TRIATEK FMS-1655L User manual

FMS-1655L
Installation Manual
Version: 03.27.17
Triatek FMS-1655L

FMS-1655L
Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
- 2 -
CONTROLLER SETTINGS
This form should be completed during the initial configuration for each room pressure controller.
Room Name / Number
Unit Model Number and Serial Number (ESN)
Analog Input
Normal Operating Pressure (reading with door closed)
Positive Isolation Setpoint
Negative Isolation Setpoint
Neutral Isolation Setpoint
Pressure Deadband
Analog Output
Analog Output Range (zero-based or offset)
Analog Output Upper Limit (0 – 100%)
Analog Output Lower Limit (0 – 100%)
Analog Output Action (Direct or Reverse)
PID Constants
Proportional Constant (0.5 – 100.0 %)
Integral Constant (0.0 – 100.0 %)
Derivative Constant (0.0 – 100.0 %)
Alarm Limits
Positive Isolation High Alarm Setpoint
Positive Isolation High Warning Setpoint
Positive Isolation Low Warning Setpoint
Positive Isolation Low Alarm Setpoint
Negative Isolation High Alarm Setpoint
Negative Isolation High Warning Setpoint
Negative Isolation Low Warning Setpoint
Negative Isolation Low Alarm Setpoint

FMS-1655L
Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
- 3-
CONTROLLER SETTINGS
Audible Alert
Operating Mode (audible or silent)
Delay Time Base (secs or mins)
Delay Setting (0 – 60)
Engineering Units
Inches of Water or Pascals

Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
FMS-1655L
FAST ACTING
ELECTRONIC ACTUATOR
Controller Actuator
120/24VAC, 30Va Transformer
Supplied by Triatek
120/24VAC, 20Va Third Party
Transformer
CORRECT
CORRECT
Triatek reserves the right to change product specifications without notice.
Warning
Failure to follow the wiring diagrams could result in damage to your
equipment and could void your warranty.
Under no circumstances should a single transformer be split between an actuator and controller. Doing so
will damage the actuator, the transformer, the controller, or all units. A single 120/24V/30Va transformer is
required for the controller and a separate 120/24V/20Va transformer is required for the actuator.
WARNING
- 4 -

FMS-1655L
GENERAL
Specifications……………………………………………………………………………………………………………………………..6
Overview………………………………………………………………………………………………………………………………......7
MOUNTING/WIRING
FMS-1655L Surface Mount Case Dimensions……………………......………………………………………………………………… 8
FMS-1655L Flush Mount Display Dimensions…………………...…………………………………………………………………… 9
FMS-1655L Surface Mount Display Dimensions……………………………………………….......……………………………....10 - 11
Remote Sensor Installation………………………………………………………........……….....………………………………....12 - 14
Remote Sensor Connector Strip…………………………………………………………………………………………………………15
Function Descriptions……………………………………………………………………………………………………………………...16
Analog Output to Modulated Air Controller ……………………………………………………………………………………………17
Analog Input to Remote Pressure Sensor - 4-20mA Out……………………………………………………………………………18
Analog Input to 2 Remote Pressure Sensors - 4-20mA Out…………………………………………………………………………19
Adding Input to Temperature Sensor……………………………………………………………………………………………………20
Digital Input to Door Switch………………………………………………………………………………………………………………21
Digital Input to Flow Switch………………………………………………………………………………………………………………22
Digital Input to Occupancy Sensor………………………………………………………………………………………………………23
Relay Output to Alarm…………………………………………………………………………………………………………………….24
Relay Output to Warning………………………………………………………………………………………………………………….25
RelayOutput1…………………………………………………………………………………………………………………………….....26
Power……………………………………………………………………………………………………………………………………….27
Isolated Power Supply ……………………………………………………………………………………………………………………..28
COMMUNICATIONS / WIRING…………………………………..................……………………………………………………………..… 29-30
FMS-1655L PROGRAMMING
Introduction…………………………………………………………..........…………………………………………...................31
Main Display Screen…………………………………………....................…………………………………………………………......31
Configuring Isolation Room Controller………………………….................……………………………………..…………………......32
Configuring Alarm Limits……..................…………………………………………………………………..……………….................32
Set Target Setpoints……………………………………………………………...............………………………...…............................32
Setting Up the Analog Output……....................……………………………………………………………………………………......32
Changing the Isolation Mode…….........…….….........……………………………………………………………………………….....33
Adding Password Security………….......................……………………………………………………………………………………33
Changing Display Settings…………...…….....................………………………………………………………………………………33
Built-In Diagnostics…………………………........…..........………………………………………………………....……………………33
MODULE SETTINGS……………………………………………………………………………………………................................................35 - 36
CLEANING THE DISPLAY……………………………………………………………………………………………………………….................37
FLOW DIAGRAMS………………………………………………………………………………………………………….................................38-40
Triatek reserves the right to change product specifications without notice.
- 5 -
TABLE OF CONTENTS

Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
FMS-1655L
Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
Electrical
4 Analog Inputs....…………………………………………………………………………………………………………………4-20mAdc, 0-5Vdc or 0-10Vdc
4 Analog Outputs......………………………………………………………………………………………………………………………… 0-5Vdc or 0-10Vdc
4 Digital Inputs.....………………………………………………………………………………………………0-5Vdc or 0-24Vdc, Active-High or Active-Low
4RelayOutputs………………………………………………………………………………………………………………………………………1A@24Vdc/AC
Input Impedance………………………………………………………………………………….............………0-5V = 100K, 0-10V = 16K, 4-20ma = 249 Ω
Output Impedance…………………………………………………………………………………………………………………………………...........……75 Ω
Power Supply……………………… Class 2, 24VAC/DC ±10%, 30VA, universal 120/240 to 24 VAC, 60/50 Hz, step-down isolation transformer provided
Communications
LonWorks® FTT-10A peer-to-peer network...………………………………………………………………………Two-Wire Twisted Pair, FTT-10A signaling
Recommended Cable Type......……………………………………………………………………………………… Connect-Air W221p-2001 or Equivalent
Touchscreen User Interface
LCD Size…......…………………………………………………………………………………………………………………………………………3.2” diagonal
LCD Type......……………………………………………………………………………………………………………………………………………Transmissive
Resolution………………………………………………………………………………………………………………………………………240 x 320 portrait
Viewing Area....……………………………………………………………………………………………………………………………50.60 mm x 66.80 mm
Color Depth...…………………………………………………………………………………………………………………………………18-bit or 262K colors
Backlight Color.....………………………………………………………………………………………………………………………………………………White
Luminous Intensity....………………………………………………………………………………………………………………………………min 2500 cd/m2
Mechanical
FMS-1655L Display Module Housing (Surface Mount)……………………………………………………………………………………3”W x 5”H x 1.13”D
FMS-1655L Display Module Housing (Flush Mount)…………………………………………………………………………………5.6”W x 8.5”H x 0.75”D
FMS-1655L Controller Housing…………………………………………………………………………………………………………4.6”W x 6.6”H x 1.9”D
Environmental
Operating Temperature………………………………………………………………………………………………………………......32° to 125° F Operating
Operating Humidity…………………………………………………………………………………………………………....10% - 95% RH, Non-condensing
Venturi Valve (Order Separately)
Diameter……………………………………………………………………………………………………………………..................….8”, 10”, 12”, 14” O.D.
CFM Range………………………………………………………………………………………………………………………………………………....35-2100
Materials…………………………………………………………………………………………………………...Aluminum, Stainless Steel, Heresite Coating
Insulation…………………………………………………………………………………………………………………………………….....……Optional
Actuation…………………………………………………………………………………………………………………………………...Electronic or Pneumatic
GENERAL
Specifications
Triatek reserves the right to change product specifications without notice.
FMS1655L --0-
Case Style
T = thin (flush)
S = surface
# of Remote Sensors
1 = single sensor
2 = dual sensor
Part Number Guide
- 6 -

