Trane CVHE User manual

March 20, 2009 AFDH-SVN01A-EN
Installation
AFDH Retrofit Air-Cooled
Adaptive Frequency™ Drive
For UCP2™, Tracer™ CH531, and Tracer
AdaptiView™ Centrifugal Chiller Controllers
Models: CVHE, CVHF, AFDH

AFDH-SVN01A-EN © 2009 Trane All rights reserved
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at
appropriate intervals throughout this manual. Warnings are provided to alert installing contractors
to potential hazards that could result in personal injury or death. Cautions are designed to alert
personnel to hazardous situations that could result in personal injury, while notices indicate a
situation that may result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance
of these precautions.
Important
Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally
occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the
identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine
and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all
refrigerants containing these compounds have the same potential impact to the environment.
Trane advocates the responsible handling of all refrigerants-including industry replacements for
CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our
customers, and the air conditioning industry. All technicians who handle refrigerants must be
certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these
service procedures. In addition, some states or municipalities may have additional requirements
that must also be adhered to for responsible management of refrigerants. Know the applicable
laws and follow them.
WARNING
Contains Refrigerant!
System contains oil and refrigerant and may be under positive pressure. Recover refrigerant to
relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use
non-approved refrigerants, refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non-approved refrigerants, refrigerant
substitutes, or refrigerant additives could result in death or serious injury or equipment damage.
ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout
this literature. Read these carefully.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE:Indicates a situation that could result in equipment or property-damage only
accidents.

© 2009 Trane All rights reserved AFDH-SVN01A-EN
WARNING
Hazardous Voltage with Capacitors!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable
frequency drives or other energy storing components provided by Trane or others, refer to the
appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors.
Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect
power and discharge capacitors before servicing could result in death or serious injury.
Note: For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN
or PROD-SVB06A-FR
WARNING
Ground Wire!
All field-installed wiring must be completed by qualified personnel. All field-installed wiring
must comply with NEC and applicable local codes. Failure to follow this instruction could result
in death or serious injuries.
WARNING
Grounding Required!
Follow proper local and state electrical code on requirements for grounding. Failure to follow
code could result in death or serious injury.
WARNING
Heavy Objects!
Only attach cables (chains or slings) to the designated lifting points. Each of the cables (chains
or slings) used to lift the unit must be capable of supporting the entire weight of the unit. Lifting
cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.
Other lifting arrangements may cause equipment or property-only damage. Failure to properly
lift unit could result in death or serious injury.
WARNING
Improper Unit Lift!
An AFDH cabinet assembly is top heavy. Test lift unit to an approximate height of no greater than
24 inches to verify proper center of gravity lift point. To avoid dropping the unit, reposition lifting
point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible
equipment or property only damage.
WARNING
Conform to all applicable national, state, and local electrical codes!
Users MUST conform to all applicable national, state, and local electrical codes during the
electrical installation and servicing of this product. Failure to follow all applicable codes could
result in an arc flash event, electrocution, explosion, or fire, which could result in death or
serious injury.
NOTICE:
Conform to all applicable national, state, and local electrical codes!
The user is responsible for conforming to all applicable national, state, and local electrical codes
during the electrical installation of this product. Failure to observe this precaution could result in
an arc flash event or other forms of uncontrolled electrical discharge, explosion, or fire, which
could result in damage to, or destruction of the equipment.

4AFDH-SVN01A-EN
Introduction
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to do so could
cause damage to the equipment.
NOTICE:
Stand-mounted AFDH supported by equipment room floor!
A stand-mounted version of an AFDH drive is designed to be rigidly supported by the equipment
room floor. Therefore, a stand-mounted AFDH drive is not recommended for use with a chiller
that is equipped with spring-type vibration or seismic isolators. Trane recommends using a
remote floor-mounted AFDH drive in this application. Trane assumes no responsibility for
equipment damage caused by the installation of an AFDH drive version that is specified as being
incorrect for the application.
NOTICE:
Incorrect application! Adapting a floor stand kit to an E-Frame AFDH!
When properly installed, the part number 50689890010 Floor Stand Kit is designed to safely
support the weight of D-Frame model AFDH drives only. The largest model D-Frame drive
weighs 872 pounds. The smallest model E-Frame drive weighs 1193 pounds. Any attempt to
adapt the 50689890010 Floor Stand Kit to an E-Frame model AFDH drive will be considered an
unsupported field modification to the drive unit design. Trane assumes no responsibility for the
equipment damage caused by a stress or fatigue failure of the floor stand kit due to any use
outside of its intended application.
NOTICE:
Excessive cable lengths between AFDH drive and compressor motor!
The variable frequency drive industry recommends that the length of the electrical cables
connecting a drive unit to a motor should be kept to less than 50 feet to protect the motor from
reflected voltage waves that can cause the motor to fail. Cable lengths that exceed 50 feet
between the drive and the motor create the potential for damage to occur to the motor
windings and/or insulation. Trane assumes no responsibility for equipment damage caused by
use of improper cable lengths.
NOTICE:
Route incoming power conduit to the roof of the AFDH cabinet!
The air-cooled AFDH drive is designed to have the incoming power conduit routed vertically into
the unit through the removable conduit connection cover located on the left-hand rear corner of
the cabinet roof. If the starter that is being replaced by the AFDH drive has the incoming power
conduit routed horizontally across the top of the starter, or connected to the side or to the
bottom of the starter cabinet, an electrician will be required to reconfigure the conduit and
wiring. Routing the incoming power conduit into the AFDH cabinet anywhere other than
through the specified location on the cabinet roof, will be considered an unsupported field
modification to the cabinet design.
Introduction
The step-by-step instructions outlined in this manual describe the procedures required to
successfully install an AFDH Retrofit Air-Cooled Adaptive Frequency™ Drive package in place of an
existing starter on a Trane® CVHE or CVHF model centrifugal chiller. This only applies to chillers
having either a UCP2™ or UCP2 FastPak™ Controller, a Tracer™ CH531 Controller Retrofit, or a
Tracer AdaptiView™ Controller.

