Tyco WS User manual

Model WS Specific Application Window Sprinklers
Horizontal and Pendent Vertical Sidewall
5.6 K-factor
Page 1 of 8 MAY 2014 TFP620
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and
components. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
General
Description
The TYCO Model WS Specic
Application Window Sprinklers are fast
response, glass bulb-type spray sprin-
klers available in Horizontal Sidewall
and Pendent Vertical Sidewall models.
These sprinklers are the rst to be
specically Listed to provide complete
wetting and coverage for heat strength-
ened, tempered, or ceramic glass
windows using closed sprinklers.
As part of the testing, the gas ow
required to achieve the time/temper-
ature relationship specied in ASTM
E119 was established in a test furnace
without sprinkler protection. A window
assembly protected with the TYCO
Model WS Window Sprinklers was
then installed in the test furnace, and
the same gas ow conditions were
maintained for a two-hour test period.
No cracking or visible damage to the
window was permitted during the test
period, even when a hose stream was
directed at the window.
The success of the Model WS Window
Sprinklers is based on their fast
response thermal sensitivity and on
their specially designed deectors that
ensure that the spray pattern wets the
entire surface of the window.
Based on successful testing, the
Model WS Window Sprinklers can be
used as interior protection of windows
or glazing in a sprinklered building or
non-sprinklered building in accordance
with Section 104 of the IBC (“Alternate
Materials, Design and Methods of
Construction and Equipment”). Also,
the Model WS Window Sprinklers
can be used as an open sprinkler for
“Outside Sprinkler Protection against
Exposure Fire”, using the design
requirements of NFPA.
As with any specic application sprin-
kler, the installation instructions
included in this data sheet must be
precisely followed. If there are addi-
tional local or jurisdictional installation
standards/codes for window sprinklers
on glazed window systems, this docu-
ment does not relieve the designer/
installer from these requirements.
Consult your local jurisdiction to verify
if or when these additional guidelines
must be followed.
NOTICE
TYCO Model WS Specific Application
Window Sprinklers described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
recognized by the approval agency, in
addition to the standards of any author-
ities having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system and
devices in proper operating condition.
The installing contractor or manufac-
turer should be contacted with any
questions.
Sprinkler
Identification
Number (SIN)
TY3388 - Horizontal Sidewall
TY3488 - Pendent Vertical Sidewall
TY3388 is a re-designation for C3388
TY3488 is a re-designation for C3488

TFP620
Page 2 of 8
Technical
Data
Approvals
UL and C-UL Listed
NYC under MEA 289-04-E
Approvals only apply to the service
conditions indicated in the Design
Criteria section.
Additional Recognition
ICC Evaluation Service (ESR-2397)
Ontario Building Code
Pipe Thread Connection
1/2 inch NPT
Discharge Coefficient
K=5.6 GPM/psi1/2 (80,6 LPM/bar1/2)
Temperature Ratings
155°F (68°C)
200°F (93°C)
Finish
Natural Brass, Signal White (RAL9003)
Polyester, and Chrome Plated
Physical Characteristics
Frame ........................ Brass
Button.................Bronze/Copper
Sealing Assembly......Beryllium Nickel
w/TEFLON
Bulb ......................... Glass
(3 mm dia.)
Compression Screw. . . . . . . . . . . . . Brass
Deector................Brass/Bronze
Operation
The glass bulb contains a uid that
expands when exposed to heat. When
the rated temperature is reached, the
uid expands sufciently to shatter the
glass bulb, allowing the sprinkler to
activate and water to ow.
Temperature
1-5/8" DIA.
(41,3 mm)
NPT
WATERWAY
OF SPRINKLER
CENTERLINE
NOMINAL MAKE-IN
7/16" (11,1 mm)
Screw
Deector
-
6
THREAD
1/2"
RELIEF
Components:
Button
Sealing
Compression
Frame
Assembly
1-
-
-
-
-
5
4
2
3
Bulb
(54,0 mm)
FLATS
WRENCH
2-1/8"
WINDOW
(20,6 mm)
13/16"
TOWARDS
DEFLECTOR
ORIENT
INDICATED TOP
DEFLECTOR
OF SPRINKLER
SPRINKLER
FRAME ARMS
1 2 3456
indicated on
rating is
Deector.
CROSS SECTION PLAN
SIDE ELEVATION
**
*
NOMINAL MAKE-IN
7/16" (11,1 mm)
SPRINKLER
DEFLECTOR
TOP OF
Compression
3
(15,9 mm)
CENTERLINE
WATERWAY
OF SPRINKLER
5
4
5/8"
6
Assembly
2
1
Components:
Frame
Button
Sealing
-
1
3
2
-
-4
6
5
-Deector
Screw
Bulb
-
-
SPRINKLER
TOWARDS
WINDOW
ORIENT
FLOW ARROW
(INDICATED ON
DEFLECTOR) ARMS
FRAME
2-1/16"
(52,4 mm)
1-1/32"
(26,2 mm)
rating is indicated
Temperature
on Deector.
