Trane Technologies CenTraVac CVHE Installation and operating instructions

X39641427002
SSAAFFEETTYY WWAARRNNIINNGG
Only qualified personnel should install and service the equipment The installation, starting up, and servicing of heating, ventilating, and air-conditioning
equipment can be hazardous and requires specific knowledge and training Improperly installed, adjusted or altered equipment by an unqualified person
could result in death or serious injury When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that
are attached to the equipment
March 2022 CCVVHHEE--SSVVXX000055BB--EENN
Installation, Operation, and Maintenance
CenTraVac™™ Water-cooled Chillers
Models CVHE, CVHF, and CVH
With Symbio™ Controls
MMooddeell:: CVHE
MMooddeell:: CVHF
MMooddeell:: CVHG

©2022 Trane CVHE-SVX005B-EN
Introduction
Read this manual thoroughly before operating or
servicing this unit
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required Your personal safety and the proper
operation of this machine depend upon the strict
observance of these precautions
The three types of advisories are defined as follows:
WARNING
Indicates a potentially hazardous situation
which, if not avoided, could result in death or
serious injury.
CAU
TION
Indicates a potentially hazardous situation
which, if not avoided, could result in minor or
moderate injury. It could also be used to alert
against unsafe practices.
NOTICE
Indicates a situation that could result in
equipment or property-damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere In particular, several of the identified
chemicals that may affect the ozone layer are
refrigerants that contain Chlorine, Fluorine and Carbon
(CFCs) and those containing Hydrogen, Chlorine,
Fluorine and Carbon (HCFCs) Not all refrigerants
containing these compounds have the same potential
impact to the environment Trane advocates the
responsible handling of all refrigerants-including
industry replacements for CFCs and HCFCs such as
saturated or unsaturated HFCs and HCFCs
Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices
are important to the environment, our customers, and
the air conditioning industry All technicians who
handle refrigerants must be certified according to local
rules For the USA, the Federal Clean Air Act (Section
608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management
of refrigerants Know the applicable laws and follow
them
WWAARRNNIINNGG
PPrrooppeerr FFiieelldd WWiirriinngg aanndd GGrroouunnddiinngg
RReeqquuiirreedd!!
FFaaiilluurree ttoo ffoollllooww ccooddee ccoouulldd rreessuulltt iinn ddeeaatthh oorr
sseerriioouuss iinnjjuurryy
AAllll ffiieelldd wwiirriinngg MMUUSSTT bbee ppeerrffoorrmmeedd bbyy qquuaalliiffiieedd
ppeerrssoonnnneell IImmpprrooppeerrllyy iinnssttaalllleedd aanndd ggrroouunnddeedd
ffiieelldd wwiirriinngg ppoosseess FFIIRREE aanndd EELLEECCTTRROOCCUUTTIIOONN
hhaazzaarrddss TToo aavvooiidd tthheessee hhaazzaarrddss,, yyoouu MMUUSSTT ffoollllooww
rreeqquuiirreemmeennttss ffoorr ffiieelldd wwiirriinngg iinnssttaallllaattiioonn aanndd
ggrroouunnddiinngg aass ddeessccrriibbeedd iinn NNEECC aanndd yyoouurr llooccaall//
ssttaattee//nnaattiioonnaall eelleeccttrriiccaall ccooddeess
WWAARRNNIINNGG
PPeerrssoonnaall PPrrootteeccttiivvee EEqquuiippmmeenntt ((PPPPEE))
RReeqquuiirreedd!!
FFaaiilluurree ttoo wweeaarr pprrooppeerr PPPPEE ffoorr tthhee jjoobb bbeeiinngg
uunnddeerrttaakkeenn ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy
TTeecchhnniicciiaannss,, iinn oorrddeerr ttoo pprrootteecctt tthheemmsseellvveess ffrroomm
ppootteennttiiaall eelleeccttrriiccaall,, mmeecchhaanniiccaall,, aanndd cchheemmiiccaall
hhaazzaarrddss,, MMUUSSTT ffoollllooww pprreeccaauuttiioonnss iinn tthhiiss mmaannuuaall
aanndd oonn tthhee ttaaggss,, ssttiicckkeerrss,, aanndd llaabbeellss,, aass wweellll aass tthhee
iinnssttrruuccttiioonnss bbeellooww::
•• BBeeffoorree iinnssttaalllliinngg//sseerrvviicciinngg tthhiiss uunniitt,,
tteecchhnniicciiaannss MMUUSSTT ppuutt oonn aallll PPPPEE rreeqquuiirreedd ffoorr
tthhee wwoorrkk bbeeiinngg uunnddeerrttaakkeenn ((EExxaammpplleess;; ccuutt
rreessiissttaanntt gglloovveess//sslleeeevveess,, bbuuttyyll gglloovveess,, ssaaffeettyy
ggllaasssseess,, hhaarrdd hhaatt//bbuummpp ccaapp,, ffaallll pprrootteeccttiioonn,,
eelleeccttrriiccaall PPPPEE aanndd aarrcc ffllaasshh ccllootthhiinngg))
AALLWWAAYYSS rreeffeerr ttoo aapppprroopprriiaattee SSaaffeettyy DDaattaa
SShheeeettss ((SSDDSS)) aanndd OOSSHHAA gguuiiddeelliinneess ffoorr
pprrooppeerr PPPPEE
•• WWhheenn wwoorrkkiinngg wwiitthh oorr aarroouunndd hhaazzaarrddoouuss
cchheemmiiccaallss,, AALLWWAAYYSS rreeffeerr ttoo tthhee aapppprroopprriiaattee
SSDDSS aanndd OOSSHHAA//GGHHSS ((GGlloobbaall HHaarrmmoonniizzeedd
SSyysstteemm ooff CCllaassssiiffiiccaattiioonn aanndd LLaabbeelllliinngg ooff
CChheemmiiccaallss)) gguuiiddeelliinneess ffoorr iinnffoorrmmaattiioonn oonn
aalllloowwaabbllee ppeerrssoonnaall eexxppoossuurree lleevveellss,, pprrooppeerr
rreessppiirraattoorryy pprrootteeccttiioonn aanndd hhaannddlliinngg
iinnssttrruuccttiioonnss
•• IIff tthheerree iiss aa rriisskk ooff eenneerrggiizzeedd eelleeccttrriiccaall
ccoonnttaacctt,, aarrcc,, oorr ffllaasshh,, tteecchhnniicciiaannss MMUUSSTT ppuutt
oonn aallll PPPPEE iinn aaccccoorrddaannccee wwiitthh OOSSHHAA,, NNFFPPAA
7700EE,, oorr ootthheerr ccoouunnttrryy--ssppeecciiffiicc rreeqquuiirreemmeennttss
ffoorr aarrcc ffllaasshh pprrootteeccttiioonn,, PPRRIIOORR ttoo sseerrvviicciinngg
tthhee uunniitt NNEEVVEERR PPEERRFFOORRMM AANNYY SSWWIITTCCHHIINNGG,,
DDIISSCCOONNNNEECCTTIINNGG,, OORR VVOOLLTTAAGGEE TTEESSTTIINNGG
WWIITTHHOOUUTT PPRROOPPEERR EELLEECCTTRRIICCAALL PPPPEE AANNDD
AARRCC FFLLAASSHH CCLLOOTTHHIINNGG EENNSSUURREE
EELLEECCTTRRIICCAALL MMEETTEERRSS AANNDD EEQQUUIIPPMMEENNTT AARREE
PPRROOPPEERRLLYY RRAATTEEDD FFOORR IINNTTEENNDDEEDD
VVOOLLTTAAGGEE

