CCR2+ Controller
9. RUN CCR2+ APPLICATION
10. CCR2+ DASHBOARD (Web App Screen)
Launch your browser from a computer or
wireless device that is connected to the CCR2+.
Tap the IP address into web browser window:
1. Wi-FI access: Type 192.168.1.10 into Web
Browser
2. LAN connection: Type 192.168.1.100 into Web
Browser
CCR2+ application will open.
For 1st login enter password »admin1234«
IMPORTANT: Change of password to secure any
unatorized interaction from 3rd parties
NOTE: You can Skip login for access to data only
in CCR+ (reading, overview only)
When the setup and is complete, the reading
display will be shown on the screen.
The Basic CCR2+ App screen has a dashboard
that offer plenty of status overview, basic and
advanced settings. The manufacturer reserves
the right to change Firmware in production to
improve handling and functionality. An up - to
- date list of settings for the given firmware is
available on the Danfoss website.
New settings can automatically upgrade
according to guidelines in instruction.
• Readings: Informations about basic settings,
device status, current time and date, storage
capacity
• User: Basic disinfection settings
• Installer: Advanced and service settings
• Corrections: Temperature sensor calibration
settings
• Scheduler: Schedule settings
• Tests: Device outputs testing tool
• Data: Access to Data log file
• Network: BMS and IP/TPC settings
• Firmware: Firmware upgrade tool
• Login: Login option
READINGS MENU:
No. Name Description
1Scheduler Open – Schedule programme active
Close - Scheduler programme not active
2S0-main temp.
S0 – value of (°C) supply temperature. The same readings apply to sensors S1 … S20.
Open - no sensor or break sensor circuit
Closed – shortcut to ground in sensor circuit
If the S0 is disinfection source, statutes are shown in color:
- Grey: S0 is start disinfection source
- Red: S0 temp. is OK(greater than disinfection temp.)
- Blue: S0 temp. is too low during disinfection process (lower than disinfection temp)
- Yellow: S0 temp. sensor is broken
3B1-start dis.
Input status B1 - G
Open – input B1 open
Close – input B1 close to G
If the B1 is disinfection source, statutes are shown in grey color.
Function is used in parallel and sequences connection.
4B2-stop dis.
Input status B2 - G
Open – input B2 open
Close – input B2 close to G
Close (shortcut B2-G) always finished disinfection process. The end of the disinfection process can
be realised automatically (look to: Advanced Menu – This is Master) or manually if it is necessary to
stop the process. When it is done manually, system reset all previous screen information (faults).
5B3-ext. alarm Information about external fault(used in sequence mode to indicate errors on primary CCR2+
master)
6Trigger timeout
To be used when input B1 source is not stable (f.ex. thermostat switch, or S0 temp. source is not
stable)
Timer will start to count down the disinfection timeout when B1 is open or. S0 temp. is less that
Dis.Set.Temp.
Timer is reseted if S0 temp. is higher that Dis.Set.Temp. or B1 input is closed.
In case of timeout count down to 0, disinfection will be stopped with timeout fault.
How much data can be stored per day in the system memory (for actually settings)
8 RT Clock The Real Time clock, show current time, date, day of the week
Data used in archive file and scheduler.