Tyco 513D User manual

Figure 513D (13D) & 513D/R (13D/R)
Riser Manifolds For NFPA 13D/13R
Residential Sprinkler Systems
Page 1 of 6 APRIL 2006 TFP960
Worldwide
Contacts
www.tyco-fire.com
General
Description
TYCO Figure 513D (13D) & 513D/R
(13D/R) Riser Manifolds provide the
necessary waterflow alarm, pressure
gauge, and drain equipment in a single
assembly for use in NFPA 13D or 13R
residential sprinkler systems as follows:
NFPA 13D
• Figure 513D (13D)
1 Inch (DN25)
Female Thread x Female Thread
NFPA 13D/13R
• Figure 513D/R (13D/R)
1-1/2 Inch (DN40)
Male Thread x Female Thread
Male Thread x Male Thread
• Figure 513D/R (13D/R)
2 Inch (DN50)
Groove x Groove
Male Thread x Groove
The variety of sizes and end connec-
tions allow cost effective and easy tran-
sition to check valves, control valves,
and system piping. The Riser Manifolds
may be installed in either the horizontal
(flow switch on top) or vertical orienta-
tion (flow going up).
NOTICE
The Riser Manifolds described herein
must be installed and maintained in
compliance with this document, as well
as with the applicable standards of the
National Fire Protection Association
(NFPA), in addition to the standards of
any other authorities having jurisdiction.
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Technical
Data
Approvals
Figure 513D (13D) and 513D/R (13D/R)
Riser Manifolds with a cover tamper
switch for the waterflow alarm switch:
UL and ULC Listed
FM Approved
Figure 513D (13D) and 513D/R (13D/R)
Riser Manifolds without a cover tamper
switch for the waterflow alarm switch:
UL Listed
FM Approved
Maximum Working Pressure
175 psi (12,1 bar)
Assembly
The manifold body of the Figure 513 is
ductile iron, whereas the manifold body of
the Figure 13 is cast iron. The two assem-
blies are completely interchangeable in
function, application, and end-to-end laying
length..
Finish
Red Painted
Installation
TYCO Figure 513D (13D) & 513D/R
(13D/R) Riser Manifolds must be
installed in accordance with this
section.
The Riser Manifolds may be installed in
either the horizontal (flow switch on top)
or vertical (flow going up) orientation.
The inlet of the Riser Manifold may be
directly connected to a shut-off control
valve.
NOTICE
(1) Where applicable, pipe thread
sealant is to be applied sparingly. Use
of a non-hardening pipe thread sealant
is recommended.
(2) Provisions for an alarm test flow
must be made. The alarm test flow is
to be through an orifice having a flow
capacity equal to or smaller than the
smallest orifice sprinkler in the system.
One of two options can be considered.
The first option is to temporarily install a
test orifice in the outlet of the drain line
prior to performing the alarm test. The
second option is to install an Inspec-
tor’s Test Connection downstream of
the Waterflow Alarm Switch
(3) Never remove any piping compo-
nent nor correct or modify any piping
deficiencies without first depressurizing
and draining the system.
Riser Manifolds
Step 1. Install the manifold body with
the flow arrow pointing in the down-
stream position using threaded con-
nections and/or listed mechanical
grooved connections, as applicable.
Step 2. Connect the drain line, and
then close the drain valve.
Step 3. Refer to Figure 4 for wiring guid-
ance. All wiring must be per-formed in
accordance with the authority having
jurisdiction and/or the National Electri-
cal Code.
Step 4. Place the system in service
by filling the system with water. When
filling the system, partially open the
control valve to slowly fill the system.
Filling the system slowly will help avoid
damaging the waterflow alarm switch.
After the system is fully pressurized,
completely open the control valve.
Step 5. Secure all supply valves open.
OBSOLETE