CVHE-SVX005B-EN 3
WWAARRNNIINNGG
FFoollllooww EEHHSS PPoolliicciieess!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn
ddeeaatthh oorr sseerriioouuss iinnjjuurryy
•• AAllll TTrraannee ppeerrssoonnnneell mmuusstt ffoollllooww tthhee
ccoommppaannyy’’ss EEnnvviirroonnmmeennttaall,, HHeeaalltthh aanndd SSaaffeettyy
((EEHHSS)) ppoolliicciieess wwhheenn ppeerrffoorrmmiinngg wwoorrkk ssuucchh aass
hhoott wwoorrkk,, eelleeccttrriiccaall,, ffaallll pprrootteeccttiioonn,, lloocckkoouutt//
ttaaggoouutt,, rreeffrriiggeerraanntt hhaannddlliinngg,, eettcc WWhheerree llooccaall
rreegguullaattiioonnss aarree mmoorree ssttrriinnggeenntt tthhaann tthheessee
ppoolliicciieess,, tthhoossee rreegguullaattiioonnss ssuuppeerrsseeddee tthheessee
ppoolliicciieess
•• NNoonn--TTrraannee ppeerrssoonnnneell sshhoouulldd aallwwaayyss ffoollllooww
llooccaall rreegguullaattiioonnss
WWAARRNNIINNGG
RReeffrriiggeerraanntt MMaayy BBee UUnnddeerr PPoossiittiivvee
PPrreessssuurree!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn
aann eexxpplloossiioonn wwhhiicchh ccoouulldd rreessuulltt iinn ddeeaatthh oorr
sseerriioouuss iinnjjuurryy oorr eeqquuiippmmeenntt ddaammaaggee
SSyysstteemm ccoonnttaaiinnss rreeffrriiggeerraanntt aanndd mmaayy bbee uunnddeerr
ppoossiittiivvee pprreessssuurree;; ssyysstteemm mmaayy aallssoo ccoonnttaaiinn ooiill
RReeccoovveerr rreeffrriiggeerraanntt ttoo rreelliieevvee pprreessssuurree bbeeffoorree
ooppeenniinngg tthhee ssyysstteemm SSeeee uunniitt nnaammeeppllaattee ffoorr
rreeffrriiggeerraanntt ttyyppee DDoo nnoott uussee nnoonn--aapppprroovveedd
rreeffrriiggeerraannttss,, rreeffrriiggeerraanntt ssuubbssttiittuutteess,, oorr nnoonn--
aapppprroovveedd rreeffrriiggeerraanntt aaddddiittiivveess
NNOOTTIICCEE
EEqquuiippmmeenntt DDaammaaggee!!
MMiixxiinngg rreeffrriiggeerraannttss oorr ooiillss ccoouulldd rreessuulltt iinn
eeqquuiippmmeenntt ddaammaaggee iinncclluuddiinngg bbeeaarriinngg ddaammaaggee,,
iinnttrroodduuccttiioonn ooff aacciiddss iinnttoo tthhee cchhiilllleerr,, oorr ccoonnttiinnuuoouuss
ppuurrggee ppuummpp--oouutt iinn hhiigghh--hheeaadd//hhiigghh aammbbiieenntt
aapppplliiccaattiioonnss
CCeennTTrraaVVaacc™™ cchhiilllleerrss aarree mmaannuuffaaccttuurreedd wwiitthh
ddiiffffeerreenntt rreeffrriiggeerraanntt//ooiill ssyysstteemmss:: 11)) cchhiilllleerrss uussiinngg
RR--112233 rreeffrriiggeerraanntt aanndd OOIILL0000002222 ccoommpprreessssoorr ooiill,,
aanndd 22)) cchhiilllleerrss uussiinngg RR--551144AA rreeffrriiggeerraanntt aanndd
vvaarriioouuss TTrraannee PPOOEE--bbaasseedd ccoommpprreessssoorr ooiillss
AAllwwaayyss vveerriiffyy pprrooppeerr rreeffrriiggeerraanntt aanndd ooiill ffoorr yyoouurr
cchhiilllleerr DDoo NNOOTT mmiixx rreeffrriiggeerraannttss aanndd ooiillss
This Installation, Operation, and Maintenance manual
applies to CenTraVac™chillers with two different
refrigerant and compressor oil systems:
• R-123 refrigerant and OIL00022 compressor oil
• R-514A refrigerant and Trane OIL00379/OIL00380
compressor oil
NNOOTTIICCEE
EEqquuiippmmeenntt DDaammaaggee!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn
eeqquuiippmmeenntt ddaammaaggee
FFoollllooww ooiill uussee iinnssttrruuccttiioonnss ffoorr ppoosstt--sseerrvviiccee
ccoommpprreessssoorr aaiirr--rruunn pprroocceedduurreess
For post-service compressor air-run procedures on
CenTraVac™ chillers that use R-514A refrigerant and
POE oil:
1 Use Trane OIL00381/OIL00382 compressor oil for
the air-run procedure
2 Upon completion of the air-run procedure, drain the
OIL00381/OIL00382 from the sump
3 After unit final assembly and evacuation, refill the
sump with Trane OIL00379/OIL00380
IImmppoorrttaanntt:: Verify proper refrigerant and compressor
oil for your chiller before proceeding!
NNOOTTIICCEE
DDoo NNoott UUssee NNoonn--CCoommppaattiibbllee PPaarrttss oorr
MMaatteerriiaallss!!
UUssee ooff nnoonn--ccoommppaattiibbllee ppaarrttss oorr mmaatteerriiaallss ccoouulldd
rreessuulltt iinn eeqquuiippmmeenntt ddaammaaggee
OOnnllyy ggeennuuiinnee TTrraannee®® rreeppllaacceemmeenntt ccoommppoonneennttss
wwiitthh iiddeennttiiccaall TTrraannee ppaarrtt nnuummbbeerrss sshhoouulldd bbee uusseedd
iinn TTrraannee CCeennTTrraaVVaacc cchhiilllleerrss TTrraannee aassssuummeess nnoo
rreessppoonnssiibbiilliittyy ffoorr ddaammaaggeess rreessuullttiinngg ffrroomm tthhee uussee
ooff nnoonn--ccoommppaattiibbllee ppaarrttss oorr mmaatteerriiaallss
Factory Warranty Information
Compliance with the following is required to preserve
the factory warranty:
AAllll nniitt IInnssttaallllaattiioonnss
Startup MUST be performed by Trane, or an authorized
agent of Trane, to VALIDATE this WARRANTY
Contractor must provide a two-week startup
notification to Trane (or an agent of Trane specifically
authorized to perform startup)
AAddddiittiioonnaall RReeqquuiirreemmeennttss ffoorr nniittss RReeqquuiirriinngg
DDiissaasssseemmbbllyy aanndd RReeaasssseemmbbllyy
When a new chiller is shipped and received from our
Trane manufacturing location and, for any reason, it
requires disassembly or partial disassembly, and
reassembly— which could include but is not limited to
the evaporator, condenser, control panel, compressor/
motor, economizer, purge, factory-mounted starter or
any other components originally attached to the fully
assembled unit— compliance with the following is
required to preserve the factory warranty:
• Trane, or an agent of Trane specifically authorized
to perform start-up and warranty of Trane®
products, will perform or have direct on-site
IInnttrroodduuccttiioonn

