminal
CAUTION:
A
ll MVRs are sealed and
leak tested prior to shipment to prevent
moisture ingress. Do not open the lower
cover as it is possible that the MVR will
not reseal when the cover is closed.
While the diaphragm will keep moisture
from ever entering the high-voltage
chamber, excessive moisture ingress
could cause damage to the magnetic
actuator mechanism and misoperation
.
CAUTION:
Do not remove and replace
the side terminal in the field. The MVR
incorporates a unique diaphragm
technology that fully encapsulates the
high-voltage chamber in the MVR. The
side terminal must be vented during
installation and then sealed to prevent
pressure build-up against the diaphragm
during the installation process. Improper
installation may cause equipment
damage and possible personal injury.
Standard Pole Replacement Details

13
Section 2: Instruction Manual and Drawings
*4t*4.73
Outline Drawings
Single-Phase 15/27kV
Drawing Number: 3188C0110
THIS INFORMATIONIS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDINGAND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENTYOU AGREE THAT ALL RIGHTSTO THE DRAWINGS AND INFORMATIONCONTAINE HEREON, AS WELL AS TOTHE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSEDHEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURESORINFORMATION DERIVED FROM THESE DRAWINGSWILL NOT BE MANUFACTURED BY OR FOR YOUOR DISCLOSED TO OTHERS WITHOUTTHE PRIOR EXPRESS WRITTEN
CONSENT OFTHOMAS AND BET TS.THESE DRAWINGS AND THE INFORMATION CONTAINEDTHEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TOBE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUTTHE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TOBE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
INCH
mm
INCH
mm
ENGLISH METRIC DUAL
8155 T&B Boulevard
Memphis, TN 38125
Phone: (800) 888-0211
Fax: (800) 888-0690
DRAWING NUMBER REV
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
MATERIAL
FINISH
DRAWING TITLE
SCALE DRAWING NUMBER
SHT. SIZE SHT. No.
NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
29.38
[746,2]
12.93
[328,5]
10.06
[255,6]
2.77
[70,3]
23.99
[609,3]
8.64
[219,4]
19.61
[498]
35.05
[890,2]
1.75
[44,5]
3188C0110
REV ECN- DESCRIPTION BY CHK. DATE
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
THIRD ANGLE PROJECTION
SDH 12/10/12
OUTLINE, RECLOSER 1-PH,
15-27KV
3/16 C 1 of 2
3188C0110
NOTES:
1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.
2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS.
[27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE
TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.
3) WEIGHT= 57 LBS. [25.8 KG.]
4) STANDARD POSITION AS SHOWN.
TRIP POSITION SHOWN DOTTED.
5) CONNECTION OF THE RECLOSER TO THE DESIGNATED
LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED
IF THE RECLOSER IS BEING USED WITH A CONTROL
CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.
6) CREEPAGE DISTANCE:
LINE TO GROUND = 41.50" [1054]
LOAD TO LINE = 52.00" [1321]
7) INTERRUPTER RATING = 12.5 KA
8) BIL: LINE TO GND = 150KV
LINE TO LINE = 150KV
LINE SIDE
(SEE NOTE 5)
OPEN/CLOSE INDICATOR
OPEN - GREEN BLACK CLOSED - RED BLACK
OPEN/CLOSE
INDICATOR
(SEE VIEW)
3/8-16 BOLT
FOR SECURING
RECLOSER TO
FRAME
MANUAL TRIP
HANDLE
SEE NOTE 4
LOAD SIDE
(SEE NOTE 5)
CABLE
CONNECTION
PROVISION
CLEARANCE SLOT FOR
USER SUPPLIED
5/8[16] DIA LAG OR
THRU BOLT
RECLOSER
x

