TTL UBT2-E User manual

UBT2-E
Controller
for
TTL air curtain systems
with electric heating
User manual
Translated English version

TTL Luftschleieranlagen - Controller UBT2-E
2
Contens
1. Safety information 2
2. Fixing 4
3. Technical data 5
3.1 Technical data of controller UBT2-E 5
3.2 Technical data of internal connecting board (ASP/PCB) 5
4. Quick -start guide 6
5. Application possibilities - basics 7
6. Controls 7
7. Operating modes 8
7.1 OFF mode 8
7.2 MANUAL mode 9
7.3 Mode AutoTK - automatic mode with door contact control 9
7.3. Mode AutoTA - automatic mode with anti-cooling protection (AKS) 9
7.3.1 AutoTA - automaticmode with AKS protection and door contact 9
7.4 Mode AutoRT - automatic mode with room temperature sensor 10
7.5 Summer/Winter mode 10
8. Timer 10
9. Basic - settings in Basic menu 11
9.1 Day / date / time 11
9.2 Language 11
9.3 Factory settings 11
9.4 Start-up 11
9.5 Memory 11
9.6 Overrun 11
5XQWLPHÀOWHU
6SHFLÀFV
11.Messages 12
12.Faults 13
13.Troubleshooting 13
14.Schedule 14
15.EU Declaration of Conformity 15
16.Wiring diagram
Manufacturer, contact, service adress
16

3
TTL Luftschleieranlagen - Controller UBT2-E
1. Safety information
For safety reasons, these assembly and operating instructions, including their safety information, must be care-
fully read and observed by all persons involved in assembly, start-up, operation, maintenance and servicing.
Please observe the following safety information on the device and in the documentation.
Warning: Safety information aiming to avoid risks to persons and property!
For your own safety, read this information very carefully!
Warning: Risk posed by electrical voltage!
Risk of electric shock.Avoid contact!
Caution: Risk posed by static charge!
The electrical circuit board can be destroyed. Remove static charge by touching an earthed object!
Note: Observe information and tips!
All product information is to be kept for the entire service life of the air curtain device!
Switching off the air curtain system(s) using the OFF key (0) on the UBT-E controller does not automa-
tically interrupt the mains power supply. Electrical equipment in the air curtain system and in the control
panel as well as the mains and connection lines may still be energised.The complete electrical disconnec-
tion of the air curtain system(s) from the mains takes place exclusively via the repair switch provided by
the customer!
WARNING
WARNING HAZARD
Air curtain devices contain dangerous, voltage-carrying exposed parts and/or moving or rotating
parts.These can cause very serious personal or material damage in case of misuse, replacing of
covers or inappropriate maintenance. Do never open the covers during operation! Do always cut
off the power supply before opening and switch off repair switch!
Assembly, disassembly, start-up, repair and changes of and to the air curtain system must only be
FDUULHGRXWE\TXDOLÀHGVSHFLDOLVWSHUVRQQHO5HSDLURIDQGFKDQJHVWRRUZLWKLQWKHGHYLFHPD\
only take place following consultation with the manufacturer or by TTL employees.
4XDOLÀHGVSHFLDOLVWSHUVRQQHODUHSHUVRQVWKDWGXHWRWKHLUVXIÀFLHQWTXDOLÀFDWLRQVKDYHEHHQ
authorised by the person responsible for the safety of the system to carry out the required
activities.The required skills include know-ledge of electrics, mechanics and heating installation, as
well as the applicable provisions, standards, accident prevention regulations, operating conditions
and on-site safety mechanisms.
7KHRSHQLQJRIDLUFXUWDLQXQLWVE\QRWTXDOLÀHGSHUVRQQHLVSDUWLFXODUO\SURKLELWHG
Original replacement parts and accessories approved by the manufacturer are designed for safety.
When using other parts or in the event of failure to observe the TTL documentation, we decline
all liability.
In the event of any ambiguities regarding technology, handling or use, we expressly recommend
checking with the manufacturer or his representative, citing the model designation.
We recommend the installation of a switch-disconnector/load-break switch with remote release
in closed proximity to the air curtain into the unit supply cable.The remote release can be con-
nected to the clambs 34 - 36 of the internal connecting board (ASP/PCB), to disconnect the air
curtain contactors from the mains supply in case of a malfunction.
ADVICE