FMS-1655L
Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
GENERAL
Overview
Triatek reserves the right to change product specifications without notice.
The Triatek FMS-1655L Room Pressure
Controller is an ultra-sensitive instrument
used to control and/or monitor air pressure
in hospital rooms, labs, and clean rooms. It
is capable of measuring and displaying air
pressures down to 0.0001” wc.
Features include:
• Digital display of pressure with a
programmable description
• Full-color touchscreen with audible and
visual alarms
• Patent-pending Safety Halo™ with 180°
edge lighting
• Four relay outputs for transmitting alarm
conditions to a remote location such as a
central monitoring station
• Auxiliary analog inputs for use with
optional sensors
• Analog outputs used in control
applications
• Dual sensor split screen viewing mode
• Password protection of programmed
setup
• Optional keylock switch for isolation
select protection
• Comprehensive real-rime diagnostics
tool built into each unit
The FMS-1655L has enhanced graphics and
Saftey Halo™ edge lighting that provides a full
180° of status visibility. The product is shipped
with the Safety HaloTM at full brightness, but
may be dimmed or even disabled completely
using the Display Setup menu.
Bright graphical color changes are used
to indicate the three different statuses
of the monitored space. These graphical
backgrounds indicate Normal when the room
pressure is within defined limits, Warning
when the room pressure is approaching
an out-of-limits condition, and Alarm when
the room pressure is outside the defined
acceptable and safe limits.
The room pressure ranges are configured
by the user, either directly from the display
or over the network from the building
management system (BMS). Room pressure
selection of positive, negative, or no isolation
is set using the user menu or an optional
keylock switch.
Alarm conditions are defined by the user
in terms of desired pressure settings for
the room being monitored. When an alarm
condition occurs, it can be annunciated
in four ways: 1) on the display, 2) with an
audible alarm, 3) transmitted via contacts
to a remote monitoring station, and 4) over
the LonWorks®network. The alarm will
automatically reset when the unit senses that
room pressure has returned to proper limits,
or the attendant can mute the audible alarm
by touching the Alarm Audible button at the
bottom of the screen.
The FMS-1655L provides four relay outputs
that can be used for remote alarms or pilot
control functions. The operation of each relay
can be configured to trigger on defined control
functions of the FMS-1655L, except for Relay
2, which is reserved for the display power
control.
It is often important to have room variables
such as temperature or relative humidity
displayed along with the room pressure.
These variables can be enabled or disabled
by the user in the Display Setup menu.
The FMS-1655L provides additional analog
inputs which can be configured for 4-20 ma
current or for voltage input signals. The input
can be scaled as needed to display correct
values, and a suitable description can be
applied.
The FMS-1655L provides analog outputs
which can be set up for 0-5v or 0-10v output.
It can be programmed to be a proportional
output for providing a linear signal to an
automation system, or programmed for a
PID floating point output for direct control of
damper actuators, speed drives, etc.
When configured for dual sensor mode (see
page 35), the FMS-1655L can monitor a
secondary pressure and display its real time
measurement on the screen along
with the primary pressure in a split screen
view (see Figure 4). This secondary
monitored pressure reading has no alarming
capabilities and is for display purposes
only. The Safety Halo™ edge lighting
continuously displays the alarm status of the
primary channel, and is not affected by the
secondary channel.
The user can set multiple access level
passwords to protect against unauthorized
access to the FMS-1655L.
The FMS-1655L provides built-in diagnostic
tools for troubleshooting during installation,
including manual override capabilities and
a comprehensive real-time view that allows
the real-time values and states of each
analog and digital input and output to be
conveniently displayed. This tool facilitates
the verification and certification processes
conducted by test and balance personnel
during commissioning. There are also options
for storing configuration settings and for
restoring those settings, as well as performing
a complete restoration of the factory default
configuration settings.
- 7 -

Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
FMS-1655L
- 8-
FMS-1655L Surface Mount Case Dimensions
Triatek reserves the right to change product specifications without notice.
3"
5"
3/4
"
3/4
"
®
PWR LED
— + GND +V
Right Side
View
Left Angle
Side View
Control Unit
Adapter
(Inside Control Unit)
1.13”
Cable provided terminated at
control unit

FMS-1655L Flush Mount Display Dimensions
FMS-1655L
- 9 -
MOUNTING/WIRING
Triatek reserves the right to change product specifications without notice.
The FMS-1655L Flush Mount display is mounted flushed to the wall using the supplied retro fit ring or wall box.
Use the retro fit ring as a template to mark the wall for cutout.

Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
SUBHEAD
FMS-1655L
Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
- 10 -
MOUNTING/WIRING
FMS-1655L Surface Mount Display
Triatek reserves the right to change product specifications without notice.
The FMS-1655L display backplate may be mounted directly to a standard single-gang wall
box using the two slots along the centerline. Use the backplate as a template to mark the
mounting holes and the cable access hole at the center of the backplate.
3.04”
5.05”
ø 0.143”
ø 0.143”
ø 0.750”

Controller Mounting Hole Patterns
FMS-1655L
- 11 -
MOUNTING/WIRING
Triatek reserves the right to change product specifications without notice.

Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
FMS-1655L Room Pressure Controllers
ordered with a remote sensor must be installed
in the wall between the isolation room and the
adjoining corridor. Port P1 must be oriented
towards the isolation room and Port P2 toward
the corridor. Please see illustration on page 13.
With this sensor orientation, a positive
pressure value indicates that the isolation
room is positive with respect to the corridor.
NOTE: A three conductor cable must be
connected between the remote sensor and
the FMS-1655L. Maximum length of this
cable is 1,000 feet.
The display unit can be installed outside the
room, at the nurses station, in the engineering
office, or at any other location as needed.
Mounting Steps:
1. Cut an opening in the wall of the isolation
room for the single-gang low voltage
bracket and remote sensor electronics.
Nominal hole dimensions are 3.65” H x
2.15” W.
2. Drill a 16” hole through the opposite wall
for the flow tube as shown.
3. Bring the 3-conductor signal wire through
the cut-out.
4. Install the single-gang low voltage
mounting bracket in the cutout. Route a
length of supplied flow tube through the
mounting bracket and through the 7/16”
hole in the opposite wall.
5. Push a length of 3-conductor cable
from the FMS-1655L controller down
wall to the opening of the single-gang
low voltage mounting bracket. Connect
cable wires to +Vin, GND, and IO at the
sensor’s 9 pin connector.
6. Attach the flow tube to the sensor port,
then push the tube and sensor module
into place and secure to the mounting
enclosure with two 6-32 x 3/4 screws
supplied.
7. Install the louvered cover plate.
8. On the opposite side (corridor) attach the
flow tube to the barbed fitting of the flow
tube mounting plate.
9. Press the mounting plate into place,
allowing the excess tube length to go into
the wall space. Secure with the screws
and anchors.
10. Install the louvered cover plate.
11. At the FMS-1655L controller, connect the
three leads from the remote sensor to
the terminals marked +V, AI_1, and GND.
Remote sensor +Vin goes to terminal
+V, remote sensor IO goes to terminal
AI_1, and remote sensor GND goes to
controller GND.
Install jumper on pin 1 JP6 and JP3 see
diagram on page 15 (If not installed at the
factory).
12. If configured for dual sensor mode, repeat
steps 1 through 10 for the secondary
remote sensor and proceed to step 13.
13. At the FMS-1655L controller, connect the
three leads from the secondary remote
sensor to the terminals marked +V, AI_2,
and GND. Remote sensor +Vin goes to
terminal +V, remote sensor IO goes to
terminal AI_2, and remote sensor GND
goes to controller GND.
Mounting/Wiring
Remote Sensor Installation
FMS-1655L
- 12 -
Triatek reserves the right to change product specifications without notice.

Mounting/Wiring
Remote Sensor Installation
FMS-1655L
- 13 -
Triatek reserves the right to change product specifications without notice.
NC
NC
GND
NC
NC
Io
NC
GND
+Vin
~
~
Remote Sensor Installation
(Side View)
ISOLATION
ROOM
CORRIDOR
Stainless Steel
Mounting Plate
Gasket
Louvered Cover
Plate
Stainless Steel
Flow Tube
Mounting Plate Gasket
Thin Silicone Caulking
(apply around tube and between
stainless steel plate and wall to seal
unit)
Terminal
For connection of transmitter to
FMS-1655L
Flow Tube
When Flow Tube mounting plate
is located directly opposite the
sensor, flow tubing must be cut as
short as possible to prevent kinks.
To FMS Controller
Wall Section
(cutaway view)
Orange wall bracket
to be installed first
by using the rotating
clamps for secure
wall attachment.

Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
Mounting/Wiring
Remote Sensor Installation
FMS-1655L
- 14 -
Triatek reserves the right to change product specifications without notice.
NC
NC
GND
NC
NC
Io
NC
GND
+Vin
~
~
Remote Sensor Installation
(Bottom View)
ISOLATION
ROOM
CORRIDOR Stainless Steel
Mounting Plate
Gasket Louvered Cover
Plate
Stainless Steel
Flow Tube
Mounting Plate
Gasket
Thin Silicone Caulking
(apply around tube and
between stainless steel
plate and wall to seal unit
penetration)
Terminal
For connection of
transmitter to
FMS-1655L
Flow Tube
When Flow Tube mounting plate
is located directly opposite the
sensor, flow tubing must be cut as
short as possible to prevent kinks.
To FMS
Controller
Wall Section
(cutaway view)
Rotating clamps secure
assembly to wall board