14
Section 2: Instruction Manual and Drawings
*4t*4.73
Outline Drawings
Single-Phase 15/27kV
Drawing Number: 3188C0110
INCH
mm
INCH
mm
ENGLISH METRIC DUAL
8155 T&B Boulevard
Memphis, TN 38125
Phone: (800) 888-0211
Fax: (800) 888-0690
THIS INFORMATIONIS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDINGAND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENTYOU AGREE THAT ALL RIGHTSTO THE DRAWINGS AND INFORMATIONCONTAINE HEREON, AS WELL AS TOTHE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSEDHEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURESORINFORMATION DERIVED FROM THESE DRAWINGSWILL NOT BE MANUFACTURED BY OR FOR YOUOR DISCLOSED TO OTHERS WITHOUTTHE PRIOR EXPRESS WRITTEN
CONSENT OFTHOMAS AND BET TS.THESE DRAWINGS AND THE INFORMATION CONTAINEDTHEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TOBE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUTTHE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TOBE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBER REV
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
MATERIAL
FINISH
DRAWING TITLE
SCALE DRAWING NUMBER
SHT. SIZE SHT. No.
NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
13.75
[349,2]
2.88
[73]
6.09
[154,6]
3188C0110 0
REV ECN- DESCRIPTION BY CHK. DATE
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
THIRD ANGLE PROJECTION
SDH 12/10/12
OUTLINE, RECLOSER 1-PH,
15-27KV
3/16 C 2 of 2
3188C0110
LINE SIDE
ARRESTER
1/2-13 BOLT/NUT
FOR ARRESTER
ARRESTER
MOUNTING
FRAME
RECLOSER
ALTERNATE
ARRESTER
POSITION
1/4-20 BOLT
WASHER/NUT
1/2-13 BOLT/NUT
FOR ARRESTER
LOAD SIDE
ARRESTER
3/8-16 BOLT/WASHER
FOR MTG FRAME
x

15
Section 2: Instruction Manual and Drawings
*4t*4.73
Single-Phase 38kV
Drawing Number: 3188C0111
INCH
mm
INCH
mm
ENGLISH METRIC DUAL
8155 T&B Boulevard
Memphis, TN 38125
Phone: (800) 888-0211
Fax: (800) 888-0690
THIS INFORMATIONIS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDINGAND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENTYOU AGREE THAT ALL RIGHTSTO THE DRAWINGS AND INFORMATIONCONTAINE HEREON, AS WELL AS TOTHE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURESDISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURESORINFORMATION DERIVED FROM THESE DRAWINGSWILL NOT BE MANUFACTURED BY OR FOR YOUOR DISCLOSED TO OTHERS WITHOUTTHE PRIOR EXPRESS WRITTEN
CONSENT OFTHOMAS AND BET TS.THESE DRAWINGS AND THE INFORMATION CONTAINEDTHEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TOBE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUTTHE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TOBE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBER REV
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
MATERIAL
FINISH
DRAWING TITLE
SCALE DRAWING NUMBER
SHT. SIZE SHT. No.
NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
31.18
[791,9]
12.93
[328,5]
10.06
[255,6]
2.77
[70,3]
23.99
[609,3]
8.64
[219,4]
19.61
[498]
35.05
[890,2]
1.75
[44,5]
3188C0111 0
REV ECN- DESCRIPTION BY CHK. DATE
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
THIRD ANGLE PROJECTION
SDH 01/03/12
OUTLINE, RECLOSER 1-PH,
38KV
3/16 C 1 of 2
3188C0111
LINE SIDE
(SEE NOTE 5)
OPEN/CLOSE INDICATOR
NOTES:
1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.
2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS.
[27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE
TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.
3) WEIGHT= 58 LBS. [26.3 KG.]
4) STANDARD POSITION AS SHOWN.
TRIP POSITION SHOWN DOTTED.
5) CONNECTION OF THE RECLOSER TO THE DESIGNATED
LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED
IF THE RECLOSER IS BEING USED WITH A CONTROL
CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.
6) CREEPAGE DISTANCE:
LINE TO GROUND = 51.00" [1295]
LOAD TO LINE = 60.00" [1524]
7) INTERRUPTER RATING = 12.5 KA
8) BIL: LINE TO GND = 170KV
LINE TO LINE = 170KV
OPEN - GREEN BLACK CLOSED - RED BLACK
OPEN/CLOSE
INDICATOR
(SEE VIEW)
3/8-16 BOLT
FOR SECURING
RECLOSER TO
FRAME
MANUAL TRIP
HANDLE
SEE NOTE 4
LOAD SIDE
(SEE NOTE 5)
CABLE
CONNECTION
PROVISION
CLEARANCE SLOT FOR
USER SUPPLIED
5/8[16] DIA LAG OR
THRU BOLT
RECLOSER
x