TTL Luftschleieranlagen - Controller UBT2-E
4
2. Fixing
The electronic controller UBT2-E is made for wall mounting The case is designed two-piece with a basic plate
and an upper section with integrated electronic equipment.
The top part is screwed with 4 screws with the basic plate.The screws are accessible below the cover plugs at
the case edges.
Illustration: Fixing measures base plate
(illustration not true to scale
Fixing of base plate
at the wall with
2 screws resp.
dowels (3, 2 x 30 / 6 x 30)
attached by controlers acces-
sories kit.
Illustration: Dimensions of cover
Unlatch - click off
(2x)
122,0
104,0
12,0
70,0
3,8
53,5
35,0
70,0
122,0
10,0
7,0

5
TTL Luftschleieranlagen - Controller UBT2-E
3.Technical data
3.1 Technical data of controller UBT2-E
Electrical connection data line, factory ready-made with plugs in several lengths,
8-wire, RJ45 (ISDN) plugs, lengths 6, 10, 20, 30, 50 m
Bus system bus two-core, voltage supply two-core,
2 cores doubled
Interface / bus system bus, 8-wire with RJ45 8/8 -plugs (2x)
Connections 2x clambs, 3-core, max. 1,0 mm² (room sensor, outside sensor)
Keybord 1 central multifunctional wheel, 2 buttons for ON/OFF and
MODE selection
Display LCD display, chromatic
Protection IP 40
Operation temperature 0°C to +45 °C
Storage temperature -10°C to +60 °C
Installation type wall mounting, cable insertion from the rear side
(mounting over a blind junction box)
Cover plastic, gray - front panel/operating surface silver colored
Dimensions (l x h x d) 122,0 x 70,0 x 35,0 mm
Weight 136 g
Conformity
(controller and internal
connection board)
In accordance to Low Voltage Directive 2006/95/EG
EMC (Electromagnetic compatibility) -compatible to
EMC Directives 2014/30/EU
In accordance to directives
DIN EN 60335-1 (Safety of electrical units)
DIN EN 60204-1 (Electr. equipment of machinery)
3.2 Technical data for internal connecting board (ASP/PCB)
Connection (power supply). Fans-connecting box: 230 V AC, 50 Hz, L, N, PE,
clambs max 2,5 mm²
Heating connection: 400 V AC, 50 Hz, L1, L2, L3, N, PE,
clambs max. 4 mm²
Fuse F 16 AT microfuse
Interface / bus system bus, 8-wire with RJ45 8/8 -plugs (2x)
Connections, at control side clambs (numbers see wiring diagram), max. 1,0 mm²
Output messages operation message (NC), failure mess. (NC)
Inputs 3x (BMS release, external automatic contakt - door,
room sensor) --- to connect potential free

TTL Luftschleieranlagen - Controller UBT2-E
6
4. Qick -start guide
c Connect the control lines resp. check them
air curtain unit — controller UBT-E
air curtain unit — automatic contact (if possibly)
air curtain unit — room temperature sensor (if possibly)
If necesarry. control lines at groupings
d Switch-ON main power supply for air curtain unit(s)
e Switch-ON power supply for air curtain unit(s)
g Operating via TTL - UBT2-E controller
Selection of operating mode:
• push Mode button
• select desired mode by central multifunctional wheel
operating modes Manual / Automatic modes AutoTK / AutoTA / AutoRT
Automatic operating modes AutoTK / AutoTA / AutoRT
Check or adjust of parameters/Values with multifunctional wheel, like:
• adjusted step for air volume performance
• adjusted heating step
• adjusted step for overrun time for anti-cooling protection
(after closing door, if door contact closed)
• adjusted switching times in case of additional use of a timer
(if room temperature sensor or door contact connected)
Checking resp. setup of secondary and additional operating parameters like
• adjustment of the room thermostate (if connected) to the local conditions