4CVHE-SVX005B-EN
technical supervision of the disassembly and
reassembly work
• The installing contractor must notify Trane—or an
agent of Trane specifically authorized to perform
startup and warranty of Trane®products—two
weeks in advance of the scheduled disassembly
work to coordinate the disassembly and
reassembly work
• Start-up must be performed by Trane or an agent of
Trane specifically authorized to perform startup and
warranty of Trane®products
Trane, or an agent of Trane specifically authorized to
perform start-up and warranty of Trane®products, will
provide qualified personnel and standard hand tools to
perform the disassembly and reassembly work at a
location specified by the contractor The contractor
shall provide the rigging equipment such as chain falls,
gantries, cranes, forklifts, etc necessary for the
disassembly and reassembly work and the required
qualified personnel to operate the necessary rigging
equipment
Copyright
This document and the information in it are the
property of Trane, and may not be used or reproduced
in whole or in part without written permission Trane
reserves the right to revise this publication at any time,
and to make changes to its content without obligation
to notify any person of such revision or change
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners
Factory Training
Factory training is available through Trane University™
to help you learn more about the operation and
maintenance of your equipment To learn about
available training opportunities contact Trane
University™
Online: www trane com/traneuniversity
Phone: 855-803-3563
Email: traneuniversity@trane com
Revision History
• Added refrigerant oil types and post-service
compressor air-run procedures for R-514A
refrigerant in Introduction and Recommended
Maintenance chapters
• Running edits
IInnttrroodduuccttiioonn

CVHE-SVX005B-EN 5
Unit Nameplate 8
Model Number Descriptions 9
Pre-Installation 10
ASHRAE Standard 15 Compliance 10
Unit Shipment 10
Installation Requirements and
Contractor Responsibilities 10
Storage Requirements 12
Unit Components 14
Unit Clearances and Weights 15
Recommended Unit Clearances 15
General Weights 16
Weights (lb) 16
Weights (kg) 20
Installation: Mechanical 25
Operating Environment 25
Foundation Requirements 25
Rigging 25
Standard Chiller Lift 25
Special Lift Requirements 27
Unit Isolation 27
Isolation Pads 27
Spring Isolators 27
Leveling the Unit 29
Installation: Water Piping 30
Overview 30
Water Treatment 30
Water Pressure Gauges 30
Valves—Drains and Vents 30
Strainers 31
Required Flow-Sensing Devices 31
Paddle Switches 31
Water Flow Detection Controller and
Sensor 31
Evaporator and Condenser Water
Piping 33
Water Piping Connections 34
Waterbox Locations 35
Grooved Pipe Coupling 35
Flange-connection Adapters 36
Victaulic Gasket Installation 36
Screw-Tightening Sequence for Water
Piping Connections 37
Flanges with 4, 8, or 12 Screws 38
Flanges with 16, 20, or 24
Screws 38
Flanges with More than 24
Screws 38
Evaporator Waterbox Covers 39
Pressure Testing Waterside Piping 39
Eddy Current Testing 39
Vent Piping 40
Refrigerant Vent Line 40
General Requirements 40
Purge Discharge 40
Vent Line Materials 40
Vent Line Sizing 40
Vent Line Installation 41
Vent Line Sizing Reference 44
Insulation 47
Unit Insulation Requirements 47
Insulation Thickness Requirements 47
Factory-applied Insulation 47
Installation: Controls 49
Symbio 800 49
AdaptiView Display 49
Tracer TU 49
Control Panel 51
Installing the Tracer AdaptiView
Display 53
Adjusting the Tracer AdaptiView Display
Arm 54
Module Installation 55
Air-Fi 55
Wi-Fi 56
Electrical Requirements 57
Table of Contents