16
Section 2: Instruction Manual and Drawings
*4t*4.73
Outline Drawings
Single-Phase 38kV
Drawing Number: 3188C0111
INCH
mm
INCH
mm
ENGLISH METRIC DUAL
8155 T&B Boulevard
Memphis, TN 38125
Phone: (800) 888-0211
Fax: (800) 888-0690
THIS INFORMATIONIS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDINGAND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENTYOU AGREE THAT ALL RIGHTSTO THE DRAWINGS AND INFORMATIONCONTAINE HEREON, AS WELL AS TOTHE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURESDISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURESORINFORMATION DERIVED FROM THESE DRAWINGSWILL NOT BE MANUFACTURED BY OR FOR YOUOR DISCLOSED TO OTHERS WITHOUTTHE PRIOR EXPRESS WRITTEN
CONSENT OFTHOMAS AND BET TS.THESE DRAWINGS AND THE INFORMATION CONTAINEDTHEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TOBE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUTTHE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TOBE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBER REV
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
MATERIAL
FINISH
DRAWING TITLE
SCALE DRAWING NUMBER
SHT. SIZE SHT. No.
NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
13.75
[349,2]
2.88
[73]
6.09
[154,6]
3188C0111 0
REV ECN- DESCRIPTION BY CHK. DATE
03/29/12
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
THIRD ANGLE PROJECTION
SDH 01/03/12
OUTLINE, RECLOSER 1-PH,
38KV
3/16 C 2 of 2
3188C0111
LINE SIDE
ARRESTER
1/2-13 BOLT/NUT
FOR ARRESTER
ARRESTER
MOUNTING FRAME
RECLOSER
1/4-20 BOLT
WASHER/NUT
ALTERNATE
ARRESTER
POSITION
3/8-16
BOLT/WASHER
FOR MTG FRAME
1/2-13 BOLT/NUT
FOR ARRESTER
LOAD SIDE
ARRESTER
x

17
Section 2: Instruction Manual and Drawings
*4t*4.73
Three-Phase 15/27kV
Drawing Number: 3188C0112
INCH
mm
INCH
mm
ENGLISH METRIC DUAL
8155 T&B Boulevard
Memphis, TN 38125
Phone: (800) 888-0211
Fax: (800) 888-0690
THIS INFORMATIONIS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDINGAND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENTYOU AGREE THAT ALL RIGHTSTO THE DRAWINGS AND INFORMATIONCONTAINE HEREON, AS WELL AS TOTHE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURESDISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURESORINFORMATION DERIVED FROM THESE DRAWINGSWILL NOT BE MANUFACTURED BY OR FOR YOUOR DISCLOSED TO OTHERS WITHOUTTHE PRIOR EXPRESS WRITTEN
CONSENT OFTHOMAS AND BET TS.THESE DRAWINGS AND THE INFORMATION CONTAINEDTHEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TOBE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUTTHE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TOBE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBER REV
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
MATERIAL
FINISH
DRAWING TITLE
SCALE DRAWING NUMBER
SHT. SIZE SHT. No.
NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
1.50
[38,1]
15.01
[381,3]
1.75
[44,5]
35.13
[892,2]
1.75
[44,5]
15.50
[393,7]
15.50
[393,7]
24.25
[616,1]
12.95
[328,9]
33.76
[857,6]
16.44
[417,6]
42.56
[1081]
19.56
[496,8]
3188C0112 2
REV ECN- DESCRIPTION BY CHK. DATE
1 G16309 UPDATE SHT 2 ADD SHT 3 SDH
9/21/12
2 UPDATED FRONT ARRESTER, SH2 SDH
11/30/12
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
THIRD ANGLE PROJECTION
sdh 11/28/11
OUTLINE, RECLOSER 3-PH,
15-27KV
1/8 C 1 of 3
3188C0112
NAMEPLATE
NOTES:
1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.
2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS.
[27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE
TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.
3) WEIGHT= 208 LBS. [94.4 KG.]
4) STANDARD POSITION AS SHOWN.
TRIP POSITION SHOWN DOTTED.
5) CONNECTION OF THE RECLOSER TO THE DESIGNATED
LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED
IF THE RECLOSER IS BEING USED WITH A CONTROL
CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.
6) CREEPAGE DISTANCE:
LINE TO GROUND = 41.50" [1054]
LOAD TO GROUND = 43.60" [1107]
LINE TO LOAD = 52.17" [1320]
7) INTERRUPTER RATING = 12.5 KA
8) BIL: LINE TO GND = 150KV
LINE TO LINE = 150KV
MVR3 RECLOSER
PENDING ECN
11-30-12A
PLEASE CONTACT
ENGINEERING FOR
CURRENT REVISION
OPEN/CLOSE
INDICATOR
(SEE VIEW)
LOAD SIDE
(SEE NOTE 5)
LINE SIDE
(SEE NOTE 5)
TORQUE TERMINAL
LUGS TO 25 FT/LBS
MANUAL TRIP
HANDLE
SEE NOTE 4
LIFT SWITCH
HERE
CABLE CONNECTION
PROVISION
CLEARANCE SLOTS FOR
USER SUPPLIED
3/4 [19] DIA LAG OR
THRU BOLTS
OPEN - GREEN
OPEN/CLOSE INDICATOR
SCALE 1/4
BLACK CLOSED - RED BLACK