Mounting / Wiring
Remote Sensor Connector Strip
FMS-1655L
- 15 -
Triatek reserves the right to change product specifications without notice.
AO_1
AO_2
AO_3
AO_4
AI_1
AI_2
AI_3
AI_4
GND
GND
+10v
+V
ANALOG IN
NT_1
NT_2
NETWRK OUT
DI_1
DI_2
DI_4
GND
GND
GND
PH1
PH2
+VS
SYN
-
IN
SASH SNSR
DIGITAL IN
RLY1
RLY2
RLY3
RLY4
C3/4
C2
C1
RELAY OUTPUTS
SHLD
DI_3
1
2
3
EXT.SNSR
SELECT
INT.SNSR
G
5v
+V
DI
EXT.
SNSR
FLASH_WP
+5v
GND
GND
GND
GND
1
SHLD
NETWRK IN
NT_2
NT_1
AUX PWR OUTPUT
ANALOG OUT
Vsel
RNG
4
1
2
3
1
LED
Ain
Aout
JP4
1
2
JP5
4
RNG
1
mA 3
LED4
JP7
Ain
1
JP6
JP3
JP2
1
1
1
1
1
1
1
NT
_1
NT_2
NETWRK
OU
T
D
I_
1
DI
_2
D
I
_4
G
N
D
G
N
D
G
N
D
PH
1
PH
2
+V
S
S
YN
-
IN
S
A
S
H
S
N
S
R
D
I
G
ITAL I
N
RLY1
RLY
2
RLY
3
RLY
4
C
3
/4
C2
C
1
RELAY
OU
TP
U
T
S
S
HL
D
D
I
_
3
1
2
3
INT
.S
N
SR
G
5
v
+
V
DI
FLASH_WP
S
HL
D
NETWRK IN
NT_2
NT_1
V
s
e
l
R
N
G
4
1
2
3
LE
D
A
in
A
ou
t
J
P4
J
P
5
R
N
G
m
A
LED
4
J
P7
A
i
n
JP3
JP2
FLA
FLA
1
1
1
NC
No Connection to Field Wiring
Field Wiring w/space for Number
Internal Wiring
Screw Terminal
Wiring Guide Legend
Symbol Description
Air Flow To and From Unit
Between Room and Corridor
Remote
Sensor/
Transmitter
GND
Io
+Vin
The electrical connections to the FMS-1655L are made via
a convenient removable terminal block as shown below. All
wiring should conform to the local regulations and National
Electrical Code.
Take care not to run sensor wiring in the same conduit as
line voltage or other conductors that supply highly inductive
loads such as generators, motors, solenoids, contactors,
etc. Use 22 AWG or larger.
Removable
Connector
for easy installation
of field wiring.
Remote Sensor
Connector

Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
Mounting / Wiring
Function Descriptions
FMS-1655L
- 16 -
Triatek reserves the right to change product specifications without notice.
Function Description
AUX Power Output Power supply outputs used for power auxiliary devices. Each is supply limited to 100
ma.
LON Communications LON FTT-10A Free Topology Network building automation system can access the
status and the configuration of the unit. Also used by configuration software to
configure unit.
Analog Output Unit has 4 analog outputs which can be configured for 0-5 VDC or 0-10VDC.
Analog Input Unit has 4 analog inputs which can be configured for 4-20 mA, 0-5VDC, or 0-10VDC.
Power The FMS-1655L can be powered by either 24 VAC or 24 VDC. A 120 VAC to 24 VAC
Step Down Isolation Transformer is provided and recommended. This power must be
from a Class 2 supply only.
Digital Input The unit has 4 digital inputs with selectable pull-up voltages of 0V, +5V and +20V.
Relay Output The unit has 4 SPDT relay outputs with normally open contacts.