6CVHE-SVX005B-EN
Installation Requirements 57
Electrical Requirements 57
Trane-supplied Starter Wiring 58
Customer-supplied Remote Starter
Wiring 59
Current Transformer and Potential
Transformer Wire Sizing 59
Power Supply Wiring 61
Three-Phase Power 61
Circuit Breakers and Fused
Disconnects 61
Power Factor Correction Capacitors
(Optional) 61
Interconnecting Wiring 62
Starter to Motor Wiring (Remote-
Mounted Starters Only) 63
Ground Wire Terminal Lugs 63
Terminal Clamps 64
Wire Terminal Lugs 64
Bus Bars 64
Starter to Control Panel Wiring 65
10 to 13 8kV Medium Voltage Motor 66
Motor Terminal Box 66
Motor Supply Wiring 67
Motor Terminals 67
Ground Wire Terminal Lug 67
System Control Circuit Wiring (Field
Wiring) 68
Water Pump Interlock Circuits and Flow
Switch Input 69
Chilled Water Pump 69
Chilled Water Proof of Flow 69
Condenser Water Pump 69
Condenser Water Proof of Flow 69
Heat Recovery Proof of Flow 69
Temperature Sensor Circuits 70
CWR—Outdoor Option 70
Optional Control and Output
Circuits 70
Starter Module Configuration 70
Schematic Wiring Drawings 70
Operating Principles 71
General Requirements 71
Cooling Cycle 71
CVHE and CVHG 3-Stage
Compressor 71
CVHF 2-Stage Compressor 71
Oil and Refrigerant Pump 72
Compressor Lubrication
System 72
Motor Cooling System 75
Tracer AdaptiView Display 75
Start-up and Shut-down 76
Sequence of Operation 76
Software Operation Overview
Diagram 76
Start-up Sequence of Operation—
Wye-delta 77
Power Up 81
Ice Building Control 81
Free Cooling Cycle 83
Free Cooling (FRCL) 84
Hot Gas Bypass (HGBP) 84
Hot Water Control 84
Heat Recovery Cycle 85
Auxiliary Condensers 85
Control Panel Devices and Unit-Mounted
Devices 85
Unit Control Panel 85
User-defined Language Support 86
Unit Start-up and Shut-down
Procedures 86
Daily Unit Start-up 86
Seasonal Unit Start-up 87
Daily Unit Shut-down 87
Seasonal Unit Shut-down 87
Recommended Maintenance 88
Record Keeping Forms 88
Normal Operation 88
TTaabbllee ooff CCoonntteennttss

CVHE-SVX005B-EN 7
Recommended Compressor Oil
Change 90
Purge System 91
Leak Checking Based on Purge Pump
Out Time 91
Long Term Unit Storage 91
Refrigerant Charge 92
Leak Testing 93
Recommended System
Maintenance 93
Condenser 93
Evaporator 94
Waterbox and Tubesheet Protective
Coatings 94
Sacrificial Anodes 94
Waterbox Removal and Installation 95
Discussion 95
Procedure 95
Reassembly 96
Torque Requirements and Waterbox
Weights 96
Connection Devices Information 97
Appendix A: Forms and Check
Sheets 98
Unit Start-up/Commissioning 98
Appendix B: Chiller Installation
Completion and Request for Trane
Service 99
Appendix C: CenTraVac™Chiller Start-
up Tasks to be Performed by Trane 102
Appendix D: CenTraVac™Chiller Annual
Inspection List 104
Appendix E: CenTraVac™Chiller
Operator Log 105
TTaabbllee ooff CCoonntteennttss

8CVHE-SVX005B-EN
Unit Nameplate
The unit nameplate is located on the left side of the
control panel A typical unit nameplate is illustrated in
the following figure and contains the following
information:
• Unit model and size descriptor
• Unit electrical requirements
• Correct operating charge and refrigerant type
• Unit test pressures and maximum operating
pressures
• Unit literature
SSeerriiaall NNuummbbeerr The unit serial number provides the
specific chiller identity Always provide this serial
number when calling for service or during parts
identification
SSeerrvviiccee MMooddeell NNuummbbeerr The service model represents
the unit as built for service purposes It identifies the
selections of variable unit features required when
ordering replacements parts or requesting service
NNoottee:: nit-mounted starters are identified by a
separate number found on the starter.
PPrroodduucctt DDeessccrriippttiioonn BBlloocckk The CenTraVac™chiller
models are defined and built using the Product
Definition and Selection (PDS) system This system
describes the product offerings using a product coding
block which is made up of feature categories and codes
that identify all characteristics of a unit
Figure 1. Typical unit nameplate

CVHE-SVX005B-EN 9
Model Number Descriptions
Digit 1, 2, 3 — Unit Function
Digit 4 — Development Sequence
Digit 5, 6, 7 — Nominal Tonnage
Digit 8 — Unit Voltage
Digit 9 — Unit Type
Digit 10, 11 — Design Sequence
Digit 12 — Hot Gas Bypass
Digit 13 — Starter Type
Digit 14 — Control Enclosure
Digit 15 — Compressor Motor Power
(CPKW)
Digit 16, 17, 18 — Compressor Impeller
Cutback
Digit 19 — Evaporator Shell Size
Digit 20 — Evaporator Tube Bundle
(Nominal Tons)
Digit 21 — Evaporator Tubes
Digit 22 — Evaporator Waterbox
Digit 23 — Condenser Shell Size
Digit 24 — Condenser Tube Bundle
(Nominal Tons)
Digit 25 — Condenser Tubes
Digit 26 — Condenser Waterbox
Digit 27 — Heat Recovery Condenser
Shell Size
Digit 28 — Heat Recovery Condenser
Tube Bundle (Nominal Tons)
Digit 29 — Heat Recovery Tubes
Digit 30 — Heat Recovery Condenser
Waterbox
Digit 31 — Auxiliary Condenser Size and
Waterbox
Digit 32 — Auxiliary Condenser Tubes
Digit 33 — Orifice Size
Digit 34 — Orifice Size
Digit 35 — Unit Option: Insulation and
RuptureGuard™™
Digit 36 — Enhanced Protection
Digit 37 — Generic BAS
Digit 38 — Extended Operation
Digit 39 — Tracer®® Communication
Interface
Digit 40 — Condenser Refrigerant
Control
Digit 41 — Manufacturing Location
Digit 42 — Special Option
Digit 43 — Water Flow Control
Digit 44 — Chilled Water Reset
Digit 45 — Heat Recovery Temperature
Sensors
Digit 46 — Gas Powered Chiller
Digit 47 — Compressor Motor Frame Size
Digit 48 — Volute Discharge Angle
Digit 49 — Operating Status
Digit 50 — Industrial Chiller Package
Digit 51 — Control Power Transformer
Digit 52 — Motor and Terminal Board
Configuration
Digit 53 — Thermal Dispersion Water
Flow Proving