18
Section 2: Instruction Manual and Drawings
*4t*4.73
Outline Drawings
Three-Phase 15/27kV
Drawing Number: 3188C0112
INCH
mm
INCH
mm
ENGLISH METRIC DUAL
8155 T&B Boulevard
Memphis, TN 38125
Phone: (800) 888-0211
Fax: (800) 888-0690
THIS INFORMATIONIS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDINGAND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENTYOU AGREE THAT ALL RIGHTSTO THE DRAWINGS AND INFORMATIONCONTAINE HEREON, AS WELL AS TOTHE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURESDISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURESORINFORMATION DERIVED FROM THESE DRAWINGSWILL NOT BE MANUFACTURED BY OR FOR YOUOR DISCLOSED TO OTHERS WITHOUTTHE PRIOR EXPRESS WRITTEN
CONSENT OFTHOMAS AND BET TS.THESE DRAWINGS AND THE INFORMATION CONTAINEDTHEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TOBE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUTTHE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TOBE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBER REV
3188C0112 2
MVR3 RECLOSER WITH
LINE SIDE AND LOAD SIDE ARRESTER FRAMES
PENDING ECN
11-30-12A
PLEASE CONTACT
ENGINEERING FOR
CURRENT REVISION
5/8-11 BOLT/NUT
FOR TRANSFORMER
MOUNTING FRAME
FOR LINE ARRESTERS
AND TRANSFORMERS
5/8-11 BOLT/NUT
FOR MTG FRAME
9.75
[247,7]
38.74
[984]
19.37
[492]
24.60
[624,71]
8.93
[226,9]
18.93
[480,9]
TRANSFORMER
LINE SIDE
ARRESTER
LINE SIDE
ARRESTERS
1/2-13 BOLT/NUT
FOR LINE SIDE
ARRESTORS
ALTERNATE
TRANSFORMER
POSITION
ALTERNATE
ARRESTER
POSITION
ALTERNATE
TRANSFORMER
POSITION
RECLOSER
LOAD SIDE
ARRESTER
FRAME
LOAD SIDE
ARRESTERS
1/2-13 BOLT/NUT
FOR LOAD SIDE
ARRESTERS
3/8-16 BOLT/WASHER
FOR LOAD SIDE
ARRESTER FRAME
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
MATERIAL
FINISH
DRAWING TITLE
SCALE DRAWING NUMBER
SHT. SIZE SHT. No.
NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
THIRD ANGLE PROJECTION
SDH 12/27/11
OUTLINE, RECLOSER 3-PH,
15-27KV
1/8 D 2 of 3
3188C0112
REV ECN- DESCRIPTION BY CHK. DATE
1 G16309 UPDATE SHT 2 ADD SHT 3 SDH
9/21/12
2 UPDATED FRONT ARRESTER, SH2 SDH
11/30/12
x

