1.2 To be provided by others
Note:
These instructions supplement the installation and operating manual of the FKRS-EU. Installation openings of the
lightweight partition wall, the fire-resistant cladding of the duct and the suspensions are implemented according to
the instructions, the installation and operating manual and supplementary to the design 478 (Promat® manual,
current version).
To be provided by others
Item Name Property / size
5Mineral wool Gross density ≥ 80 kg/m³, melting point ≥ 1000 °C,
d = 20 mm
6Cross bar Mounting rail Hilti MQ 41/3 or equivalent (incl. fixing mate-
rial)
7Steel wire clip 63 / 11.2 / 1.53, alternative coarse thread screw ≥ 5 × 80
8Steel wire clip 38 / 10.7 / 1.2
9Dry wall screw 3.9 × 45
10 Promatect-LS35 Cut-to-size pads d = 35 mm
11 Promatect-H Cut-to-size pads d = 10 mm
12 Hilti HUS 6
Fischer FFS 7.5 × 112
or equivalent
13 Promat glue K84
14 Threaded rod M10
15 Mineral wool Mineral wool (melting point ≥ 1000 °C) or gypsum mortar
for compensating unevenness
1.3 Special tool
Installation kit WE
Special tool
Fire damper Type FKRS-EU4