AFDH-SVN01A-EN 5
Introduction
D-Frame size AFDH drive packages can be ordered in a unit-mounted, stand-mounted, or remote
floor-mounted cabinet configuration. The D-Frame units can be equipped with a drive having a
maximum rating of 302 amps, 361 amps, or 443 amps.
The E-Frame size AFDH drive packages can be ordered in either a unit-mounted or a remote-floor
mounted cabinet configuration. The E-Frame units can be equipped with a drive having a
maximum rating of 540 amps, 590 amps, 678 amps, or 730 amps.
Important: The unit-mounted versions of AFDH Retrofit Air-Cooled Adaptive Frequency™ Drive
packages are not suitable for installation on chillers having direct-mount starters. To
determine if a specific unit-mounted starter is in fact a direct mount starter, please
refer to Figure 2, p. 12.
Note: Prior to July 1994, early version UCP2™ and UCP2 FastPak™ controls did not have AFD
compatible software in their Chiller Modules or their Clear Language Display Modules.
Between July 1994 to June 1998 the first release of AFD compatible UCP2™ hardware/
software allowed a speed reduction down to as low as 42 Hz. In June 1998, the second
version UCP2™ software release allowed speed reduction down to 38 Hz, which resulted in
slightly improved energy savings. To determine if a specific UCP2™ control type is
equipped with AFDH compatible hardware and software, please refer to “UCP2
compatibility with AFDH drives,” p. 16.
Note: The factory installed Tracer™ CH530 chiller controller system will not support an AFDH Air-
Cooled Adaptive Frequency™ drive. The controller system must first be upgraded to Tracer
AdaptiView™ before an AFDH retrofit package can be installed.
Note: At the time of writing of this manual edition (March 2009) only the D-Frame version of the
AFDH drive packages had been officially released for sale.
Note: The AFDH series of retrofit air-cooled Adaptive Frequency™ drive packages are only
intended for installation on existing Trane®chillers with CVHE or CVHF model centrifugal
compressors. Trane makes no claim of suitability or performance regarding retrofit AFDH
drives on older Trane®centrifugal compressor models or on chillers made by other
manufacturers. Although there may exist successful drive retrofits to these units, users are
cautioned that Trane has not evaluated these installations. Accordingly, Trane cannot
provide assurances regarding performance, reliability or suitability of retrofit AFDH
installations to other than Trane® model CVHE and CVHF compressors.
Other literature required before ordering or installing an AFDH retrofit
This manual must be used in conjunction with the following publications:
ECTV-PRB009-EN Engineering Bulletin, Chiller Upgrades Selection and Application Guideline for
Air-cooled Adaptive Frequency™ Drive Retrofit
TR1-SVX10A-EN TR1™ Series VFD Variable Frequency Drive Installation and Operation manual
CVRD-SVP01A-EN Tracer™CH531 Chiller Controller Retrofit Replacement Panel Startup and
Programming manual.
CVRE-SVP01A-EN Tracer AdaptiView™Panel Upgrade Programming Guide.
CTV-SVP02A-EN Tracer™TU Service Tool for Water-Cooled CenTraVac™Chillers with Tracer
AdaptiView™Controls Programming Guide.
CVHE-M-7 Water-Cooled Hermetic CenTraVac® Models CVHE and CVHF 50 and 60 Hz Cooling-Only
and Heat-Recovery Direct-Drive CenTraVacs with UCP2 Control Panels, Operation and
Maintenance manual.
Trademarks
Trane® and the Trane logo are trademarks of Trane in the United States and other countries. All
trademarks referenced in this document are the trademarks of their respective owners.

