
RLC-SVU007B-GB 9
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
Low Voltage Wiring / Ice Making (Optional)
Low Voltage Wiring
The remote devices described below require low voltage
wiring. All wiring to and from these remote input devices
to the Control Panel must be made with shielded, twisted
pair conductors. Be sure to ground the shielding only at
the panel.
Important:
To prevent control malfunctions, do not run low voltage
wiring (<30 V) in conduit with conductors carrying more
than 30 volts.
Emergency Stop
UC800 provides auxiliary control for a customer
specified/installed latching trip out. When customer
furnished remote contact 6S2, the chiller will run
normally when the contact is closed. When the contact
opens, the unit will stop and a manually resettable
diagnostic is generated.This condition requires manual
reset at the chiller switch on the front of the control
panel.
This customer-furnished contact must be compatible
with 24 VDC, 12 mA resistive load.
External Auto/Stop
If the unit requires external Auto/Stop function, the
installer must provide remote contact 6S1.
The chiller will run normally when the contact is closed.
When contact opens, the compressor(s), if operating, will
go to the RUN: UNLOAD operating mode and cycle off.
Unit operation will be inhibited. Closure of the contact
will permit the unit to return to normal operation.
Field-supplied contacts for all low voltage connections
must be compatible with dry circuit 24 VDC for a 12mA
resistive load. Refer to the field diagrams that are
shipped with the unit.
Ice Making (Optional)
When the Ice Making Command is removed (i.e. all
the installed Ice Making inputs are set to “auto”), the
compressors shall be stopped after the run unload
period (if not already stopped due to Ice Making
Complete).The chiller shall return to normal Auto mode
of operation, and allowed to restart only after enforcing a
2 minute delay called the “Ice to NormalTransition time”.
During this inhibit, the Evaporator water flow request
shall be commanded on. After the delay, the chiller can
restart again per the differential to start and the normal
Chilled Water Setpoint (or Hot Water Setpoint – if in
Heating Mode).The Ice To NormalTransition inhibit shall
be annunciated as a Chiller Submode and a countdown
timer showing the remaining time left shall be displayed.
Ice Making Configuration:
Ice Making is configured throughTU, and there shall be
two installation options:
1. Not Installed
2. Installed with Hardware
Ice Making: Not Installed
If the Ice Building Configuration item is set to ‘Not
Installed’, the application will not build the Ice Making
objects, and will require none of the Ice Making specific
LLIDS.
Ice Making: Installed with Hardware
If the Ice Making Configuration item is set to ‘Installed’,
the application will require the following LLIDs:
• External Ice Making Input (Dual Low Voltage Binary
Input)
Ice Making Setpoints:
After Ice Making is configured, there shall be three Ice
Making Settings or Setpoints:
1. Ice Making Command
2. Ice Making Enable/Disable
3. Ice MakingTermination Setpoint
The ice making setpoints can all be manipulated through
TU. Some of the Setpoints can be manipulated with User
Interface on the Display, the External Hardware Interface
BAS (if a BAS is installed).
The setpoints associated with ice making are explained
in more detail below.
Ice Making Command
This is the command to enter ice making.This setting is
defined as an Auto/On settings. Setting this to On will
command the application into ice building if ice building
is enabled and the Chiller is in the “Auto” command
mode. Setting the Ice Making command to Auto will
command the application to follow the next priority
functional mode.
Regardless of the setting of the Setpoint Source (see
setpoint arbitration.doc) any of the following 4 signals
can combine to comprise the Ice Building Command
(assuming they are each installed).
Contact closure input for External Ice Making Command
Front Panel Ice Making Command (also writable from
TU Lontalk Communicated Ice Making Command (LCI-C,
BACnet, Modbus)
Time of Day scheduler
All ice making signals have to be turned to “auto” to be
able to turn back Ice Making Command to “Auto” mode.
The overall Ice Making Command, must be toggled from
“Ice Making”, to “Auto” to “Ice Making” again, before Ice
Making can be entered a second time.
Ice Making Enable/Disable setting
This setting does not start or stop ice building.This is
the command to enable or disable the entire ice building
feature. It can only be set through the Display orTU.The
Ice Making Command starts and stops ice building.
Ice Making Termination setpoint
This setpoint controls when Ice Making is complete. If
the Entering WaterTemperature decreases below this
setpoint with no deadband Ice Making will be deemed
complete. This setpoint has a range of –6.7°C (20°F) to
0°C (32°F) with a default of -2.8°C (27°F).