10 CVHE-SVX005B-EN
Pre-Installation
ASHRAE Standard 15
Compliance
Trane recommends that indoor CenTraVac™chiller
installations fully meet or exceed the guidelines of the
current version of ASHRAE®Standard 15, in addition
to any applicable national, state, or local requirements
This typically includes:
• A refrigerant monitor or detector that is capable of
monitoring and alarming within the acceptable
exposure level of the refrigerant, and that can
actuate mechanical ventilation
• Audible and visual alarms, activated by the
refrigerant monitor, inside the equipment room and
outside of every entrance
• The equipment room should be properly vented to
the outdoors, using mechanical ventilation that can
be activated by the refrigerant monitor
• The purge discharge and the rupture disk must be
properly piped to the outdoors
• If required by local or other codes, a self-contained
breathing apparatus should be available in close
proximity to the equipment room
Refer to the latest copy of ASHRAE Standard 15 for
specific guidelines Trane assumes no responsibility for
any economic, health, or environmental issues that
may result from an equipment room’s design or
function
Unit Shipment
Inspect unit while it is still on the truck for any shipping
damage The chiller ships shrink-wrapped in a 0 010-in
(0 254 mm) recyclable film protective covering Do NOT
remove shrink-wrap for inspection! Inspect for damage
to the shrink-wrap and determine if physical damage
has occurred
Each chiller ships from the factory as a hermetically
assembled package; it is factory-assembled, -wired,
and -tested All openings except for the waterbox vent
and drain holes are covered or plugged to prevent
contamination during shipment and handling “Unit
Components,” p 14 shows an illustration of a typical
unit and its components As soon as the unit arrives at
the job site, inspect it thoroughly for damage and
material shortages In addition:
1 Verify the hermetic integrity of the unit by checking
the chiller pressure for an indication of holding
charge pressure
2 To prevent damaging moisture from entering the
unit and causing corrosion, each chiller is
pressurized with 3 to 5 psig (20 7 to 34 5 kPaG) of
dry nitrogen before shipment
NNoottee:: The holding charge should register
approximately 5 psig (34.5 kPaG) at 72°F (22.2°C).
Place a gauge on the access valve provided
(indicated by arrow and circle in the following
figure) on the refrigerant pump discharge line to
verify the holding charge. If the charge has
escaped, contact your local Trane sales office for
instructions.
3 The loose parts box and isolator pads ship on top of
the control panel box
4 Check the oil sump sight glasses to verify that the
sump was factory-charged with 9 gallons (34 1 L) of
oil If no oil level is visible, contact your local Trane
sales office
IImmppoorrttaanntt:: If isolation springs are installed, do NOT
block oil tank serviceability.
Figure 2. Refrigerant pump discharge line access
valve
Installation Requirements and
Contractor Responsibilities
A list of the contractor responsibilities typically
associated with the unit installation process is provided
in the following table
WWAARRNNIINNGG
CCoommbbuussttiibbllee MMaatteerriiaall!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn
ddeeaatthh ,, sseerriioouuss iinnjjuurryy,, oorr eeqquuiippmmeenntt ddaammaaggee
SShhrriinnkk--wwrraapp iiss aa ccoommbbuussttiibbllee mmaatteerriiaall AAvvooiidd ooppeenn
ffllaammeess aanndd hhoott ssppaarrkkss

CVHE-SVX005B-EN 11
NNoottee:: The chiller should remain within its protective
shrink-wrap covering during storage.
Type of Requirement Trane Supplied
Trane Installed
Trane Supplied
Field Installed
Field Supplied
Field Installed
Foundation • Meet foundation requirements
Rigging
• Safety chains
• Rigging shackles
• Lifting beam
Disassembly/Reassembly
(as required)
• Trane will perform or have
direct on-site supervision
of the disassembly and
reassembly work (contact
your local Trane office for
pricing)
Isolation • Isolation pads or spring
isolators
• Isolation pads or spring isolators
• Optional spring isolators, when required, are
installed by others; do NOT overload springs and do
NOT install isolation springs if they block serviceable
parts such as the oil tank system, service valves,
etc.
Electrical
• Circuit breakers or fusible
disconnects (optional)
• Unit-mounted starter
(optional)
• Power factor correction
capacitors (PFCCs)
(optional)
• Jumper bars
• Temperature sensor
(optional outdoor air)
• Flow switches (may be
field supplied); for
installation instructions
for the ifm efector®flow
detection controller and
sensor, refer to “Water
Flow Detection
Controller and
Sensor,” p. 31 or Trane
literature that shipped
with the device
• Remote-mounted
starter (optional)
• Air-Fi®wireless
communication
(optional)
• Wi-Fi wireless
communication
(optional)
• Circuit breakers or fusible disconnects (optional)
• Electrical connections to unit-mounted starter
(optional)
• Electrical connections to remote-mounted starter
(optional)
• Wiring sizes per submittal and National Electric Code
(NEC)
• PFCCs (remote mounted starter optional only)
• Terminal lugs
• Ground connection(s)
• Jumper bars
• BAS wiring (optional)
• Inter-processor communication (IPC) wiring (AFD
and remote-mounted starters only)
• Control voltage wiring (AFD and remote-mounted
starters only)
• Oil pump interlock wiring (AFD and remote mounted
starters only)
• High condenser pressure interlock wiring (AFD and
remote-mounted starters only)
• Chilled water pump contactor and wiring including
interlock
• Condenser water pump contactor and wiring
including interlock
• Option relays and wiring
• Symbio 800 BAS communication wiring (optional)
Water piping • Flow sensing devices
(may be field supplied)
• Taps for flow sensing devices
• Taps for thermometers and gauges
• Thermometers
• Strainers (as required)
• Water flow pressure gauges
• Isolation and balancing valves in water piping
• Vents and drain on waterbox valves (one each per
pass)
• Pressure relief valves (for waterboxes as required)
PPrree--IInnssttaallllaattiioonn

