4400 Series UPS Seismic Kit Installation Instructions – 94016-001
2. 4400 50kVA Seismic Installation
Table 2 lists the contents of the 4400 50kVA (4400500SEISMICKIT) and 80kVA (4400800SEISMICKIT)
Seismic Kits. Figure 1 shows the order of assembly for the [bolt + lockwasher + washer] fastener group.
TABLE 2 50 KVA SEISMIC KIT CONTENTS
440500SEISMICKIT Contents
No. P/N* Description Quan
5 66437 TOP SEISMIC BRACKET 1
667193 SEISMIC MOUNTING CHANNEL 2
7-a –Hex Bolt, 1/4—20,1-1/2” 1
7-b –Flat Washer, 1/4 1
7-c –E—Ring, F/0.25 Shaft 1
10-a –Hex Bolt, 1/2—13 x 3/4” 8
10-b –Lock Washer, 1/2 8
10-c –Flat Washer, 1/2 8
11-a –Hex Bolt, 5/16—18 x 1” 4
11-b –Lock Washer, 5/16 4
11-c –Flat Washer, 5/16 4
–94016 4400 Seismic Kit Installation Manual 1
1. Prepare the oor anchorages. Arrange the anchorages to ac-
commodate the nal layout including placement for ancillary
battery and/or Auxiliary cabinets. (Figure 11)
2. Prepare the wall anchorages. Key measurements off the an-
chorage placement in Step 1. (Figure 12)
3. Table 2 lists the components of the 50kVA Seismic Kit. Figure 10
show the Seismic anchorage components in the Seismic Kit for
the 50kVA cabinets.
4. Assemble the fastener groups in Table 2, [7a-7c], [10a-10c], and
[11a-11c] as shown in Figure 1.
5. Secure the Top Seismic Bracket [5] to the top rear of the UPS
using three (3) fastener group [11]. (Figure 13)
6. Position the UPS over the oor anchors
7. Slip each Seismic Mounting Channel [6] over the three oor
anchors on each side of the UPS.
8. Tilt the Base bracket up against the UPS bottom bracket on the
UPS base.
9. Align the holes in the Seismic Mounting Channels [6] with the
UPS bottom brackets.
10. Use the remaining eight (8) fastener group [11] to secure the
Seismic Mounting Channels [6] to the UPS bottom brackets.
(Figure 14, Figure 15)
11. Secure the Top Seismic Bracket to the wall anchors using 5/16” Bolts.
12. Once installation is complete, secure the door of the UPS using the two
(2) Fastener Group [7]. (Figure 16)
a
b
c
FIGURE 1: FASTENER
GROUP (BOLT +LOCK
WASHER + WASHER)
P/N 440500SEISMICKIT
5
6
7
5
FIGURE 10: SEISMIC KIT
COMPONENTS (50 KVA)