Table of Contents
AFDH-SVN01A-EN 6
Warnings, Cautions and Notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Other literature required before ordering or installing an AFDH retrofit . 5
Trademarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit Model Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Model Number Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Nameplates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 1. AFDH nameplate example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Confirming the AFDH package can be properly installed . . . . . . . . . . . . . . . 12
Installation considerations for unit-mounted AFDH drives . . . . . . . . . . . 12
Figure 2. Example of a direct-mount chiller starter panel . . . . . . . . . . . . . . . . 12
Figure 3. Comparison of unit-mounted AFDH to typical unit-mounted starter. 13
Installation considerations for stand-mounted AFDH . . . . . . . . . . . . . . . 14
Figure 4. Example of a stand-mounted version of an AFD drive . . . . . . . . . . . 14
Installation considerations for remote floor-mounted AFDH . . . . . . . . . 15
Confirm chiller controller system compatibility with AFDH drive . . . . . . . . 16
UCP2 compatibility with AFDH drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 1. AFDH compatible UCP2 module hardware & software part numbers 17
Equipment room ambient temperature considerations . . . . . . . . . . . . . . . . . 17
Chiller upgrades . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Electrical cable size specifications for AFDH drives . . . . . . . . . . . . . . . . . . . . 18
Table 2. Input/output power wire cable sizes AFDH D-Frame drives . . . . . . . 18
Table 3. Input/output power wire cable sizes AFDH E-Frame drives . . . . . . . 18
Requirements for installation technicians . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Tools required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Miscellaneous field provided material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Recommended rigging and lifting procedures for AFDH drive units . . . . . 20
Unit lifting points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 5. Unit lifting points and center of gravity . . . . . . . . . . . . . . . . . . . . . . 20
Preferred lifting method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 6. Preferred lifting method using two identical individual hoists . . . . . 21
Alternative lifting method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 7. Alternative lifting method using a single hoist and spreader bar . . . 21
AFDH Drive Package Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
D-Frame drive unit dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 8. Top, front, and side view of D-Frame AFDH cabinet with dimensions 22
Figure 9. Rear view of D-Frame AFDH cabinet with dimensions . . . . . . . . . . . 23
E-Frame drive unit dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Figure 10. Top, front, and side view of E-Frame AFDH cabinet with dimensions 24
Figure 11. Rear view of E-Frame AFDH cabinet with dimension . . . . . . . . . . . . 25
Drive unit weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

AFDH-SVN01A-EN 7
Table 4. AFDH D-Frame unit weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 5. AFDH E-Frame unit weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
D-Frame and E-Frame Drive unit components . . . . . . . . . . . . . . . . . . . . . . . . 26
Drive unit component parts housed within the custom enclosure . . . . . 26
Figure 12. Mounting location of D and E-Frame custom enclosure parts . . . . . 26
Table 6. Custom enclosure parts; D-Frame 302 amp model drives . . . . . . . . 28
Table 7. Custom enclosure parts; D-Frame 361 amp model drives . . . . . . . . 28
Table 8. Custom enclosure parts; D-Frame 443 amp model drives . . . . . . . . 29
Table 9. Custom enclosure parts; E-Frame 540 amp model drives. . . . . . . . . 30
Table 10. Custom enclosure parts; E-Frame 590 amp model drives. . . . . . . . . 30
Table 11. Custom enclosure parts; E-Frame 678 amp model drives. . . . . . . . . 31
Table 12. Custom enclosure parts; E-Frame 730 amp model drives. . . . . . . . . 31
Control box components for UCP2 version AFDH . . . . . . . . . . . . . . . . . . 32
Figure 13. D and E-Frame AFDH UCP2 control box components . . . . . . . . . . . 32
Table 13. UCP2 control box component part numbers . . . . . . . . . . . . . . . . . . 32
Additional hardware shipped with all UCP2 AFDH packages . . . . . . . . . 33
Table 14. UCP2 miscellaneous hardware package contents . . . . . . . . . . . . . . 33
Figure 14. Buss bar specifications; UCP2 miscellaneous hardware packages . . 33
Control box components for CH531/AdaptiView version AFDH . . . . . . . 34
Figure 15. D and E-Frame AFDH CH531/AdaptiView control box components . 34
Table 15. CH531/AdaptiView control box component part numbers . . . . . . . . 34
Additional hardware shipped with CH531/AdaptiView AFDH packages 35
Table 16. CH531/AdaptiView miscellaneous hardware package contents . . . . 35
Figure 16. Buss bars specifications; CH531/AdaptiView hardware packages . . . 35
Other AFDH drive package accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Figure 17. Floor stand kit parts for stand-mounted D-Frame AFDH. . . . . . . . . . 36
Figure 18. D and E-Frame floor-mounted AFDH; corner support kit parts . . . . . 37
Table 17. Part numbers for motor panel transition covers . . . . . . . . . . . . . . . 37
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Removal of electrical connections to the existing starter . . . . . . . . . . . . . . . 38
Mechanical removal of the existing unit-mounted starter . . . . . . . . . . . . . . 39
Mechanical removal of the existing remote-mounted starter . . . . . . . . . . . . 40
Mechanical installation of a Unit-Mounted AFDH drive . . . . . . . . . . . . . . . . . 40
Figure 19. Removal of Z-bracket weldment nuts . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 20. Position cabinet base over evaporator brackets and install clips . . . 42
Figure 21. Leveling the AFDH drive cabinet against the Z-bracket . . . . . . . . . . 42
Mechanical installation of a stand-mounted D-Frame AFDH . . . . . . . . . . . . 43
Figure 22. Assembly of floor stand kit components . . . . . . . . . . . . . . . . . . . . . 44
Figure 23. Attach assembled floor stand to drive unit. . . . . . . . . . . . . . . . . . . . 45
Mechanical installation of a remote floor-mounted AFDH . . . . . . . . . . . . . . 46
Figure 24. Assembly and installation of corner support kit components. . . . . . 47
Electrical installation (all AFDH models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Install shorting buss bars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Figure 25. Buss bar installation on compressor motor terminal board . . . . . . . 49
Input power wire installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Figure 26. Conduit shroud and two-piece incoming wire access cover . . . . . . . 50
Figure 27. Factory installed input disconnect circuit breaker . . . . . . . . . . . . . . 51
Grounding AFDH cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Figure 28. Location of AFDH cabinet ground terminal . . . . . . . . . . . . . . . . . . . 52
Output wiring from the AFDH to the CTV motor . . . . . . . . . . . . . . . . . . . 52