19
Section 2: Instruction Manual and Drawings
*4t*4.73
Three-Phase 38kV
Drawing Number: 3188C0113
INCH
mm
INCH
mm
ENGLISH METRIC DUAL
8155 T&B Boulevard
Memphis, TN 38125
Phone: (800) 888-0211
Fax: (800) 888-0690
THIS INFORMATIONIS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDINGAND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENTYOU AGREE THAT ALL RIGHTSTO THE DRAWINGS AND INFORMATIONCONTAINE HEREON, AS WELL AS TOTHE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURESDISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURESORINFORMATION DERIVED FROM THESE DRAWINGSWILL NOT BE MANUFACTURED BY OR FOR YOUOR DISCLOSED TO OTHERS WITHOUTTHE PRIOR EXPRESS WRITTEN
CONSENT OFTHOMAS AND BET TS.THESE DRAWINGS AND THE INFORMATION CONTAINEDTHEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TOBE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUTTHE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TOBE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBER REV
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
MATERIAL
FINISH
DRAWING TITLE
SCALE DRAWING NUMBER
SHT. SIZE SHT. No.
NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
1.50
[38,1]
15.01
[381,3]
1.75
[44,5]
35.13
[892,2]
1.75
[44,5]
15.50
[393,7]
15.50
[393,7]
24.25
[616,1]
12.95
[328,9]
35.57
[903,5]
18.25
[463,6]
42.56
[1081]
19.56
[496,8]
3188C0113 2
REV ECN- DESCRIPTION BY CHK. DATE
1 G16348 UPDATE SHT 2 ADD SHT 3 SDH
9/21/12
2
UPDATE ARRESTER FRAME. SH2
SDH
11/30/12
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
THIRD ANGLE PROJECTION
sdh 11/28/11
OUTLINE, RECLOSER 3-PH,
38KV
1/8 C 1 of 3
3188C0113
NAMEPLATE
NOTES:
1) DIMENSIONS IN BRACKETS [XXX] ARE MILLIMETERS.
2) MAXIMUM CANTILEVERED TERMINAL PAD LOAD OF 60 LBS.
[27 KG.] PER PAD ALLOWABLE. HORIZONTAL CABLE
TENSIONS PER PHASE TO BE OPPOSITE IN DIRECTION.
3) WEIGHT= 211 LBS. [95.7 KG.]
4) STANDARD POSITION AS SHOWN.
TRIP POSITION SHOWN DOTTED.
5) CONNECTION OF THE RECLOSER TO THE DESIGNATED
LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED
IF THE RECLOSER IS BEING USED WITH A CONTROL
CONTAINING DIRECTIONAL OVER CURRENT CAPABILITY.
6) CREEPAGE DISTANCE:
LINE TO GROUND = 51.00" [1295]
LOAD TO GROUND = 52.00" [1320]
LINE TO LOAD = 60.56" [1538]
7) INTERRUPTER RATING = 12.5 KA
8) BIL: LINE TO GND = 170KV
LINE TO LINE = 170KV
MVR3 RECLOSER
PENDING ECN
09-20-12D
PLEASE CONTACT
ENGINEERING FOR
CURRENT REVISION
OPEN/CLOSE
INDICATOR
(SEE VIEW)
LOAD SIDE
(SEE NOTE 5)
LINE SIDE
(SEE NOTE 5)
TORQUE TERMINAL
LUGS TO 25 FT/LBS
MANUAL TRIP
HANDLE
SEE NOTE 4
LIFT SWITCH
HERE
CABLE CONNECTION
PROVISION
CLEARANCE SLOTS FOR
USER SUPPLIED
3/4 [19] DIA LAG OR
THRU BOLTS
OPEN - GREEN
OPEN/CLOSE INDICATOR
SCALE 1/4
BLACK CLOSED - RED BLACK