Mounting / Wiring Remote Sensor
Analog Output to Modulated Air Controller
FMS-1655L
- 17 -
Triatek reserves the right to change product specifications without notice.
AO_1
AO_2
AO_3
AO_4
AI_1
AI_2
AI_3
AI_4
GND
GND
+10v
+V
ANALOG IN
NT_1
NT_2
NETWRK OUT
DI_1
DI_2
DI_4
GND
GND
GND
PH1
PH2
+VS
SYN
-
IN
SASH SNSR
DIGITAL IN
RLY1
RLY2
RLY3
RLY4
C3/4
C2
C1
RELAY OUTPUTS
SHLD
DI_3
1
2
3
EXT.SNSR
SELECT
INT.SNSR
G
5v
+V
DI
SRVC
EXT.
SNSR
FLASH_WP
+5v
GND
GND
GND
GND
1
SHLD
NETWRK IN
NT_2
NT_1
AUX PWR OUTPUT
ANALOG OUT
Vsel
RNG
4
1
2
3
1
LED
Ain
Aout
JP4
1
2
JP5
4
RNG
1
mA 3
LED3
LED4
JP7
1
JP6
JP3
1
1
1
1
1
1
1
NC
No Connection to Field Wiring
Field Wiring w/space for Number
Internal Wiring
Screw Terminal
Wiring Guide Legend
Symbol Description
Air Flow To and From Unit
Between Room and Corridor
CONNECTIONS FOR POWERED OUTPUT
+
10v
+
V
NT_1
NT_
2
NETWRK
OU
T
DI
_1
D
I_
2
D
I_4
G
N
D
G
ND
G
ND
P
H1
PH2
+VS
SY
N
-
IN
S
A
S
H
S
N
S
R
D
I
G
ITAL IN
R
LY1
RLY2
RLY3
RLY
4
C
3
/4
C2
C1
RELAY OUTPUT
S
S
HL
D
D
I
_3
1
2
3
SELECT
I
NT
.S
N
SR
G
5v
+
V
DI
S
RV
C
FLASH_WP
+
5v
G
ND
G
N
D
G
N
D
S
HL
D
NETWRK I
N
NT
_
2
NT
_
1
AUX PWR
O
UTPU
T
V
se
l
R
N
G
4
1
2
3
LE
D
A
out
J
P
4
J
P
5
R
N
G
LED
3
LED
4
J
P7
JP3
1
1
1
~
~
-
+
Air
Control
Modulator
+
-
+
-
Optional External
Transmitter
Power Supply
0-5v (JP7)
Jumper Setting
AI 1
AI 2
AI 3
AI 4
1
2
3
4
= JUMPER ON
Analog Input
0-10v (JP7)
AI 1
AI 2
AI 3
AI 4
JP7
1
2
3
4
Analog Input
4-20mA (JP6)
AI 1
AI 2
AI 3
AI 4
Analog Input
JP6
0-5v (JP5)
AO 1
AO 2
AO 3
AO 4
Analog Output
0-10v (JP5)
AO 1
AO 2
AO 3
AO 4
JP5
Analog Output
Note: 4-20mA can only be used if the
corresponding JP7 Analog Input Jumper
is set to OFF.
Note: Each Analog Input or Output value can be set independent of one another.
Example:
AI 1 can be set to 0-5v jumper OFF (JP7 PIN 1)
AI 2 can be set to 0-10v jumper ON (JP7 PIN 2)
AI 3 can be set to 4-20mA jumper ON (JP6 PIN 3) and jumper OFF (JP7 PIN 3)
AO 1 can be set to 0-10v jumper ON (JP5 PIN 1)
AO 2 0-5v can be set to 0-5v jumper OFF (JP5 PIN 2)
= JUMPER OFF
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
Purchased Separately
Purchased Separately
4-20mA Loop

Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
Mounting / Wiring
Analog Input to Remote Pressure Sensor - 4-20mA Out
FMS-1655L
- 18 -
Triatek reserves the right to change product specifications without notice.
AO_1
AO_2
AO_3
AO_4
AI_1
AI_2
AI_3
AI_4
GND
GND
+10v
+V
ANALOG IN
NT_1
NT_2
NETWRK OUT
DI_1
DI_2
DI_4
GND
GND
GND
PH1
PH2
+VS
SYN
24V IN
SASH SNSR
DIGITAL IN
RLY1
RLY2
RLY3
RLY4
C3/4
C2
C1
RELAY OUTPUTS
SHLD
DI_3
EXT.SNSR
SELECT
INT.SNSR
5v
+V
DI
SRVC
EXT.
SNSR
FLASH_WP
+5v
GND
GND
GND
GND
1
SHLD
NETWRK IN
NT_2
AUX PWR OUTPUT
ANALOG OUT
Vsel
RNG
LED1
1
LED
Aout
LED2
JP4
1
2
JP5
4
RNG
1
mA 3
JP7
Ain
1
JP6
LED1
JP3
LED2
1
1
1
1
1
1
NT_1
NT
_2
NETWRK
OUT
D
I_
1
D
I_
2
D
I_
4
G
N
D
G
N
D
G
N
D
PH
1
PH2
+V
S
S
YN
24
V
IN
S
A
S
H
S
N
SR
D
I
G
ITAL I
N
RLY
1
R
LY
2
RLY
3
R
LY
4
C3
/4
C
2
C
1
RELAY
O
UTPUT
S
S
HLD
D
I
_
3
I
NT
.S
N
SR
5
v
+
V
DI
S
RV
C
FLASH_WP
S
HLD
NETWRK I
N
NT
_
2
V
sel
R
N
G
LED
1
LE
D
A
ou
t
LED2
J
P4
J
P
5
R
N
G
J
P
7
Ai
n
LED1
JP3
LED2
1
1
4-20mA OUT
NC
No Connection to Field Wiring
Field Wiring w/space for Number
Internal Wiring
Screw Terminal
Wiring Guide Legend
Symbol Description
Air Flow To and From Unit
Between Room and Corridor
Remote
Pressure
Sensor
Io
+Vin
GND
0-5v (JP7)
Jumper Setting
AI 1
AI 2
AI 3
AI 4
1
2
3
4
= JUMPER ON
Analog Input
0-10v (JP7)
AI 1
AI 2
AI 3
AI 4
JP7
1
2
3
4
Analog Input
4-20mA (JP6)
AI 1
AI 2
AI 3
AI 4
Analog Input
JP6
0-5v (JP5)
AO 1
AO 2
AO 3
AO 4
Analog Output
0-10v (JP5)
AO 1
AO 2
AO 3
AO 4
JP5
Analog Output
Note: 4-20mA can only be used if the
corresponding JP7 Analog Input Jumper
is set to OFF.
Note: Each Analog Input or Output value can be set independent of one another.
Example:
AI 1 can be set to 0-5v jumper OFF (JP7 PIN 1)
AI 2 can be set to 0-10v jumper ON (JP7 PIN 2)
AI 3 can be set to 4-20mA jumper ON (JP6 PIN 3) and jumper OFF (JP7 PIN 3)
AO 1 can be set to 0-10v jumper ON (JP5 PIN 1)
AO 2 0-5v can be set to 0-5v jumper OFF (JP5 PIN 2)
= JUMPER OFF
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4