8AFDH-SVN01A-EN
Figure 29. Output wiring from AFDH to CTV motor . . . . . . . . . . . . . . . . . . . . . 53
Routing of control wiring to AFDH cabinet (all models) . . . . . . . . . . . . . . . . 54
Figure 30. Factory provided conduit holes in AFDH control box . . . . . . . . . . . . 54
Control wiring connections (UCP2 model AFDH only) . . . . . . . . . . . . . . . . . . 55
Figure 31. UCP2 wiring connections to 2X1 terminal strip in AFDH control box 55
Control wiring connections (CH531/AdaptiView model AFDH only) . . . . . . 56
Figure 32. CH531 wiring connections to 2X1 terminal strip in AFDH control box 56
AFDH drive program parameters used with all Trane controls . . . . . . . . . . 57
Table 18. Trane specific AFDH program parameters and settings . . . . . . . . . . 57
Required reprogramming of UCP2 controls . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Table 19. UCP2 menu parameters for proper chiller operation with AFDH . . . 58
Figure 33. AF PC Constant formula and sample calculation . . . . . . . . . . . . . . . 59
Required reprogramming of CH531 controls . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Table 20. CH531 CVR firmware parameter settings with a retrofit AFDH . . . . . 61
Table 21. CT meter scales for TechView or Tracer TU. . . . . . . . . . . . . . . . . . . 62
Required reprogramming of AdaptiView controls . . . . . . . . . . . . . . . . . . . . . 62
Reprogramming retrofit AdaptiView controls (CVR firmware) . . . . . . . . 62
Table 22. UC800/AdaptiView CVR parameter values with a retrofit AFDH . . . . 63
Reprogramming factory installed AdaptiView controls (CTV firmware) 64
Table 23. UC800/AdaptiView CTV parameter values with a retrofit AFDH . . . . 64

AFDH-SVN01A-EN 9
Unit Model
Number
For service purposes, Trane Model
AFDH Air-Cooled drive upgrade
packages are assigned a multiple
character alphanumeric model
number that precisely identifies each
unit.
An explanation of the identification
code that appears on the unit
nameplate is shown below. Use of the
service model number will enable the
owner/operator, installing
contractors, and service technicians
to define the operation, components,
and options for any specific unit.
Refer to the model number printed on
the nameplate when ordering
replacement parts or requesting
service.
Example model number:
AFDH0312FA0C10D1010
Digit 1, 2, 3, 4— Unit Model
A = Adaptive
F = Frequency
D = Drive
H = Design Sequence H
Digit 5, 6, 7, 8— Nameplate RLA
0312 = 312 Rated Load Amps
Digit 9— Voltage
F = 460 Volts/60 Hz/3 Phase
G = 480 Volts/60 Hz/3 Phase
Digit 10, 11— Design Sequence
A0) = Initial Design
Digit 12— Enclosure Type
C = Retrofit Standard Enclosure
Digit 13— Agency Listing
1 = UL (Underwriters Laboratory) & CSA
(Canadian Standards Association)
Digit 14— Harmonic Attenuation
0 = Standard Attenuation
1 = 414 Max RLA Line Reactor
2 = 643 Max RLA Line Reactor
3 = 500 Max RLA Line Reactor
4 = 1200 Max RLA Line Reactor
5 = 12 Pulse Autotransformer
Digit 15— VFD Frame Size
C = 302 Maximum RLA
D = 361 Maximum RLA
E = 443 Maximum RLA
G = 540 Maximum RLA
H = 590 Maximum RLA
J = 678 Maximum RLA
K = 730 Maximum RLA
Digit 16— Control Type
1 = UCP2
2 = CH531 / AdaptiView
Digit 17— Motor/Panel Transition
0 = None
A = 6-inch Transition
B = 18.5-inch Transition
C = 12-inch Transition
Digit 18— Mounting Type
1 = Unit Mount
2 = Floor Mount
3 = Remote Mount
Digit 19— Floor Mount Options
0 = None
A = Floor Mount Corner Brackets
B = Floor Mount Corner Brackets & Legs
Model Number Descriptions