20
Section 2: Instruction Manual and Drawings
*4t*4.73
Outline Drawings
Three-Phase 38kV
Drawing Number: 3188C0113
INCH
mm
INCH
mm
ENGLISH METRIC DUAL
8155 T&B Boulevard
Memphis, TN 38125
Phone: (800) 888-0211
Fax: (800) 888-0690
THIS INFORMATIONIS TRANSMITTED SUBJECT TO THE FOLLOWING UNDERSTANDINGAND AGREEMENT BY ACCEPTANCE OF THIS DOCUMENTYOU AGREE THAT ALL RIGHTSTO THE DRAWINGS AND INFORMATIONCONTAINE HEREON, AS WELL AS TOTHE SUBJECT MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURESDISCLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVICES EMBODYING SUCH FEATURESORINFORMATION DERIVED FROM THESE DRAWINGSWILL NOT BE MANUFACTURED BY OR FOR YOUOR DISCLOSED TO OTHERS WITHOUTTHE PRIOR EXPRESS WRITTEN
CONSENT OFTHOMAS AND BET TS.THESE DRAWINGS AND THE INFORMATION CONTAINEDTHEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TOBE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUTTHE PRIOR WRITTEN CONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TOBE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH LENT.
THOMAS & BETTS, PROPRIETARY RIGHTS
DRAWING NUMBER REV
3188C0113 2
MVR3 RECLOSER WITH
LINE SIDE AND LOAD SIDE ARRESTER FRAMES
PENDING ECN
11-30-12A
PLEASE CONTACT
ENGINEERING FOR
CURRENT REVISION
9.75
[247,7]
38.74
[984]
19.37
[492]
24.60
[624,71]
8.93
[226,9]
18.93
[480,9]
TRANSFORMER
LINE SIDE
ARRESTER
LINE SIDE
ARRESTERS
1/2-13 BOLT/NUT
FOR LINE SIDE
ARRESTORS
ALTERNATE
TRANSFORMER
POSITION
ALTERNATE
ARRESTER
POSITION
ALTERNATE
TRANSFORMER
POSITION
RECLOSER
LOAD SIDE
ARRESTER
FRAME
LOAD SIDE
ARRESTERS
1/2-13 BOLT/NUT
FOR LOAD SIDE
ARRESTERS
3/8-16 BOLT/WASHER
FOR LOAD SIDE
ARRESTER FRAME
5/8-11 BOLT/NUT
FOR TRANSFORMER
MOUNTING FRAME
FOR LINE ARRESTERS
AND TRANSFORMERS
5/8-11 BOLT/NUT
FOR MTG FRAME
3/8-16 BOLT/WASHER
FOR LOAD SIDE
ARRESTER FRAME
APPROVED
CHECKED
DRAWN DATE
DATE
DATE
MATERIAL
FINISH
DRAWING TITLE
SCALE DRAWING NUMBER
SHT. SIZE SHT. No.
NEXT ASS'Y
ENGINEERING SPEC. QUALITY STD. MATERIAL STD.
ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS CHECKED BELOW
THIRD ANGLE PROJECTION
SDH 12/27/11
OUTLINE, RECLOSER 3-PH,
38KV
1/8 D 2 of 3
3188C0113
REV ECN- DESCRIPTION BY CHK. DATE
1 G16348 UPDATE SHT 2 ADD SHT 3 SDH
9/21/12
2UPDATE ARRESTER FRAME, SH 2 SDH
11/30/12
x
Table of contents
Other Thomas&Betts Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Belimo
Belimo FSAF24-SR US quick start guide

GREEN INSTRUMENTS
GREEN INSTRUMENTS G3610 instruction manual

BrakeBuddy
BrakeBuddy SELECT 3 39524 instruction manual

Pfeiffer Vacuum
Pfeiffer Vacuum HIPACE operating instructions

Schaeffler
Schaeffler RT Series Mounting manual

Datcon
Datcon DT1102 (PS) operating instructions

SICK
SICK KTS-WB81141142ZZZZ quick start guide

Festo
Festo EGC Series operating instructions

Minebea Intec
Minebea Intec PR 6207 installation manual

IFM Electronic
IFM Electronic ASinterface AS-i AirBox 32 AC042A installation instructions

HBM
HBM T10FS Mounting instructions

iplex
iplex EZIPIT technical information