12 CVHE-SVX005B-EN
Type of Requirement Trane Supplied
Trane Installed
Trane Supplied
Field Installed
Field Supplied
Field Installed
Relief • Rupture disk assembly
• RuptureGuard™
(optional); refer to
Installation, Operation,
and Maintenance:
RuptureGuard Pressure
Relief System Option
(CTV-SVX06*-EN)
• Vent line and flexible connector and vent line from
rupture disk to atmosphere
Insulation • Insulation (optional) • Insulation
• Chiller feet insulation
Water Piping Connection
Components
Flanged (optional)
• Welded on flange for
300 psig (2068.4 kPaG)
waterboxes
Flanged (optional)
• Victaulic®to flange
adapter for 150 psig
(1034.2 kPaG)
waterboxes
Victaulic®
• Victaulic®coupling for 150 psig (1034.2 kPaG) and
300 psig (2068.4 kPaG) waterboxes
• Fasteners for flanged-type connections (optional)
Other Materials
• Trace gas (1 lb [0.45 kg] maximum per machine as
needed to perform leak testing)
• Material and equipment to perform leak testing
• Dry nitrogen (8 psig [55.2 kPaG] maximum per
machine as needed)
“Appendix B: Chiller
Installation Completion
and Request for Trane
Service,” p. 99 (CTV-
ADF001*-EN; refer to “,”)
• To be completed by installing contractor prior to
contacting Trane for start-up
Chiller start-up
commissioning(a)
• Trane, or an agent of
Trane specifically
authorized to perform
start-up of Trane®
products
Post-commissioning
transport of empty
refrigerant containers for
return or recycling
• Move empty refrigerant containers to an easily
accessible point of loading
(a) Start-up must be performed by Trane or an agent of Trane specifically authorized to perform start-up and warranty of Trane®products. Contractor shall
provide Trane (or an agent of Trane specifically authorized to perform start-up) with notice of the scheduled start-up at least two weeks prior to the
scheduled start-up.
Storage Requirements
NNoottee:: If the chiller is stored outdoors for any amount of
time, ddoo NNOOTT rreemmoovvee AANNYY sshhiippppiinngg
ccoovveerriinnggss.. PPrrootteecctt tthhee cchhiilllleerr ffrroomm tthhee
eelleemmeennttss aanndd pprrootteecctt aaggaaiinnsstt ffrreeeezziinngg,,
especially if any shipping materials have been
removed.
NNOOTTIICCEE
EEqquuiippmmeenntt DDaammaaggee!!
FFaaiilluurree ttoo pprrootteecctt tthhee uunniitt ffrroomm ffrreeeezziinngg ccoouulldd
rreessuulltt iinn eeqquuiippmmeenntt ddaammaaggee
IIff fflluuiidd hhaass bbeeeenn aaddddeedd ttoo tthhee ppiippiinngg,, tthhee uunniitt mmuusstt
bbee pprrootteecctteedd ffrroomm ffrreeeezziinngg FFrreeeezzee ddaammaaggee ffrroomm
aann uunnhheeaatteedd eeqquuiippmmeenntt rroooomm iiss nnoott tthhee TTrraannee
ccoommppaannyy''ss rreessppoonnssiibbiilliittyy TThheessee aarree iinnddoooorr uunniittss
NNOOTTIICCEE
IInnssuullaattiioonn DDaammaaggee!!
FFaaiilluurree ttoo ffoollllooww tthheessee iinnssttrruuccttiioonnss ccoouulldd rreessuulltt iinn
iinnssuullaattiioonn ddaammaaggee
TToo pprreevveenntt ddaammaaggee ttoo ffaaccttoorryy iinnssttaalllleedd iinnssuullaattiioonn::
•• DDoo nnoott aallllooww tthhee iinnssuullaattiioonn ttoo bbee eexxppoosseedd ttoo
eexxcceessssiivvee ssuunnlliigghhtt SSttoorree iinnddoooorrss oorr ccoovveerr wwiitthh
ccaannvvaass ttoo pprreevveenntt eexxppoossuurree
•• DDoo nnoott uussee tthhiinnnneerrss aanndd ssoollvveennttss oorr ootthheerr ttyyppeess
ooff ppaaiinntt UUssee oonnllyy wwaatteerr bbaassee llaatteexx
Less than 1 month 1–6 months Greater than 6 months
Location requirements:
• Solid foundation
• Vibration free
• Dry
• Temperature range -40°F to 158°F
(-40°C to 70°C)
Location requirements:
• Solid foundation
• Vibration free
• Dry
• Temperature range -40°F to 158°F
(-40°C to 70°C)
Location requirements:
• Solid foundation
• Vibration free
• Dry
• Temperature range -40°F to 158°F
(-40°C to 70°C)
• Do not remove any plastic coverings • Do not remove any plastic coverings • Do not remove any plastic coverings
PPrree--IInnssttaallllaattiioonn

CVHE-SVX005B-EN 13
Less than 1 month 1–6 months Greater than 6 months
• Do not charge the chiller with refrigerant
• If additional refrigerant is on site, follow
manufacturer’s storage requirements
• Do not charge the chiller with refrigerant
• If additional refrigerant is on site, follow
manufacturer’s storage requirements
• Do not charge the chiller with refrigerant
• If additional refrigerant is on site, follow
manufacturer’s storage requirements
• Verify dry nitrogen pressure using gauge
located on the evaporator shell reads
3 to 5 psig (20.7 to 34.5 kPaG)
• Notify the local Trane office if charge has
escaped
• Verify dry nitrogen pressure using gauge
located on the evaporator shell reads
3 to 5 psig (20.7 to 34.5 kPaG)
• Notify the local Trane office if charge has
escaped
• Verify dry nitrogen pressure using gauge
located on the evaporator shell reads 3 to 5 psig
(20.7 to 34.5 kPaG)
• Notify the local Trane office if charge has
escaped
• Do not operate purge unit • Do not operate purge unit • Do not operate purge unit
• Verify waterbox and tube bundles are
clean and dry
• Verify waterbox and tube bundles are clean and
dry
• Conduct an oil analysis and verify no oil
breakdown(a)
• Repeat yearly
• Replace oil if breakdown has occurred
• If no oil analysis program has been followed,
replace oil prior to start-up
• Every six months, check unit pressure or
vacuum and take note of changes that could
indicate a leak; contact your local Trane office if
any leaks occur
• Every six months, start the oil pump and rotate
compressor shaft about 450° to prevent
potential bearing issues (a); contact your local
Trane Service Agency to perform this task
• If the chiller will be stored for more than
six months after production, contact your local
Trane Service Agency for required extended
storage actions to minimize impact to the chiller
and preserve the warranty.
• Chillers stored five years or longer should be
inspected for leaks every five years by a
qualified service organization
(a) If the chiller will be stored for more than six months after production, contact your local Trane Service Agency for required extended storage actions to
minimize impact to the chiller and preserve the warranty.
PPrree--IInnssttaallllaattiioonn

