- 20 -
‘ Installation ‘
‘ For Qualified HVAC Installer Only ‘
Troubleshooting
WARNING:
• These procedures must be performed by a qualified HVAC technician or
electrician.
• Risk of personal injury or death could occur by attempting to troubleshoot or
repair this unit by untrained persons.
• Exercise the usual precautions when working with high voltage.
• When the circuit has been de-energized, always discharge any residual current in
the secondary circuit with an insulated handle screwdriver.
• Always ground power supply and Ionizing-Collecting Cell(s) when bench testing.
Recommended Service Tools
• Screwdriver, 8” common with insulated handle (plastic)
• Screwdrivers, Phillips #1 and # 2 with insulated handle (plastic)
• Needle Nose Pliers with insulated handles (plastic)
• Multimeter
• High Voltage Probe
Indication of Electrical Trouble
The air cleaner is equipped with a Red CELL ENERGIZED light for indicating proper unit
operation. When the unit is in normal operation (with the HVAC system blower running,
Front Panel Assembly in place, and ON/OFF switch in the ON position) and the Red CELL
ENERGIZED light is not illuminated, the problem is a shorted secondary circuit or Air Flow
Sensor fault. Although failure of the indicating light itself should not be overlooked, this
condition is unusual.
Air Flow Sensor (AFS) Circuit
WARNING:
The following procedure must be performed by an authorized HVAC contractor.
Failure to do so may result in personal injury or death.
1. Make sure the HVAC system blower is not operating, the ON/OFF switch is in OFF
position and the circuit breaker is turned OFF or input power cord is disconnected.
2. Remove the Front Panel Assembly.
3. Remove the cover from the Power Tray Assembly by removing the two screws on top
of unit.
4. Locate the AFS Thermistor, a small circuit with a small gray disc connected to the
power supply by two silver wires. Refer to the section entitled AIR FLOW SENSOR
(AFS) (page 2). Carefully bend the thermistor (small gray disc) wire leads so the
thermistor is located in the center of the 3/16” diameter hole in the Power Tray
Assembly and approximately 1/8” from the inside edge of the Power Tray Assembly
front.
- 5 -
‘ Maintenance ‘
Washing Ionizing-Collecting Cells and Prefilters
Regular washing of the Forever Filter®Ionizing-Collecting Cells is necessary to ensure
proper performance. A thorough washing once every six months will be adequate for most
installations. More frequent washing (once every one to three months) may be necessary
with some installations (new home for example) where there is new carpeting, plaster dust,
or excessive cigarette smoke.
CAUTION:
Handle Ionizing-Collecting Cells with care as cell plates can be sharp and cause injury if
not handled properly.
Remove Ionizing-Collecting Cells and Prefilters from the Air Cleaner:
1. Turn air cleaner ON/OFF switch to OFF position. Wait 15 seconds. Remove Front
Panel Assembly.
2. Carefully remove the Ionizing-Collecting Cells and Prefilters and set aside in a safe
place.
3. Do not drop the Ionizing-Collecting Cell(s). This can cause damage to the cell plates or
ionizing wires which results in excessive arcing and poor performance.
Wash Ionizing-Collecting Cells and Prefilters:
We suggest you follow the instructions below to properly and thoroughly clean your
Ionizing-Collecting Cells.
1. Place enough hot water in a utility tub to cover the first cell. Dissolve 2-4 oz. of
granulated automatic dishwasher detergent (NOT laundry detergent) in the water.
2. Allow the cell to soak for 30 minutes. Agitate the cell up and down in the solution until it
appears clean and remove the cell from the solution.
3. Repeat steps 1 and 2 for second cell.
4. Agitate the Prefilters up and down in the solution until they appear clean.
5. With a water hose, rinse the Ionizing-Collecting Cells and Prefilters. The hose should be
held about 10” from the cell plates and at a slight angle for maximum cleaning results.
Be careful not to spray the ionizing wires directly with the hose as the water pressure can
cause the wire(s) to stretch and break. The cell frame should be thoroughly rinsed along
the edges to dislodge any trapped lint or dirt. Carefully wipe a damp cloth or sandpaper
(not emery cloth) along the length of the ionizing wires.
6. Stand Ionizing-Collecting Cells and Prefilters in upright position and allow to dry two
hours. You may experience a slight discoloration of the aluminum collector cell plates
after washing. This is a normal chemical reaction between the aluminum and detergent
and will not harm your unit or affect its performance.
Replace Cells in the Air Cleaner:
1. Replace Prefilters and Ionizing-Collecting Cells in cabinet. Check that airflow arrow on
Cells point in same direction as air flows through the duct (if you have to force the cell
past the positioning screw in the cabinet bottom, the cell is probably in the incorrect
position.)
2. Replace Front Panel Assembly (engage tabs on lower edge of door into slots in cabinet).
3. Turn air cleaner ON/OFF switch to ON position.