AFDH-SVN01A-EN 10
Nameplates
A nameplate is installed on each AFDH Air-Cooled Drive unit. Always provide the model number
and serial number that is printed on this nameplate when making warranty inquiries, ordering
parts, or ordering literature for the unit
Figure 1. AFDH nameplate example

AFDH-SVN01A-EN 11
Nameplates
Note: This page has been intentionally left blank.

AFDH-SVN01A-EN 12
Pre-Installation
Confirming the AFDH package can be properly installed
This chapter details potential interference fit problems, mechanical incompatibility situations,
electrical code stipulations, and electrical conduit and wiring issues that can prevent the successful
installation and/or operation of an AFDH retrofit drive package.
Installation considerations for unit-mounted AFDH drives
Unit-mounted AFDH drives are incompatible with direct-mount starters
Certain chillers larger than 800 tons in size that were built after 2001, were equipped with direct-
mount starters. A direct-mount starter differs from a standard unit-mounted starter in that it is
bolted directly to the motor flanges and the motor terminal board is flush with the back of the starter
panel box. Refer to Figure 2.
A direct-mount starter also lacks the Z-brackets and transition cover that are an integral part of the
standard unit-mounted starter and which are also necessary for the correct installation of a unit-
mounted AFDH drive.
When a chiller that is equipped with a direct-mount starter is being upgraded with an AFDH retrofit
drive, the drive package must either be a stand-mounted or a remote floor-mounted version of the
AFDH.
Figure 2. Example of a direct-mount chiller starter panel
1. Motor terminal access in left-center quadrant of
cabinet. Motor terminal access in an AFDH drive
cabinet is located to the left in the upper third portion
of the cabinet
2. Compressor motor terminal board. Flush to back of
direct-mount starter cabinet
3. Hidden by direct-mount starter cabinet is the fact that
there are no Z-brackets available for mounting an
AFDH drive

AFDH-SVN01A-EN 13
Pre-Installation
Evaluate space available for rigging/installing unit-mounted AFDH
All models of the D-Frame and E-Frame AFDH unit-mounted retrofit drives are taller, wider, and
deeper than the typical Wye Delta unit-mounted starter they are intended to replace. Accordingly
any project should start with a careful evaluation on whether there is ample enough space to rig
the AFDH into place and if any of the existing building piping and conduit will not interfere with
its mounting.
NOTICE:
Route incoming power conduit to the roof of AFDH cabinet!
The air-cooled AFDH drive is designed to have the incoming power conduit routed vertically into
the unit through the removable conduit connection cover located on the left-hand rear corner of
the cabinet roof. If the starter that is being replaced by the AFDH drive has the incoming power
conduit routed horizontally across the top of the starter, or connected to the side or to the
bottom of the starter cabinet, an electrician will be required to reconfigure the conduit and
wiring. Routing the incoming power conduit into the AFDH cabinet anywhere other than
through the specified location on the cabinet roof, will be considered an unsupported field
modification to the cabinet design.
Important: NEC codes require that electrical disconnect switches can be no higher than 72
inches above the surface of the operator area floor or platform. Check the potential
mounted height of the AFDH disconnect switch, especially if the chiller has large
shells or is mounted on structural steel.
Important: Other factors that affect the space required to successfully install a stand-mounted
AFDH drive include the clearance distances specified by the local electrical codes.
Typical code regulations require an average of 36-inches clearance from the panel
to nonconducting surfaces and 47-inches to a conducting surface. Check and confirm
that when installed, the drive clearances will conform to all local codes. Do not forget
to account for cabinet door swing clearances.
Note: Refer to manual section “AFDH Drive Package Specifications,” p. 22 for the dimensions and
weights of all models of AFDH drives”
Figure 3. Comparison of unit-mounted AFDH to typical unit-mounted starter.
1. Typical Wye Delta unit-mounted starter (60
in. tall x 38 in. wide x 14 in. deep)
2. Unit-mounted D-Frame AFDH
superimposed over the outline of the unit-
mounted starter
3. Unit-mounted E-Frame AFDH
superimposed over the outline of the unit
mounted starter
4. Ensure sufficient overhead clearance space
is available for drive installation
5. Electrical disconnect switch for drive unit.
Note: Center of switch assembly is 24-
inches above the base of the cabinet. Refer
to Figure 8, p. 22 for D-Frame cabinets and
Figure 10, p. 24 for E-Frame cabinets