14 CVHE-SVX005B-EN
Unit Components
NNoottee:: The control panel side of the unit is always
designated as the front side of the unit.
Figure 3. Typical CVHF CenTraVac™™ chiller
1
2
3
4
5
6
7
8
9
0
-0
1 Suction Elbow
2 Compressor
3 Terminal Box
4 Control Panel
5 Condenser
6 Motor Housing
7 Economizer
8 Oil Tank Assembly
9 Purge
10 Evaporator
11 Display Panel
PPrree--IInnssttaallllaattiioonn

CVHE-SVX005B-EN 15
Unit Clearances and Weights
Recommended Unit Clearances
Adequate clearances around and above the chiller are
required to allow sufficient access for service and
maintenance operations Specific unit clearance
requirements are indicated in the submittal package
provided for your unit
• Do NOT install piping or conduit above the
compressor motor assembly or behind the suction
elbow of the unit
• Minimum vertical clearance above the unit is 3 ft
(92 cm)
• Use a housekeeping pad to provide better service
clearances; refer to submittal for more information
Per National Electric Code (NEC) Article 110: Unit
mounted starters from 0 to 600V require a 42 inch
(107 cm) clearance, 601 to 2500V require a 48 inch
(122 cm) clearance, and 2501 to 9000V require a 60 inch
(152 cm) clearance Refer to NEC and local electrical
codes for starter and control panel clearance
requirements
Figure 4. Clearance requirements
3 ft. (92 cm)
A
18 in. (46 cm)
Economizer
Auxiliary condenser (optional)
Cooling condenser
Evaporator Motor
Right-hand tube pull shown, apply
tube pull clearance dimension to
left end for left-hand tube pull.
Optional
unit-mounted starter
These dimensions per
NEC Article 110
B
C
D
E
Table 1. Clearance requirements
Evaporator Size Shell Combo A B C D E
in. cm in. cm in. cm in. cm in. cm
032 Short/Long
Short/Short 45 114 141 358 321 815 34 86 53 134
Short/Long 77 195 219 556 431 1094 34 86 53 134
Long/Long 45 114 187 474 411 1043 34 86 53 134
050 Short/Long
Short/Short 45 114 141 358 321 815 40 101 62 157
Short/Long 78 198 219 556 431 1094 40 101 62 157
Long/Long 45 114 187 474 411 1043 40 101 62 157

16 CVHE-SVX005B-EN
Table 1. Clearance requirements (continued)
Evaporator Size Shell Combo A B C D E
in. cm in. cm in. cm in. cm in. cm
080 Short/Long
Short/Short 53 134 141 358 329 835 36 91 76 193
Short/Long 85 215 219 556 439 1115 36 91 76 193
Long/Long 53 134 187 474 419 1064 36 91 76 193
142 Medium/Long/
Extended
210 Long
Medium/Long 78 198 207 525 444 1127 44 111 92 233
Long/Long 58 147 187 474 424 1076 44 111 92 233
Extended/Long 58 147 209 530 469 1191 44 111 92 233
Long/Long 59 149 187 474 426 1082 47 119 102 259
250 Extended Extended/Long 63 160 209 530 475 1206 43 109 115 292
Note: All dimensions are approximate; refer to the unit submittal package for exact dimensions for your unit.
eneral Weights
Weights (lb)
IImmppoorrttaanntt:: The weight information provided here
should be used for general information
only. Trane does not recommend using this
weight information for considerations
relative to chiller handling, rigging, or
placement. The large number of variances
between chiller selections drives variances
in chiller weights that are not recognized in
these tables. For specific weights for your
chiller, refer to your submittal package.
UUnniitt CClleeaarraanncceess aanndd WWeeiigghhttss

CVHE-SVX005B-EN 17
Table 2. Representative weights, 60 Hz chillers (lb)
Model
Comp Size
CPKW
Evap Size Cond Size Weights without Starters Weights with Starters
NTON EVSZ CDSZ Operating Shipping Operating Shipping
CVHE
230–320
233
032S 032S
14828 13469 — —
289 — — 16508 15149
230–320 289 032S 032L 15433 13924 17113 15604
230–320 289 032L 032L 16277 14574 17957 16254
230–320 289 050S 050S 20035 17599 21715 19279
230–320 289 050S 050L 21001 18356 22681 20036
230–320 289 050L 050L 22352 19304 24032 20984
360–500 455 050S 050S 20717 18281 22397 19961
360–500 455 050S 050L 21683 19038 23363 20718
360–500 455 050L 050L 23034 19986 24714 21666
360–500 455 050S 080S 23200 20265 24880 21945
360–500 455 050L 080L 26793 22976 28473 24656
360–500 455 080S 080S 29854 25634 31534 27314
360–500 455 080S 080L 31442 26917 33122 28597
360–500 455 080L 080L 33463 28333 35143 30013
UUnniitt CClleeaarraanncceess aanndd WWeeiigghhttss