7
TTL Luftschleieranlagen - Controller UBT2-E
5.Application possibilities - basics
The controller TTL -UBT2-E is an universal electronic operator panel for comfortable switching and control of
TTL air curtain devices with electric heating of all types and construction lengths.
The used CAN bus technology affords the possibility to connect several units.
The power supply of the single units, particularly the power supply for the electric heating must be detatched
and separately fused for every single unit respective to the electric load of each.
Please regard hereto the corresponding typing circuit diagramms.
Single units can be interconnected at the control level to functionelly groups.
Sutchlike units of a group will be controlled equal and operates at the same operating stage or power level.
By comparison to similar step switches TTL -UBT-E offers enlarged functions concerning::
• AUTOMATIC modes for switching in dependency of a door contact (AutoTK) by units ON-OFF or
door contact with additional time-limitated overrun time (AutoTA) for anti-cooling protection (AKS),
or by room temperature sensor (RT)
• automatic adjustment of air volume performance and heating step in dependence on differency of
actual temperature to desired setpoint for control via room temperature sensor.
• groupings of units
• display menu with plain text display of menu points
SURJUDPPLQJRIEDVLFIXQFWLRQVOLNHSURJUDPPLQJVRIHQDEOHUHVWDUWRYHUUXQWLPHÀOWHUOLIHWLPH
• Clock and timer with weekly programm
6. Controls
23
1
1 Multifunctional wheel
2 Button ON/OFF
2 MODE button

TTL Luftschleieranlagen - Controller UBT2-E
8
7. Operating modes
7.1 Manual - Operating mode - manual operation
If the step option is displayed in the bottom line, you can set different fan settings
by turning the multifunctional rotary knob. If you press the multifunctional rotary
knob, the heating option will be displayed.A heating setting from 1 – 3 can be tur-
ned on by using the multifunctional rotary knob depending on the set fan setting.
Fan step 1 - 2 - heating step 0 -1
Fan step 3 - heating step 0 - 2
Fan step 4 - 5 - heating step 0 - 3
Set the Manual operation (if required). Press the Mode key (PGM Mode dis-
playd). Select manual by using the multifunctional rotary knob (the text colour will
FKDQJHIURPRUDQJHWREODFN3UHVVWKHNQREWRFRQÀUPWKHVHOHFWLRQ7KHPDQXDO
option is displayed on the top line of the display in addition to the actual tempera-
ture. Press the multifunctional rotary knob to activate manual operation.
(Only for operation with a timer)
Turn the multifunctional rotary knob to set the setting in the bottom pre-selection line. Press the multifunc-
WLRQDOURWDU\NQREWRFRQÀUP1H[WWXUQWKHNQREWRVHOHFWDIDQVHWWLQJDQGSUHVVWKHNQREWRFRQÀUPWKH
selection. Set heating settings 1 - 3 using the same method (depending on the set fan settings, see above).
Select the timer using the multifunctional rotary knob and set the related clock symbol.
Clock symbol = timer OFF
Clock symbol orange = timer set in advance
Press the MODE key again to activate the selected operational mode (also see point 8).
(Default setting: fan step = 0, heating step = 0 -symbol color blue).
7.2 AutoTK - Operating mode - automatic mode with door contact control
Press the Mode key (PGM Mode display). Select AutoTK using the multifunc-
tional rotary knob (the text colour will change from orange to black). Press the
NQREWRFRQÀUPWKHVHOHFWLRQ7KHAutoTK option is displayed on the top line of
the display next to the actual temperature.
Next, you can set a fan setting, heating (depending on the selected fan setting, also
see point 1) and/or the timer using the multifunctional rotary knob.Turn the knob
WRWKHOHIWRUULJKWWRGRWKLVDQGSUHVVWKHNQREWRFRQÀUPWKHVHOHFWLRQ'HIDXOW
setting: fan step 0 and heating step 0).
The integrated timer can be set in advance (also see point 8).
Clock symbol = timer OFF
Clock symbol orange = timer set in advance
Press the MODE key again to activate the selected operational mode.
The switch-off of air curtain device(s) by OFF key (0) at the UBT-E control panel doesn`t
disconnect automatically the power connection to the electricity grid. Electrical systems
inside the air curtain unit as well as in the control panel and also the power cable and the
data lines may still be energized.The complete electrical disconnection of the air curtain
device from the mains will be effect exclusively by a repair switch provided by customer!
20°C
So 01.01.12 - 11.55
AutoTK
Stufe
20°C
So 01.01.12 - 11.55
Hand