14 AFDH-SVN01A-EN
Pre-Installation
Installation considerations for stand-mounted AFDH
NOTICE:
Stand-mounted AFDH supported by equipment room floor!
A stand-mounted version of an AFDH drive is designed to be rigidly supported by the equipment
room floor. Therefore, a stand-mounted AFDH drive is not recommended for use with a chiller
that is equipped with spring-type vibration or seismic isolators. Trane recommends using a
remote floor-mounted AFDH drive in this application. Trane assumes no responsibility for
equipment damage caused by the installation of an AFDH drive version that is specified as being
incorrect for the application.
NOTICE:
Route incoming power conduit to the roof of AFDH cabinet!
The air-cooled AFDH drive is designed to have the incoming power conduit routed vertically into
the unit through the removable conduit connection cover located on the left-hand rear corner of
the cabinet roof. If the starter that is being replaced by the AFDH drive has the incoming power
conduit routed horizontally across the top of the starter, or connected to the side or to the
bottom of the starter cabinet, an electrician will be required to reconfigure the conduit and
wiring. Routing the incoming power conduit into the AFDH cabinet anywhere other than
through the specified location on the cabinet roof, will be considered an unsupported field
modification to the cabinet design.
Important: Other factors that affect the space required to successfully install a stand-mounted
AFDH drive include the clearance distances specified by the local electrical codes.
Typical code regulations require an average of 36-inches clearance from the panel
to nonconducting surfaces and 47-inches to a conducting surface. Check and confirm
that when installed, the drive clearances will conform to all local codes. Do not forget
to account for cabinet door swing clearances.
Important: The design intention of a stand-mounted AFDH drive, is for the drive to be installed
in front of the chiller with the motor terminal access cover of the drive cabinet lined
up with the compressor motor terminal box. The cable connections between the
drive and the motor terminals will be shrouded by an extended sheet-metal
transition cover. Refer to Figure 4.
Note: Refer to the manual section “AFDH Drive Package Specifications,” p. 22 for the dimensions
and weights of all models of AFDH drives”
Figure 4. Example of a stand-mounted version of an AFD drive
1. Example of a stand-mount AFD drive
2. Motor terminal access cover of drive lined up with
compressor motor terminal box. Cable connections
between drive and the motor terminals shrouded by
an extended sheet-metal transition cover

AFDH-SVN01A-EN 15
Pre-Installation
Installation considerations for remote floor-mounted AFDH
NOTICE:
Excessive cable lengths between AFDH drive and compressor motor!
The variable frequency drive industry recommends that the length of the electrical cables
connecting a drive unit to a motor should be kept to less than 50 feet to protect the motor from
reflected voltage waves that can cause the motor to fail. Cable lengths that exceed 50 feet
between the drive and the motor create the potential for damage to occur to the motor
windings and/or insulation. Trane assumes no responsibility for equipment damage caused by
use of improper cable lengths.
NOTICE:
Route incoming power conduit to the roof of the AFDH cabinet!
The air-cooled AFDH drive is designed to have the incoming power conduit routed vertically into
the unit through the removable conduit connection cover located on the left-hand rear corner of
the cabinet roof. If the starter that is being replaced by the AFDH drive has the incoming power
conduit routed horizontally across the top of the starter, or connected to the side or to the
bottom of the starter cabinet, an electrician will be required to reconfigure the conduit and
wiring. Routing the incoming power conduit into the AFDH cabinet anywhere other than
through the specified location on the cabinet roof, will be considered an unsupported field
modification to the cabinet design.
Important: Other factors that affect the space required to successfully install a remote floor-
mounted AFDH drive include the clearance distances specified by the local electrical
codes. Typical code regulations require an average of 36-inches clearance from the
panel to nonconducting surfaces and 47-inches to a conducting surface. Check and
confirm that when installed, the drive clearances will conform to all local codes. Do
not forget to account for cabinet door swing clearances.
Important: Plan the installation location of a remote floor-mounted AFDH drive to position it in
relation to the chiller compressor motor such that the maximum length of the cables
connecting the drive to the motor will not exceed 50 feet.
Note: Conduit connections to the AFDH for the power output wiring can be made either at the back
of the cabinet or on the top of the cabinet. Which of these options is chosen shall be at the
discretion of the installing electrician.
Note: Refer to the manual section “AFDH Drive Package Specifications,” p. 22 for the dimensions
and weights of all models of AFDH drives”

