Diagnostics -Version
S.X
The Herrtronic MD humidifier includes built-in
diagnostics capability to identify potential
problems, protect the system,
and
minimize
service/repair time. Should the system detect a
critical condition, a "fault"
warning
will be
displayed
on
the LCD. Certain faults
prompt
immediate system
shutdown
to protect the MD unit
or ductwork. Other faults allow the unit to continue
to operate
but
alert the operator to potential
problems that require maintenance. Other faults,
which are designed for initial system tune-up or
preventative maintenance, are classified as "non-
indicating." These faults are viewed
by
pressing the
"fault" key
on
the control panel. The table reflects
all of the faults the system is capable of detecting.
Please note, however, that certain faults are unique
to
certain control modes
or
networked systems
and
are only visible where applicable.
During operation,
when
an
"indicating" fault
occurs, the
word
FAULT
will be visible in the lower
right
hand
section of the LCD. The red fault light
will also be illuminated.
If
an "indicating" fault has been detected or a
preventative check is being performed, follow this
procedure to determine the cause of the fault:
1.
The LCD
must
be in the Main Menu to access
diagnostics. Press "FAULT" key to determine the
type of fault.
2.
Press the
up
arrow to determine if there is
more than one fault.
3.
If
possible, correct the condition causing the
fault signal or
plan
corrective action.
4.
Press "ENTER" to clear the fault signal from
the display
When
"ENTER" is pressed, all faults
registered in the
unit
will
be
cleared.
If
the
condition causing the fault is
not
corrected, another
fault signal will occur.
5.
Under normal operating conditions, pressing
the "fault" button will
prompt
the following
display:
In
a multi-unit network, the master ("00")
unit
will indicate a fault within the entire network.
To
find the fault(s), follow steps 1
and
2 for the master
unit.
If
the display indicates
"No
Faults Present
In
System," then neither the Master, nor
any
Slave
unit, has any faults.
If
any slave has a fault, the LCD will read:
Utilize the communications (Menu
4)
from the
Master to access the particular slave with fault(s) to
determine the fault. (Refer to communication
instructions in the programming section). Press the
up
arrow key to determine if there is more than one
"slave" that has a "fault."
System "Fault" Conditions
(See
Troubleshooting
Section
for
corrective
action)
OPERATION
FAULT
STATUS COMMENTS
Current Shutdown
and
120% of Capacity
Overload
,,,
Drain Manual Setpoint Exceeded
Reset'"
Contactor Continued Humidification
Failed'" Operation Required
Cylinder Full Continued Humidification
Zero Current Operation required; unit not
functioning properly
Fill Svstem Shutdown and Fill for
15
min. -cannot
Fault" Drain Manual achieve capacity
Rese~l)
setpoint or cyl. full
Zero Electrode Continued Humidification
Current Operation required, no current
draw
Non-zero Slow
Iv
Continued Defective drain
Decreasing Amps Operation system
Non-zero Non- Continued Defective drain
Decreasing Amps Operation system
Non-zero Non- Continued Defective
fill
system
Increasing Amps Operation
Non-zero Slow
Iv
Continued Defective
fill
system
Increasing Amp's Operation
Cylinder Full Continued Caused by low water
Operation
conductivi~
foaming,
or end of cyl. life
End of Cylinder Continued Cannot achieve
ca~acity
Life'" Operation and on cylinder
fu
for
programmed duration
Air Flow/High Svstem Insufficient airt10w/
Limit Shutdown, high limit setting
Automatic
Reset("
exceeded
Hi Humidity Continued Alarm threshold
Alarm""(" Operation achieved
Lo
Humidity Continued Alarm threshold
Alarm(3)",,)
Operation achieved
Humidity Sensor Continued Humidity less than
4%
Failed!})
Operation unless or greater than 100%
both
fail
Slave "XX" Has Continued Oper- Slave has fault
Faul~"
ation of Master
Communication Continued Oper- Slave operation
Port Fault ation of Master
unknown
(1) Manual reset requires the problem be corrected
and
the unit
turned "on" at the keypad
(0) Automatic reset will resume normal operation once the circuit
is
closed.
(3) Proportional + Integral Control Only
(')
Indicating Fault
20
Herrtronic
MD
Series
Installation and Operation Manual
/