TFP960
Page 2 of 6
1
1
1
QTY.
1
. . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . .
. . . .
3
2
1
NO.
976-519-01ULC/FM
Gauge
200 psi/1400 kPa
Water Pressure
2343
Paddle, UL/FM
Modied With:
Switch, VSR-SF,
Waterow Alarm
DESCRIPTION
Female x Female
1" Manifold Body,
Paddle and Cover
Tamper Switch,
or
NPT
971-096-01
N/R
P/N
2. ULC Listed Manifold equipped with
Cover Tamper Switches installed
internal to Waterow Alarm Switch
N/R - Not Replaceable3.
Approximate weight,
7.5 lbs. (3,4 kg)
NOTES:
1.
FEMALE
1" NPT
DRAIN VALVE
(NORMALLY
CLOSED)
9-3/4"
(247,7 mm)
3-5/8"
(92,1 mm)
3-1/2"
(88,9 mm)
FEMALE
1" NPT
10" (254,0 mm)
31
3/4" NPT
4-1/2"
(114,3 mm)
2-7/8"
(73,0 mm)
WATERFLOW
2
1
1
1
QTY.
1
. . . .
. . . . . . . . . .
. . . . . . . . . . .
. . .
3
NO.
1
2
971-096-00
976-519-02
DESCRIPTION
1-1/2" Manifold Body:
Male x Male NPT
Waterow Alarm
Switch, VSR-SF,
Modied With:
Paddle, UL/FM
Male x Female NPT
ULC/FM
Tamper Switch,
300 psi/2000 kPa
Paddle and Cover
Water Pressure
Gauge
or
or
2341
N/R
P/N
ULC Listed Manifold equipped with
Cover Tamper Switches installed
internal to Waterow Alarm Switch
Approximate weight,
8.7 lbs. (3,9 kg)
N/R - Not Replaceable
2.
3.
NOTES:
1.
DRAIN VALVE
(NORMALLY
CLOSED)
3-1/2"
(88,9 mm)
10" (254,0 mm)
2-1/8" (54,0 mm)
11-1/8" (282,6 mm)
311-1/2" NPT
WATERFLOW
2
1"
NPT
4-1/2"
(114,3 mm)
11-3/8"
(288,9 mm)
MALE
1-1/2" NPT
OPTIONAL
5-3/8"
(136,5 mm)
FEMALE
1-1/2" NPT
OPTIONAL
FIGURE 1
1 INCH (DN25) RISER MANIFOLD
ASSEMBLY AND DIMENSIONS
FIGURE 2
1-1/2 INCH RISER MANIFOLD
ASSEMBLY AND DIMENSIONS
OBSOLETE

TFP960
Page 3 of 6
Care and
Maintenance
TYCO Figure 513D (13D) & 513D/R
(13D/R) Riser Manifolds must be ser-
viced and maintained in accordance
with this section.
Before closing a fire protection system
control valve for inspection or main-
tenance work on the fire protection
system that it controls, permission to
shut down the effected fire protection
system must first be obtained from
the proper authorities and all person-
nel who may be affected by this action
must be notified.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for moni-
toring proprietary and/or central station
alarms.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any authority having
jurisdiction. The installing contractor or
product manufacturer should be con-
tacted with any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
NOTICE
No attempt is to be made to repair any
Riser Manifold component in the field.
Only the pressure gauge or waterflow
alarm switch can be replaced. If any
other problems are encountered, the
entire riser manifold must be replaced.
The flow and alarm test procedure
will result in operation of the associ-
ated alarms. Consequently, notification
must be given to the owner and the fire
department, central station, or other
signal station to which the alarms are
connected, and notification must be
given to the building occupants.
The following inspection procedure
must be performed as indicated, in
addition to any specific requirements
of the NFPA, and any impairment must
be immediately corrected:
Flow Test Procedure
Step 1. Fully open the drain valve.
Make certain that drainage water will
not cause any damage or injury.
Step 2. Verify that the residual (flowing)
pressure indicated by the pres-
sure gauge is no less that originally
recorded for the system when it was
first installed.
Step 3. Close the drain valve.
Step 4. Verify that the static (not
flowing) pressure indicated by the pres-
sure gauge is no less that originally
recorded for the system when it was
first installed.
Alarm Test Procedure with a Test
Orifice
(See Installation Note 2)
Step 1. Temporarily install a test orifice
in the drain line outlet.
Step 2. Fully open the drain valve.
Make certain that drainage water will
not cause any damage or injury.
Step 3. Verify operation of the associ-
ated alarms.
Step 4. Close the drain valve.
Step 5. Remove the test orifice from
the drain line outlet.
Alarm Test Procedure with an
Inspector’s Test Connection (See
Installation Note 2)
Step 1. Fully open the Inspector’s
Test Connection Valve. Make certain
that drainage water will not cause any
damage or injury.
Step 2. Verify operation of the associ-
ated alarms.
Step 3. Close the Inspector’s Test Con-
nection Valve.
1
1
1
QTY.
1. . .
. . . .
. . . . . . . . . .
. . . . . . . . . . .
2
3
NO.
1
Male NPT x Groove
2" Manifold Body:
Paddle and Cover
300 psi/2000 kPa
Waterow Alarm
Switch, VSR-SF,
Paddle, UL/FM
Tamper Switch,
ULC/FM
Gauge
Water Pressure
Modied With:
or
DESCRIPTION
Groove x Groove
or
976-357-01
976-520-01
2341
P/N
N/R
ULC Listed Manifold equipped with
Cover Tamper Switches installed
internal to Waterow Alarm Switch
Approximate weight,
11.0 lbs. (5,0 kg)
1.
NOTES:
3.
2.
N/R - Not Replaceable
DRAIN VALVE
(NORMALLY
CLOSED)
3-1/2"
(88,9 mm)
1"
NPT
4-1/2"
(114,3 mm)
2-1/4" (57,2 mm)
13" (330,2 mm)
31
WATERFLOW
2
2" NPT
OPTIONAL
2" GROOVE
OPTIONAL
2"
GROOVE
12"
(304,8 mm)
5-7/16"
(138,1 mm)
FIGURE 3
2 INCH (DN50) RISER MANIFOLD
ASSEMBLY AND DIMENSIONS
OBSOLETE