16 AFDH-SVN01A-EN
Pre-Installation
Confirm chiller controller system compatibility with AFDH drive
Before starting the process of installing the AFDH, first confirm that the existing chiller controller
system has the hardware and/or software components required to make it compatible with an
AFDH retrofit.
The controller systems that can accept an AFDH retrofit are:
• UCP2™ and UCP2 FastPak™ controller systems shipped after July 1994 (refer to UCP2 sub-
chapter that follows this bulleted list for more details).
Note: If a UCP2 FastPak™ control is equipped with a pulse type actuator, it must first be
upgraded to the current UCP2 style stepper actuator before installing the AFDH retrofit.
• Tracer™ CH531 retrofit control upgrade packages (all models).
Note: The factory installed Tracer™ CH530 chiller controller system will not support an AFDH
Air-Cooled Adaptive Frequency™ drive. The controller system must first be upgraded
to Tracer AdaptiView™ before an AFDH retrofit package can be installed.
• Tracer™ AdaptiView
Note: UC800 controller must be equipped with an AdaptiView software version released in
February 2009 or newer. Upload the correct AdaptiView software version as required.
UCP2 compatibility with AFDH drives
UCP2 chiller controller system history
• Prior to July 1994, UCP2™ and UCP2 FastPak™ controls did not have AFD compatible software
in their Chiller Modules or in their Clear Language Display Modules.
• Between July 1994 to June 1998 the first release of AFD compatible UCP2™ hardware/software
allowed a speed reduction down to as low as 42 Hz.
• In June 1998, the second version UCP2™ software release allowed speed reduction down to 38
Hz, which resulted in slightly improved energy savings.
AFDH compatible UCP2 hardware and software
To determine if a UCP2™ or UCP2 FastPak™ is equipped with hardware and software that will
accept an AFDH retrofit, refer to Table 1 and the instructions below:
1. Open the UCP2 door and record the X-code style part number printed on both the Chiller
Module and the Clear Language Display Module.
a. Compare these X-code numbers to the hardware part numbers listed in Table 1.
i. If the X-codes are equal to or greater than the hardware part numbers listed in Table 1
for each module type, then the modules are both hardware and software compatible with
an AFDH retrofit.
ii. If either (or both) X-codes are lower than the hardware part numbers listed in Table 1, the
module or modules have an unacceptable hardware part number for use with an AFDH
retrofit. Go to Step 2.
2. If the hardware X-code on a Chiller or a Clear Language Display module is unacceptable for use
with an AFDH retrofit, proceed to determine the revision level of the software contained within
each module before condemning it as being totally unusable. To determine the module
software’s AFDH compatibility, go to the UCP2 Clear Language Display and access the Module
Software Revision Levels menu found under the Service Tests group. Record the software
service part numbers displayed for both modules.
a. Compare these software service part numbers to the software part numbers listed in Table 1.
i. If these part numbers are equal to or greater than the software part numbers listed in
Table 1 for each module type, then these modules have previously received a service

AFDH-SVN01A-EN 17
Pre-Installation
retrofit and are actually compatible with an AFDH retrofit despite their root hardware part
number.
ii. If either (or both) these part numbers are lower that the software part numbers listed in
Table 1, the module or modules cannot be used with an AFDH drive. Purchase the
appropriate replacement modules through service parts.
Table 1. AFDH compatible UCP2 module hardware & software part numbers
Equipment room ambient temperature considerations
An air-conditioned equipment room is not a prerequisite for the installation and operation of an
AFDH retrofit drive package.
However, be advised that all models of the AFDH air-cooled drives are not suitable for installation
into equipment rooms where the ambient temperature conditions are expected to exceed either
95°F for a continuous 24-hour period, or where the potential maximum ambient temperatures can
exceed 104°F.
If the ambient temperatures exceed either of these conditions, the potential exists to trigger a drive
shut down from an over temperature fault - effectively disabling the chiller until the drive
temperature drops to the factory set, non-adjustable, safe temperature level that will allow the
drive to be restarted.
If the ambient temperatures routinely exceeds either of these conditions, the overall service life of
the drive may be compromised.
Chiller upgrades
• The chiller condenser loop setpoint should be set to 72°F to fully exploit the energy savings
possible with a retrofit AFDH drive.
• In some climates and applications, it may be beneficial to set the condenser loop setpoint even
lower, to 65°F.
Important: Under such low condenser water conditions, use of an oil recovery system is
recommended. These systems are found on all Trane chillers built since 1985. Refer
to general service bulletins CTV-SB-26 and CTV-SB-68 for upgrade information.
UCP2 Module Types (Capable
of Speed Reduction to 42 Hz) Hardware Part Number -
Extension Software Service Part Number -
Extension
Chiller Module X13650450-04 to 15 6200-0038-05 to 16
Clear Language Display Module X13650448-03 to 14 6200-0056-07 to 23
UCP2 Module Types (Capable
of Speed Reduction to 38 Hz) Hardware Part Number -
Extension Software Service Part Number -
Extension
Chiller Module X13650450-16 or higher 6200-0038-17 or higher
Clear Language Display Module X13650448-15 or higher 6200-0056-24 or higher