9
TTL Luftschleieranlagen - Controller UBT2-E
The system must have been provided with a turning-off delay to prevent that the air curtain system is turned
on or off every time the door is opened or closed.This overrun can be set in the BASIC menu to 10 - 300 sec.
(Default setting: turning-off delay 60 sec, see point 9.6)
7.3 AutoTA - Automatic operation with anti-cooling protection (AKS)
Press the Mode key (PGM Mode display). Select AutoTA using the multifunctio-
nal rotary knob (the text colour will change from orange to black). Press the knob
WRFRQÀUPWKHVHOHFWLRQ7KHAutoTA option is displayed on the top line of the
display next to the actual temperature.
You can set the temperature for the cooling protection (AKS) between 11° and
30° C by using the multifunctional rotary knob.Turn the knob to the left or right
to do this until the required temperature has been reached (Default setting: fan
step = 0, heating step = 0 and AKS temperature = 15° C). Press the multifunctional
URWDU\NQREWRFRQÀUPWKHVHOHFWLRQ
The integrated timer can be set in advance (also see point 8).
Clock symbol = timer OFF
Clock symbol orange = timer set in advance
Press the MODE key again to activate the selected operational mode.
If the temperature drops below the preselected value, the system will switch to fan step 1 and heating step 1
WKH$.6GLVSOD\ZLOOÁDVKUHG
If the system uses the timer, the cooling protection will always have priority.
7.3.1 AutoTA - Automatic operation with AKS and door contact
Press the Mode key (PGM Mode display). Select AutoTA using the multifunctio-
nal rotary knob (the text colour will change from orange to black). Press the knob
WRFRQÀUPWKHVHOHFWLRQ
Next, you can set a fan step (1-5) and heating by using the multifunctional rotary
knob (depending on the selected fan setting, also see point 1).Turn the knob to
WKHOHIWRUULJKWWRGRWKLVDQGSUHVVWKHNQREWRFRQÀUPWKHVHOHFWLRQ'HIDXOW
setting: fan step = 0, heating step = 0 and AKS temperature = 15° C).
The integrated timer can be set in advance (also see point 8).
Clock symbol = timer OFF
Clock symbol orange = timer set in advance
Press the MODE key again to activate the selected operational mode.
The system must have been provided with a turning-off delay to prevent that the air curtain system is turned
on or off every time the door is opened or closed.This overrun can be set in the BASIC (menu to 10 - 300 sec.
(Default setting: turning-off delay 60 sec., see point 9.6)..
20°C
AKS
15°C
So 01.01.12 - 11.55
AutoTA
20°C
AKS
15°C
So 01.01.12 - 11.55
AutoTA

