SUMMARY OF ALERT CODE & CHARGE ASSISTTM LEDS
Charge Assist™ (CA) Procedure for a NON-Communicating
24VAC Control System
STEP 3:
Press the mode button on the CA board and follow the CA
procedures starting with STEP 1 in the Communicating
Comfort Control Section above.
STEP 4:
After the CA control exits the CA mode CYCLE, the tech-
nician must then return the
NON-COMMUNICATING 24 volt indoor CONTROL to the
desired customer setting.
STEP 1:
Outdoor units coupled with 24 volt indoor units (outdoor
units require BAYACHP024* for 24V operation) require the
technician to set up the Variable Speed (VS) Air Handler
or VS Furnace with the DIP switches for the size of the
equipment installed. (Unit tonnage, CFM per ton 350,
400, 450 required, the blower delays and Heating airflow)
CA cycle is compatible with ENHANCED Mode.
STEP 2:
A technician must set the indoor system control to call for
the SECOND STAGE of COOLING. The indoor CON-
TROL must be set low enough to ensure the system
continues to run in SECOND STAGE of COOLING
throughout the CA mode cycle. The CA control will exit
the CA mode CYCLE if the system control does not stay
in the SECOND STAGE cooling cycle. (The CA Control
must see 24 Volts AC call on both Y1 and Y2.)
LED
Colo
Fault LED Alert
Code Description Control
Displa
LED
Colo
Description
90 Excessive Communication Errors N/A Flashing See Charging Flash Rate
Loss of Heat/Cool Demand Message
(COMM) Off Charged or not in CA Mode
Loss of Bit Master (Clock Signal) On Charge is Correct
2 Flash Defrost Fault A
1On 1st stage compressor requests
3 Flash Defrost Fault B and/or C
2On 2nd stage compressor request
4 Flash Defrost Fault A and [B and/or C] Fast Flash Initialization at Power Up ~ 60 seconds
5 Flash Ambient Temperature Sensor Fault
(Out of Range - Open or Shorted) Med Flash Oil Return Mode ** (Forced Defrost)
6 Flash Coil Temperature Sensor Fault
(Out of Range - Open or Shorted) Slow Flash Standard operation
Low Pressure Cut Out Fault (Open
outside of defrost Cycle-Hard lock out, cycle
power to reset)
Off Charge Assist™ mode or no power to control
Low Pressure Cut Out Fault
Heat/Cool Lock out LitePort Occasional Flash For transmitting LitePort TM data
Low Pressure Cut Out Fault (Open
outside of defrost Cycle-Short lock out) Wait ¤ Flashing
Flash device count when in communication
(number of COMM products connected in system);
Rapid flashes followed by a pause indicates
disrupted communications
10 Flash 102 Y2 without Y1 - Miswire
(24 volt mode only) N/A Off No power
11 Flash 67 Liquid Temperature Sensor Fault
(Out of Range - Open or Shorted) N/A On Solid at power-up
12 Flash 113 Liquid Pressure Sensor Fault
(Out of Range - Open or Shorted) ERR 113 Flashing See Stabilization Flash Rate
13 Flash 67
External Outdoor Temperature
Sensor Fault
(Out of Range - Shorted)
N/A Off Not in CA Mode
PM Missing with local copy
(Operational) ERR 114 ADD On System requires refrigerant charge
(Control has 24 volt AC output to Charge Solenoid)
Bad Data in PM with local copy
(Operational) N/A
Ambient Temperature is out of range -
Ambient Temperature must be above 55°F
and below 120°F to enter CA Mode
Bad Data in PM no local copy
(Not Operational)
Note: ODT LED will flash 1 sec ON/OFF for 30
seconds and the CHARGING LED will flash 5 times per
second for 2 seconds, then exit CA.
PM Missing with no local copy
(Not Operational) RECOVER On
Need to recover refrigerant - Unit locked out
for 1 hour or press mode button to exit
Charge Assist™
15 Flash * 50 Duplicate OD Temperature Sensor * N/A
Liquid pressure below 90 psig - Liquid
pressure must be above 90 psig to enter CA
Mode
16 Flash * 123 Demand Configuration Fault * N/A
Note: LOW pressure LED will be on for 30 seconds
and the CHARGING LED will flash 5 times per second
for 2 seconds, then exit CA.
High Presure Monitor Fault
(Hard lock out, cycle power to reset) ERR 80 Notes: ** Used with 20 SEER Models
High Presure Monitor Fault
(Short lock out) Wait ¤
18 Flash 18 24V Sensing Error (24V Missing at Y1) ERR 18
N/A
ERR 79
ERR 67
Green
Charge Assist™ (CA) LEDs
Red
Notes:
On
Flashing
ERR 91
4 highest priority Faults display flash codes sequentially. 2 second pause between faults and 4 second pause between sequences. Cycle power to ODU to clear Faults.
* Alert flash code will not be implemented for initial release
¤ Wait icon will appear on the Comfort Control during: Equipment minimum off time, Charge Assist
TM, Short lock out (see Alert Codes "7 Flash" & "17 Flash")
CHARGED
17 Flash 80
LOW
ODT
Red
14 Flash 114
Amber
7 Flash 79
STATUS
COM
91
1 Flash
67
68
ERR 114
CHARGING
Printed from D802247P01 Rev08