TFP960
Page 4 of 6
. . . . . . . . . .
. . . .
. . . . . . . . . .
. . . .
SWITCH TERMINAL CONNECTIONS
IMPROPER CONNECTION METHOD PROPER CONNECTION METHOD
CAUTION:
WATERFLOW SWITCH TYPICAL ELECTRICA CONNECTIONS
NOTE:
COVER TAMPER SWITCH (ULC ASSEMBLIES ONLY)
INCOMING
OUTGOING
SINGLE
CONDUCTOR
UNINSULATED
LOOPED SECTION
CLAMPING
PLATE
TERMINAL
SEPARATE
CONDUCTORS
CLAMPING
PLATE
TERMINAL
SEVERED
STRIPPED
ENDS
An uninsulated section of a
single conductor is not
permitted to be looped around
the terminal and serve as two
separate connections. The
wire must be severed to serve
as two separate connections,
thereby providing supervision
of the connection in the event
that the wire becomes
dislodged from the terminal.
COM
NCNO
NO FLOW
CONDITION
CONTACTS SPDT (Form C)
5A @ 125 VAC
2.5A @ 30 VDC
CONTACT RATING
COM
NO NC
POWER
LOCAL
SIGNAL
DEVICE
NON-SUPERVISED
CIRCUIT
END OF LINE
RESISTOR
COM
STYLE B/CLASS B
SUPERVISED CIRCUIT
(SEE NOTE)
CONTROL
PANEL
NO
NC
For supervised circuits, see "Switch Terminal Connections" above. The Waterow Alarm
Switch has two switches, one can be used to operate a central station, proprietary or remove
signaling unit, while the other contact is used to operate a local audible or visual annunciator.
CONTACTS SHOWN
WITH COVER IN PLACE
COM
CONTACT RATING
NO
CONTACTS
3A @ 250 VAC
5A @ 125 VAC
1mA @ 5 VDC min.
NC
SPDT (Form C)
FIGURE 4
RISER MANIFOLD
WIRING GUIDANCE
OBSOLETE

TFP960
Page 5 of 6
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indi-
cate the full product name, including
description and part number (P/N).
Riser Manifolds
Specify: Size (specify), Figure (specify
513D or 513D/R), Connection Type
(specify inlet x outlet) Riser Manifold
(specify with or without) a cover tamper
switch for the waterflow alarm switch,
P/N (specify):
UL / ULC / FM Assemblies
With Cover Tamper Switch
1 Inch (DN25)
FT x FT...........................4085
1-1/2 Inch (DN40)
MT x FT ..........................4088
1-1/2 Inch (DN40)
MT x MT..........................4089
2 Inch (DN50)
G x G ............................4093
2 Inch (DN50)
MT x G ...........................4094
UL / FM Assemblies
Without Cover Tamper Switch
1 Inch (DN25)
FT x FT...........................4047
1-1/2 Inch (DN40)
MT x FT ..........................4057
1-1/2 Inch (DN40)
MT x MT..........................4058
2 Inch (DN50)
G x G ............................4059
2 Inch (DN50)
MT x G ...........................4064
Notes:
Orders for Figure 513D or 513D/R Mani-
folds may be filled with Figure 13D or
13D/R Manifolds, respectively. The
two assemblies are completely inter-
changeable in function, application,
and end-to-end laying length.
If a ULC Listing is required, the Riser
Manifold must be ordered with a cover
tamper switch for the waterflow alarm
switch.
Replacement Parts
Specify: Product Description (specify)
for use with Figure (specify 513D,
513D/R, 13D, or 13D/R) Riser Manifold,
P/N (specify from Figure 1, 2 or 3, as
applicable)