18 CVHE-SVX005B-EN
Table 2. Representative weights, 60 Hz chillers (lb) (continued)
Model
Comp Size
CPKW
Evap Size Cond Size Weights without Starters Weights with Starters
NTON EVSZ CDSZ Operating Shipping Operating Shipping
CVHF
350–570 588 050S 050S 20487 17984 22167 19664
350–570 588 050S 050L 21453 18741 23133 20421
350–570 588 050L 050L 22703 19567 24383 21247
350–570 588 050S 080S 22970 19968 24650 21648
350–570 588 050L 080L 26512 22557 28192 24237
350–570 588 080S 080S 31845 26997 32173 27715
350–570 588 080S 080L 32131 27318 33811 28998
350–570 588 080L 080L 34319 28855 35999 30535
350–910 957 080S 080S 32843 28385 35843 31385
350–910 957 080S 080L 34481 29668 37481 32668
350–910 957 080L 080L 36669 31205 39669 34205
350–910 957 080L 142L 44814 37663 47814 40663
350–910 957 142M 142L 48446 40540 51446 43540
350–910 957 142L 142L 49667 41453 52667 44453
1070–1300 1062 080L 142L 45710 38559 48710 41559
1070–1300 1062 142M 142L 49116 41210 52116 44210
1070–1300 1062 142L 142L 50337 42123 53337 45123
1070–1300 1062 142E 142L 51762 43109 54762 46109
1070–1300 1062 142M 210L 55062 46057 58062 49057
1070–1300 1062 142L 210L 56333 46970 59333 49970
1070–1300 1062 142E 210L 57758 47956 60758 50956
1070–1300 1062 210L 210L 61899 51929 64899 54929
1070–1300 1062 250E 250L 76152 63330 79152 66330
1470 1340 210L 210L 64550 54580 67550 57580
1470–1720 1340 142L 210L 58984 49621 61984 52621
1470–1720 1340 250E 250L 78803 65981 81803 68981
Notes:
1. TECU tubes, 0.028 in. tube wall thickness.
2. 300 psig marine waterboxes.
3. Heaviest possible bundle and motor combination.
4. Operating weights assume the largest possible refrigerant charge.
5. Weights with starters assume the heaviest possible starter (AFD when it’s an allowed option).
6. Industrial Control Panel (INDP) option, add 50 lb.
7. Control Power Transformer (CPTR) option, add 130 lb.
8. Supplemental Motor Protection (SMP) option, add 500 lb.
UUnniitt CClleeaarraanncceess aanndd WWeeiigghhttss

CVHE-SVX005B-EN 19
Table 3. Representative weights, 50 Hz chillers (lb)
Model
Comp Size
CPKW
Evap Size Cond Size Weights without Starters Weights with Starters
NTON EVSZ CDSZ Operating Shipping Operating Shipping
CVHE
190–320
215
032S 032S
14785 13426 — —
231 — — 16456 15097
190–320
215
032S 032L
15390 13881 — —
231 — — 17061 15552
190–320
215
032L 032L
16234 14531 — —
231 — — 17905 16202
190–320
215
050S 050S
19696 17195 — —
231 — — 21419 18918
190–320
215
050S 050L
20712 17952 — —
231 — — 22435 19675
190–320
215
050L 050L
21829 18682 — —
231 — — 23636 20502
300–500
360
050S 050S
21307 18806 — —
379 — — 22608 20107
300–500
360
050S 050L
22323 19563 — —
379 — — 23624 20864
300–500
360
050L 050L
23524 20390 — —
379 — — 24825 21691
300–500
360
050S 080S
24923 21589 — —
379 — — 26224 22890
300–500
360
080S 080S
30740 26520 — —
379 — — 32041 27821
300–500
360
080S 080L
32328 27803 — —
379 — — 33629 29104
300–500
360
080L 080L
34349 29219 — —
379 — — 35650 30520
UUnniitt CClleeaarraanncceess aanndd WWeeiigghhttss

20 CVHE-SVX005B-EN
Table 3. Representative weights, 50 Hz chillers (lb) (continued)
Model
Comp Size
CPKW
Evap Size Cond Size Weights without Starters Weights with Starters
NTON EVSZ CDSZ Operating Shipping Operating Shipping
CVHG
480–565 489 050S 050S 22258 19747 22815 20304
480–565 489 050S 050L 23274 20504 23831 21061
480–565 489 050L 050L 24391 21244 24948 21801
480–565 489 050S 080S 25874 22538 26431 23095
480–565 489 050L 080L 28712 24647 29269 25204
480–565 489 080S 080L 33279 28754 33836 29311
670–780 621 080S 080S 32952 28732 33509 29289
670–780 621 080S 080L 34540 30015 35097 30572
670–780 621 080L 080L 36561 31431 37118 31988
670–780 621 080L 142L 45020 38203 45577 38760
670–780 621 142M 142L 49518 41562 50075 42119
670–780 621 142L 142L 50789 42475 51346 43032
920–1100 621 080L 142L 46086 39269 46643 39826
920–1100 892 142M 142L 50988 43032 51545 43589
920–1100 892 142L 142L 52259 43945 52816 44502
920–1100 892 142M 210L 56984 47879 57541 48436
920–1100 892 142L 210L 58205 48792 58762 49349
920–1100 892 142E 210L 59630 49778 60187 50335
920–1100 892 210L 210L 63821 53751 64378 54308
Notes:
1. TECU tubes, 0.028 in. tube wall thickness.
2. 300 psig marine waterboxes.
3. Heaviest possible bundle and motor combination.
4. Operating weights assume the largest possible refrigerant charge.
5. Weights with starters assume the heaviest possible starter (AFD when it’s an allowed option).
6. Industrial Control Panel (INDP) option, add 50 lb.
7. Control Power Transformer (CPTR) option, add 130 lb.
8. Supplemental Motor Protection (SMP) option, add 500 lb.
Weights (kg)
IImmppoorrttaanntt:: The weight information provided here
should be used for general information
only. Trane does not recommend using this
weight information for considerations
relative to chiller handling, rigging, or
placement. The large number of variances
between chiller selections drives variances
in chiller weights that are not recognized in
these tables. For specific weights for your
chiller, refer to your submittal package.
UUnniitt CClleeaarraanncceess aanndd WWeeiigghhttss
This manual suits for next models
2
Table of contents
Other Trane Technologies Chiller manuals

Trane Technologies
Trane Technologies THERMO KING C Series User manual

Trane Technologies
Trane Technologies CVHE Installation and operating instructions

Trane Technologies
Trane Technologies RTAG 225 Owner's manual

Trane Technologies
Trane Technologies Agility HDWA PC 747 Installation and operating instructions