Mounting / Wiring
Analog Input to 2 Remote Pressure Sensors - 4-20mA Out
FMS-1655L
- 19 -
Triatek reserves the right to change product specifications without notice.
AO_1
AO_2
AO_3
AO_4
AI_1
AI_2
AI_3
AI_4
GND
GND
+10v
+V
ANALOG IN
NT_1
NT_2
NETWRK OUT
DI_1
DI_2
DI_4
GND
GND
GND
PH1
PH2
+VS
SYN
-
IN
SASH SNSR
DIGITAL IN
RLY1
RLY2
RLY3
RLY4
C3/4
C2
C1
RELAY OUTPUTS
SHLD
DI_3
1
2
3
EXT.SNSR
SELECT
INT.SNSR
G
5v
+V
DI
SRVC
EXT.
SNSR
+5v
GND
GND
GND
GND
SHLD
NETWRK IN
NT_2
NT_1
AUX PWR OUTPUT
ANALOG OUT
Vsel
RNG
4
1
2
3
1
LED
Ain
4
Aout
JP4
1
2
JP5
4
RNG
1
mA 3
LED3
LED4
JP7
Ain
1
JP6
JP3
1
1
1
1
1
1
1
NC
No Connection to Field Wiring
Field Wiring w/space for Number
Internal Wiring
Screw Terminal
Wiring Guide Legend
Symbol Description
Air Flow To and From Unit
Between Room and Corridor
+1
0
v
NT_1
NT_
2
N
ETWRK
OUT
D
I_
1
D
I_
2
D
I_
4
G
N
D
G
N
D
G
N
D
PH
1
PH
2
+V
S
S
YN
-
IN
S
A
S
H
S
N
S
R
D
I
G
ITAL I
N
R
LY
1
R
LY
2
R
LY3
RLY
4
C3/
4
C
2
C
1
RELAY
O
UTPUT
S
S
HLD
D
I
_
3
I
NT
.S
N
SR
G
5
v
+
V
DI
S
RV
C
+
5v
G
N
D
G
N
D
G
N
D
S
HL
D
NETWRK I
N
NT
_
2
NT
_
1
AUX PWR OUT
Vse
l
LE
D
4
LED
3
L
E
D4
JP3
1
Remote
Pressure
Sensor 1
~
~
Remote
Pressure
Sensor 2
GND
Io
+Vin
GND
Io
+Vin
~
~
~
~
4-20mA OUT
0-5v (JP7)
Jumper Setting
AI 1
AI 2
AI 3
AI 4
1
2
3
4
= JUMPER ON
Analog Input
0-10v (JP7)
AI 1
AI 2
AI 3
AI 4
JP7
1
2
3
4
Analog Input
4-20mA (JP6)
AI 1
AI 2
AI 3
AI 4
Analog Input
JP6
0-5v (JP5)
AO 1
AO 2
AO 3
AO 4
Analog Output
0-10v (JP5)
AO 1
AO 2
AO 3
AO 4
JP5
Analog Output
Note: 4-20mA can only be used if the
corresponding JP7 Analog Input Jumper
is set to OFF.
Note: Each Analog Input or Output value can be set independent of one another.
Example:
AI 1 can be set to 0-5v jumper OFF (JP7 PIN 1)
AI 2 can be set to 0-10v jumper ON (JP7 PIN 2)
AI 3 can be set to 4-20mA jumper ON (JP6 PIN 3) and jumper OFF (JP7 PIN 3)
AO 1 can be set to 0-10v jumper ON (JP5 PIN 1)
AO 2 0-5v can be set to 0-5v jumper OFF (JP5 PIN 2)
= JUMPER OFF
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4

Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
Mounting / Wiring
Analog Input to Temperature Sensor
FMS-1655L
- 20 -
Triatek reserves the right to change product specifications without notice.
0-5v (JP7)
Jumper Setting
AI 1
AI 2
AI 3
AI 4
1
2
3
4
= JUMPER ON
Analog Input
0-10v (JP7)
AI 1
AI 2
AI 3
AI 4
JP7
1
2
3
4
Analog Input
4-20mA (JP6)
AI 1
AI 2
AI 3
AI 4
Analog Input
JP6
0-5v (JP5)
AO 1
AO 2
AO 3
AO 4
Analog Output
0-10v (JP5)
AO 1
AO 2
AO 3
AO 4
JP5
Analog Output
Note: 4-20mA can only be used if the
corresponding JP7 Analog Input Jumper
is set to OFF.
Note: Each Analog Input or Output value can be set independent of one another.
Example:
AI 1 can be set to 0-5v jumper OFF (JP7 PIN 1)
AI 2 can be set to 0-10v jumper ON (JP7 PIN 2)
AI 3 can be set to 4-20mA jumper ON (JP6 PIN 3) and jumper OFF (JP7 PIN 3)
AO 1 can be set to 0-10v jumper ON (JP5 PIN 1)
AO 2 0-5v can be set to 0-5v jumper OFF (JP5 PIN 2)
= JUMPER OFF
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
AO_1
AO_2
AO_3
AO_4
AI_1
AI_2
AI_3
AI_4
GND
GND
+10v
+V
ANALOG IN
1
2
3
EXT.
SNSR
+5v
GND
GND
GND
GND
AUX PWR OUTPUT
ANALOG OUT
RNG
4
1
2
3
Ain
4
Aout
JP4
2
JP5
4
RNG
1
mA
3
JP7
Ain
JP6
1
1
1
NT_1
NT_2
NETWRK OUT
DI_1
DI_2
DI_4
GND
GND
GND
PH1
PH2
+VS
SYN
+
-
24V
IN
SASH SNSR
DIGITAL IN
RLY1
RLY2
RLY3
RLY4
C3/4
C2
C1
RELAY OUTPUTS
SHLD
DI_3
EXT.SNSR
SELECT
INT.SNSR
G
5v
+V
DI
SRVC
SRVC
FLASH_WP
1
SHLD
NETWRK IN
NT_2
NT_1
PWR
Vsel
1
SW1
LED1
JP2
LED
LED2
1
P4
Tx
LED3
LED4
Rx
*
*
*
*
*
*
*
*
*
SW1
LED1
D1
D1
D1
JP3
1
1
1
1
1
11
1
1
1
1111111
1
111
1
1
1
11
1
11
1
111
1
11
1
111
1
111
1
1111
1
1
1
11
1
11
1
111
1
11111111
1
111
1
1111
1
11
1
1111111111
1
1111
1
111
1
1111
1
11111111111111
1
JP2
FLA
JP2
FLA
LED2
1
LED3
LED
LED
LED
LED4
LED
LED
LED
1
1
1
1
1
11
1
1
1
1111111
1
111
1
1
1
11
1
11
1
111
1
11
1
111
1
111
1
1111
1
1
1
11
1
11
1
111
1
11111111
1
111
1
1111
1
11
1
1111111111
1
1111
1
111
1
1111
1
11111111111111
1
NC
No Connection to Field Wiring
Field Wiring w/space for Number
Internal Wiring
Screw Terminal
Wiring Guide Legend
Symbol Description
Air Flow To and From Unit
Between Room and Corridor
~
~
-
+
Temperature
Sensor
-
+
Power
Supply
Purchased Separately
Table of contents
Other TRIATEK Controllers manuals
Popular Controllers manuals by other brands

Sentera Controls
Sentera Controls HPSPX-LP Mounting and operating instructions

Resol
Resol BASIC controller Manual for the specialised craftsman

Topcon
Topcon ISOBUS Artemis Operation manual

Argo-Hytos
Argo-Hytos EL6 quick start guide

Siemens
Siemens SSC161.05UT manual

KNX
KNX Push Button RF+ operating instructions