18 AFDH-SVN01A-EN
Pre-Installation
Electrical cable size specifications for AFDH drives
Table 2. Input/output power wire cable sizes AFDH D-Frame drives
Table 3. Input/output power wire cable sizes AFDH E-Frame drives
D-Frame AFDH 302 Amp Drive 361 Amp Drive 443 Amp Drive
INCOMING POWER TO DRIVE CIRCUIT
BREAKER:
Number of Cable Lugs Per Phase &
Range of Wire Sizes Lugs Will Accept
Two Wire Lugs
3/0 - 250KCMIL Three Wire Lugs
2/0 - 400KCMIL
Two Wire Lugs
250KCMIL -
500KCMIL
OUTPUT POWER TO COMPRESSOR
MOTOR:
Number of Wire Cables Per Phase &
Size of Factory Installed Wires
Two
3/0 Wires Two
4/0 Wires Two
250KCMIL Wires
E-Frame AFDH 540 Amp Drive 590 Amp Drive 678 Amp Drive 730 Amp Drive
INCOMING POWER TO DRIVE CIRCUIT
BREAKER:
Number of Cable Lugs per Phase &
Range of Wire Sizes Lugs Will Accept
Three Wire Lugs
2/0 - 400KCMIL Three Wire Lugs
2/0 - 400KCMIL Three Wire Lugs
2/0 - 400KCMIL Three Wire Lugs
2/0 - 400KCMIL
OUTPUT POWER TO COMPRESSOR
MOTOR:
Number of Wire Cables Per Phase &
Size of Factory Installed Wires
Three
4/0 Wires Three
250KCMIL Wires Three
350KCMIL Wires Three
350KCMIL Wires

AFDH-SVN01A-EN 19
Pre-Installation
Requirements for installation technicians
To properly install an AFDH Retrofit Adaptive Frequency™ Drive package, the technician must have
a good working knowledge of the centrifugal chiller controller system involved in the application.
Training is highly recommended before beginning this upgrade.
Tools required
Normal tools are required to perform the work. An HVAC service technician with a well stocked tool
chest should already have the majority of the normal tools needed for this job.
In addition to the normally carried service tools and hardware, the following is a partial list of
specific field supplied hardware and software components and special tools that will also be
required to perform the drive retrofit:
•The appropriate lifting device or devices (including all necessary rigging hardware) with the
capacity to safely lift up to 1500 lbs.
– Important! A spreader bar will be required if the drive unit will be hoisted into position
using a single lifting device that is capable of making only a single-point lift.
•A PC or laptop computer equipped with the correct software tools for the chiller controller
involved in the application.
– TechView™ or KestrelView™service software version 11.0 with service pack (SP) 3 or
newer.
– Tracer™ TU service software version 2.01.020 or newer.
Note: The most current CTV and CVR microprocessor (MP) firmware files are included with the
program files for the TechView™, KestrelView™, and Tracer™ TU service software tools.
•Type A to Type B USB cable to connect the computer to a Tracer™ UC800 controller
•An RS-232 male DB9 to female DB9 pin to pin serial cable connect the computer to a
DynaView™ display
– Important! The cable must not be a “null-modem” cable.
– Important! The cable must be less than 50 feet in length.
– The Radio Shack ® part number for a proper cable is 26-117B.
•South pole magnet screwdriver (TOL01343).
Miscellaneous field provided material
Some field provided material will be required to perform the drive retrofit. A partial list of material
is provided here to help the technician to plan ahead and to avoid material shortages at the job site.
•Self-adhesive cable tie mounting bases and cable ties.
– Used to help “clean up” wiring runs during the installation process.
•Loctite® 554 thread sealant for refrigerant applications (Trane part number SEL00528).
– Used in applications where a pressure transducer needs to be installed.

20 AFDH-SVN01A-EN
Pre-Installation
Recommended rigging and lifting procedures for AFDH drive units
WARNING
Heavy Objects!
Only attach cables (chains or slings) to the designated lifting points. Each of the cables (chains
or slings) used to lift the unit must be capable of supporting the entire weight of the unit. Lifting
cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.
Other lifting arrangements could cause equipment or property-only damage. Failure to properly
lift unit could result in death or serious injury.
WARNING
Improper Unit Lift!
An AFDH cabinet assembly is top heavy. Test lift unit to an approximate height of no greater
than 24 inches to verify proper center of gravity lift point. To avoid dropping the unit, reposition
lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury
or possible equipment or property only damage.
Unit lifting points
1. Factory provided unit lift tabs
2. AFDH D-Frame Unit front-to-rear center of gravity
3. AFDH E-Frame Unit front-to-rear center of gravity
4. Frequency drive module section of the cabinet assembly. Weight of drive module can result in
the unit attempting to lean to the right as it is lifted if the rigging is not adjusted correctly
Figure 5. Unit lifting points and center of gravity
Other manuals for CVHE
8
This manual suits for next models
2
Table of contents
Other Trane DC Drive manuals

Trane
Trane TR200 Series User manual

Trane
Trane Liquid-Cooled Adaptive Frequency AFDE Installation and operating instructions

Trane
Trane TR200 Series Manual

Trane
Trane TR150 User manual

Trane
Trane LonWorks TR1 Series VFD User manual

Trane
Trane TR150 User manual

Trane
Trane TR150 Operating instructions

Trane
Trane VLT AQUA Drive FC 202 VLT AutomationDrive FC... User manual

Trane
Trane TR200 Series Operating instructions

Trane
Trane TR1 6002-6004 User manual