TTL Luftschleieranlagen - Controller UBT2-E
10
7.4 AutoRT - Automatic operation with room temperature sensor
Press the Mode key (PGM Mode display). Select AutoRT using the multifunctio-
nal rotary knob (the text colour will change from orange to black). Press the knob
WRFRQÀUPWKHVHOHFWLRQ7KHAutoRT option will be displayed on the top line
next to the actual temperature.
Select the room temperature using the multifunctional rotary knob and press the
NQREWRFRQÀUPWKHVHOHFWLRQ
Next, you can set the required room temperature (R-Temp). Press the multifunc-
WLRQDOURWDU\NQREWRFRQÀUPWKHVHOHFWLRQ'HIDXOWVHWWLQJ57HPS&
The integrated timer can be set in advance (also see point 8).
Clock symbol = timer OFF
Clock symbol orange = timer set in advance
Press the MODE key again to activate the selected operational mode.
The fan control will follow the set room temperature (preference temperature). Depending on the difference
between the actual temperature and the set room temperature, the control will adjust the fan and heating
setting.
7.5 Summer/Winter operation
'XUFKGLHJHWUHQQWH9RUZDKOYRQ9HQWLODWRUVWXIH/XIWOHLVWXQJXQG+HL]XQJVVWXIHNDQQGLH+HL]XQJGHÀQLHUW
abgeschaltet werden. Dies gestattet einen Betrieb der Luftschleieranlage ohne Heizung, also beispielsweise zur
Türabschirmung im Sommer gegen eindringende Warmluft.
Diese Funktion steht in allen Betriebsarten zur Verfügung.
8.Timer
Press the Mode key (PGM Mode display). Select Timer using the multifunctional
rotary knob (the text colour will change from orange to black). Press the knob to
FRQÀUPWKHVHOHFWLRQ
f the system must be turned on at 8:10 a.m. and turned off at noon every Monday,
program the following:
Turn the multifunctional rotary knob to select the week day (Monday): Mo.
Press the rotary knob to set the time: 08:10 - 12:00
You can program a second turning-on and -off time in the next line.You must con-
ÀUPWLPHVWKDWKDYHQRWEHHQSURJUDPPHGRQ0RQGD\VE\SUHVVLQJWKHPXOWLIXQF-
tional rotary knob.
You can program the times for the other days in the same way.
Press the MODE key again to activate the selected times.
Clock symbol = timer OFF
Clock symbol orange = timer set in advance
(programmed next time of the day)
Clock symbol green = timer in operation
(programmed next turning-off time of the day)
20°C
RT Soll 20°C
So 01.01.12 - 11.55
AutoRT
Mo 08:10 - 12:00
00:00 - 00:00
Di 00:00 - 00:00
00:00 - 00:00
Mi 00:00 - 00:00
00:00 - 00:00
Do 00:00 - 00:00
00:00 - 00:00
Schaltzeiten

11
TTL Luftschleieranlagen - Controller UBT2-E
9. Basic - settings in Basic menu
Press the Mode key (PGM Mode display). Select Basic by using the multifunc-
tional rotary knob (the text colour will change from orange to black). Press the
NQREWRFRQÀUPWKHVHOHFWLRQ
A menu will be displayed with the different setting options.
9.1 Day / date / time settings
Press the multifunctional rotary knob and turn it to select and change the rela-
ted data (24:00 hour notation).
9.2 Language settings
Press the multifunctional rotary knob and turn it to select and change the related data.
If required, you can switch from GER to ENG, NLD, FRA, ITA oder PL.
9.3 Factory settings - defaults
Press the multifunctional rotary knob and turn it to select and change the related data.The original data is
restored.
9.4 Start up
Press the multifunctional rotary knob and turn it to select and change the related data.
After the air curtain has been switched on, the speed will switch to setting 1 during 3 seconds and, next, to set-
ting 5 for another 3 seconds automatically. Next, the system will operate based on the set fan setting (default
setting: OFF).
9.5 Memory
Press the multifunctional rotary knob and turn it to select and change the related data.
The memory function ensures that all set values are kept saved in case of power outage. (Default setting: me-
mory ON).
9.6 Overrun (turning-off delay)
Press the multifunctional rotary knob and turn it to select and change the related data.
The turning-off delay at door contact operation can be set between 10 and 300 sec. (Default setting: turning-off
delay 60 sec).
5XQWLPHÀOWHU
Press the multifunctional rotary knob and turn it to select and change the related data.The service life of the
ÀOWHUFDQEHVHWEHWZHHQKRXUVGHIDXOWVHWWLQJKRXUV
Again press the MODE key to activate the changed basic setting.
AutoRT 21°C
PGM Mode
Mo 01.01.12 11:55
Language Ger
Werkseinst. aus
Anlauf aus
memory aus
060sNachlauf
950hFilterzeit
Datum/Zeit