WRENCH
FLATS
1/2"
NPT
2-1/8"
(54,0 mm)
TOWARDS WINDOW ELEVATIONCROSS SECTION
*
*
*
FIGURE 1
MODEL WS WINDOW SPRINKLER
HORIZONTAL SIDEWALL
FIGURE 2
MODEL WS WINDOW SPRINKLER
PENDENT VERTICAL SIDEWALL

TFP620
Page 3 of 8
Design Criteria
The TYCO Model WS Specic
Application Window Sprinklers are UL
and C-UL Listed and NYC Approved
(MEA 335-01-E) for use as “Specic
Application Window Sprinkler” and as
open sprinklers for “Outside” use.
These sprinklers are also recognized by
Underwriters Laboratories of Canada
(ULC), and the Ontario Building Code
for use in the Province of Ontario,
Canada as providing a two-hour equiv-
alency for a re separation assembly
when installed in accordance with this
code.
Area of Use
When acceptable to the Authority
Having Jurisdiction and unless modi-
ed by a local jurisdictional standard or
code mentioned previously, the TYCO
Model WS Window Sprinklers may be
used in either a sprinklered or unsprin-
klered building to protect non-operable
window openings that are part of a re
separation provided:
•
in an interior re separation, the
window sprinklers are installed on
both sides of the window in the re
separation (Figure 3A-1),
• in jurisdictions where exterior spatial
separation (that is, separation
from adjacent space) is dened as
protecting an adjacent building from
a re in your building, window sprin-
klers are installed on the interior side
of the building (Figure 3A-2), or
• in jurisdictions where exterior spatial
separation is dened as protecting
your building from a re in an adja-
cent building (that is, exposure
protection), open window sprinklers
are installed on the exterior side of
the building (Figure 3A-3).
System Protection Type
• Interior: Wet Systems
• Outside Exposure: Deluge
Glass Type
The following types and thicknesses of
glass are recognized for use with TYCO
Model WS Window Sprinklers:
•
Non-operable, heat-strengthened,
tempered, single-glazed (single
pane), not less than 1/4 in. (6 mm)
thick;
•
Non-operable, heat-strengthened,
tempered, double-glazed (double
pane or insulated), not less than 1/4
in. (6 mm) thick;
•
Non-operable, UL Classied and
labeled FireLite Plus WS ceramic
glass by Technical Glass Products
(TGP), not less than 5/16 in. (8 mm)
thick; or,
NOTE: Refer to FireLite Plus WS
ceramic glass technical data sheet for
other classification limitations at www.
fireglass.com.
•
Non-operable, stronger glass window
assemblies, not less than 1/4 in. (6
mm) thick.
Type of Window Frame/Mullion
Non-combustible Frame with a stan-
dard EPDM rubber gasket seal
Vertical joints of glass panes must be
connected by butt-joints using a sili-
cone sealant between the individual
panes or by Noncombustible Mullions.
(Refer to Figures 3B-1 and 3B-2)
Maximum Length of Window
Assembly
Unlimited
Maximum Height of Window
Assembly
13 ft. (3,96 m)
(Refer to Figures 3C and 3D)
Maximum Distance Between
Window Sprinklers
8 ft. (2,44 m)
(Refer to Figures 3B-1 and 3B-2)
Minimum Distance Between
Window Sprinklers
6 ft. (1,83 m) unless separated by a
bafe or mullion of sufcient depth to
act as a bafe.
A mullion will act as a bafe, when
in the case of the Pendent Vertical
Sidewall, the mullion extends to the
back of the sprinkler deector, and in
the case of the Horizontal Sidewall, the
mullion extends to the sprinkler wrench
at.
(Refer to Figures 3B-1 and 3B-2)
Minimum Distance from Standard
Sprinklers
6 ft. (1,83 m) unless separated by a
bafe
Sprinkler Location
•
Mullioned Glazing Assemblies:
Locate window sprinklers within each
mullioned glazing segment. Refer to
Figure 3B-1.
•
Butt-Jointed Glazing Assemblies:
Locate window sprinklers on
maximum 8 ft. (2,44 m) centers. Refer
to Figure 3B-2.