TTL Luftschleieranlagen - Controller UBT2-E
12
6SHFLÀFV
At most 10 air curtain systems can be managed with one control panel
with the UBT2-E control.
Each printed circuit board is equipped with a coding switch for this purpose.
The coding reads as follows:
0= MASTER, 1 - 9 = SLAVE.
NOTE: never use the same coding for two systems.
If input does not follow in the programming mode (PRG Mode) for more than 60 seconds, the mode will be
terminated automatically.
Temperature sensor
The cable must be laid separately and must be as short as possible
DWPRVWPWRHQVXUHWKDWWKHVHQVRULVLQÁXHQFHGDVOLWWOHDVSRVVLEOH
by electromagnetic radiation.
The sensor cable must be shielded in unfavourable situations or when
the cable lengths are different (at most 20 m).
Room temperature sensor (dimensions 70 x 70 x 27 mm)
11. Messages
&OHDQÀOWHU (QGRIDGMXVWHGÀOWHUOLIHWLPH&OHDQÀOWHUXUJHQWO\
Filter can cleaned by a vac cleaner or can wipped clean.
1RWH$IWHUDZHWFOHDQLQJRIÀOWHUGRUHSODFHÀOWHU
after complete drying of this!
5HVHWPHVVDJHV Push MODE button (display PGM mode). By whipping
the multi funktional wheel select the prompt (text
FRORUFKDQJHVIURPRUDQJHWREODFNDQGFRQÀUPE\
pushing.
No enable No enable by on-site BMS.The unit cannot start.
5HVHWPHVVDJHV Automatically after setting a enable signal by BMS.
6HQVRUGHIHNWand actual temperature display 01°C Temperature sensor broken, not connected or max.
wire length is exceeded.
6HQVRUGHIHNW and actual temperature display 55°C Circuit short of tempearture sensor.
5HVHWPHVVDJHV The message will be deleted if failure of temperature
sensor is removed, and the air curtain unit goes into
normal operation.

13
TTL Luftschleieranlagen - Controller UBT2-E
12. Faults
Faulty message
The error message will be generated as a collective fault in the MASTER system when a fault occurs.
Only the faulty fan will be put out of service with regard to Motor overheat .
:KHQWKHV\VWHPLVWXUQHGRQÀUVWWKHVODYHV\VWHPVPXVWEHVXSSOLHGZLWKSRZHU
Potential-free messages
Function and fault messages are available on the printed circuit board in the form of change-over switches.
Message motor overheat
will be displayed when the temperature control is activated (fan motors).The faulty fan will be put out of ser-
vice.The system must be checked (contact a specialised installation company).
Cancel error message: Press the Mode key (PGM Mode display). Select the conformation option using the
PXOWLIXQFWLRQDOURWDU\NQREWKHWH[WFRORXUZLOOFKDQJHIURPRUDQJHWREODFN3UHVVWKHNQREWRFRQÀUPWKH
selection.
13.Troubleshooting
Error Display Possible cause Solution
System is not working Display OFF
1RWHQDEOHG
6HQVRUGHIHFW
No main power supply
Not turned ON
BMS/DDC release fault
Temperature sensor fault
cable broken
Circuit-short
Turn ON main power supply
Turn ON system
see ploint 7
Replace sensor
Replace cable
Resolve circuit-short
,QVXIÀFLHQWDLUÁRZVSHHG 0RWRURYHUKHDW
)LOWHUVHUYLFHOLIH
Fan fault
Air intake grill dirty
Air intake grill dirty
Replace fan (see pt. 12)
Clean air intake grill
Clean air intake grill (see pt. 11)
No heating
+HDWHURYHUWHPS
Heating is not turned ON
System has overheated
Air intake grill dirty
Turn ON heating (see pt. 7)
Clean air inatke grill
Reset
Clean air intake grill
No function FRPHUURU Error in data transfer Reset
The air curtain system must be reset when a fault occurs. Disconnect the power supply from the whole sys-
tem. Wait 10 seconds and again turn on the system (also see point 10).
Note: After a main power break the air curtain will reswitch in abandoned operating
PRGHVWDQGDUGFRQÀJXUDWLRQDSURJUDPPLQJIRUVZLWFKRQLQKLELWLVSRVVLEOH

TTL Luftschleieranlagen - Controller UBT2-E
14
14. Schedule
UBT2 -E
Manual
Step
Heating
Timer Timer
Set
temperature
AutoTK
Step
Heating
Timer
AutoTA
Step
Heating
R Temp
(cooling
protection
temperature)
AutoRT
Timer
Timer
Week
switching
clock
Basic
Start up
Date /
time
Language
Factory set
Memory
Step 0 MV
Overrun
Run time
filter
MODE
UBT2-E

15
TTL air curtain systems - Controller UBT-E
15. EU Declaration of Conformity
EU Declaration of Conformity
within the meaning of the EC Machinery Directive 2006/42/EC.
As the manufacturer:
TTL Torluftschleier GmbH
Fabrikstraße 5 • 73650 Winterbach/Germany
Fon +49 71 81/40 09 - 0 • Fax +49 71 81/40 09 - 10
E-Mail: info@luftschleier.de • www.luftschleier.de
we hereby declare that the product described below corresponds to the applicable health and
safety requirements of the cited EC Directive on the basis of its design and construction, as
well as the work carried out by us. If the product is altered in a manner not approved by us, this
declaration shall lose its validity.
Product designation: Electronic controller for air curtain devices
Model designation: UBT2-E
Applicable EC Directives: EC Low Voltage Directive 2006/95/EC
EC EMC Directives 2014/30/EU
EC Ecodesign Directive 2009/125/EG
Applied standards: DIN EN 60335-1
DIN EN 60204-1
In the event of any questions, please contact the manufacturer at the address above.
TTL GmbH reserves the right to undertake any change or improvement to parts or their acces-
sories without the obligation to update earlier products and existing documentation.
The German text is binding. Technical documentation is available in full.
Winterbach, 01.01.2019
Andrè Szameitat
Executive manager

TTL Torluftschleier GmbH
Fabrikstraße 5 • 73650 Winterbach
Fon +49 (0) 71 81 / 40 09 - 0
Fax +49 (0) 71 81 / 40 09 - 10
info@luftschleier.de • www.luftschleier.de
Imprint
User manual for controller TTL-UBT-2E
Translated English version 01
Manufacturer: TTL Torluftschleier GmbH
1. Edition January 2019: 1.500, printed at chloreene-free paper
By:TTL Torluftschleier GmbH (German version)
Copyright:TTL Torluftschleier GmbH
Reprint, also excerpts, only with written authorization.
Technical changes reserved.
Table of contents
Other TTL Controllers manuals
Popular Controllers manuals by other brands

LINK-MI
LINK-MI LM-R90U user manual

Lynn Electronics
Lynn Electronics CTR2-Mini+ Assembly manual

Swagelok
Swagelok KPF Series Maintenance instructions

IFM Electronic
IFM Electronic A5 Interface AS-i CONTROLLER e AC1333 installation instructions

Grundfos
Grundfos PM 2 Installation and operating instructions

ILX Lightwave
ILX Lightwave LDC-3900 user guide