Maximum Distance from Vertical
Mullion
4 ft. (1,22 m)
(Refer to Figure 3B-1)
Minimum Distance from Vertical
Mullions
4 in. (101,6 mm)
(Refer to Figure 3B-1)
Intermediate Horizontal Mullions
Intermediate Horizontal Mullions were
not tested with the Model WS Window
Sprinklers. Their use is outside the
scope of the “Specic Application”
Listing for the window sprinklers. Refer
to Figure 3B-3.
Deflector Location
Sprinkler Deectors must be located as
described below in order to ensure that
the entire surface of the glass window
is covered. Sprinkler Deectors are
positioned with respect to the window
frame, not the ceiling.
•
Horizontal Sidewall: Locate within the
outside edge of the window frame
from 1/2 to 4 in. (12,7 mm to 101,6
mm) away from the glass and 2 ± 1
in. (50,8 mm ± 25,4 mm) down from
the top of the exposed glass. Refer
to Figure 3C.
•
Pendent Vertical Sidewall: Locate
4 to 12 in. (101,6 mm to 304,8 mm)
from the face of the glass and 3 ± 1
in. (76,2 mm ± 25,4 mm) down from
the top of exposed glass. Refer to
Figure 3D.
Minimum Clearance from Face of
Glass to Combustible Materials
For glass types other than FireLite
Plus WS ceramic glass by TGP, all
combustible materials shall be kept
2 in. (50,8 mm) from the front face of
the glass. This can be accomplished
by a minimum 36 in. (914,4 mm) pony
wall or other method acceptable to the
authority having jurisdiction.
Escutcheon Assemblies
The Model WS Window Sprinklers
can be used with any metallic ush or
extended escutcheons, provided the
dimensions from the sprinkler deector
to the window frame and glass surface
as specied in this data sheet are
maintained. These sprinklers are not
listed for recessed applications.
Recommended Hydraulic
Requirements
The authority having jurisdiction should
be consulted to determine the hydraulic
requirements for each installation.
Interior Protection Sprinklered
Building
Identify which compartmented area
has the most hydraulically demanding
window sprinklers. Calculate up to the
most demanding 46.5 linear feet of
Model WS Window Sprinklers on one
side of the glazing. The 46.5 linear feet
(14,2 linear meters) is based upon 1.2
x the square root of the system area
of operation, when the system area of
operation is 1500 sq.-ft. in accordance
with NFPA 13 Light/Ordinary Hazard
density curves.

TFP620
Page 4 of 8
Where the area of Glazing is less than
14.2 linear meters, all window sprinklers
on one side shall be calculated.
If an area reduction for quick response
sprinklers is utilized, the linear length of
the calculated window sprinklers may
be reduced, but in no case shall be less
than 36 linear feet (1.2 x √900).
If a single re can be expected to
operate Model WS Window Sprinklers
and sprinklers within the design area of
a hydraulically calculated system, the
water demand of the window sprinklers
shall be added to the water demand
of the hydraulic calculations and shall
be balanced to the calculated area
demand.
If the window sprinklers are located in
an area other than the hydraulic design
area, the demand of the window sprin-
klers is not required to be added to
the demand of the remote hydraulic
design area. However, it is necessary
to prove hydraulically the simultaneous
operation of the Model WS Window
Sprinklers and the ceiling sprinklers
adjacent to the window sprinklers.
Interior Protection Non-Sprinklered
Building
Calculate all sprinklers on the most
demanding side of the glazing
assembly within the enclosure.
Exterior Exposure Protection
Calculate all sprinklers controlled by the
deluge valve using the design require-
ments of NFPA.
Duration of Water Supply
Duration of water supply must comply
with requirements of NFPA. If window
sprinklers are used to provide the
equivalency of a re rating, the water
supply must be capable of supplying
water for the required rating period.
Minimum Flow per Sprinkler
20 GPM (75,7 LPM) for sprinkler
spacing of 6 to 8 ft. (1,83 to 2,44 m)
or 15 GPM (56,8 LPM) for sprinkler
spacing less than 6 ft. (1,83 m).
Maximum Pressure per Sprinkler
•
Horizontal Sidewall: 70 psi (4,83 bar)*
* The 70 psi is only for cold solder
purposes. If there is a bafe or a
mullion of sufcient depth to act as a
bafe, separating the sprinklers, the
maximum pressure is 175 psi (12,07
bar).
• Vertical Sidewall: 175 psi (12,07 bar)
FIGURE 3A-1 - INTERIOR FIRE SEPARATION
FIGURE 3A-2 - EXTERIOR FIRE SEPARATION - SPRINKLERS INSIDE
FIGURE 3A-3 - EXTERIOR FIRE SEPARATION - SPRINKLERS OUTSIDE
When acceptable to the Authority Having Jurisdiction the Model WS Specic Application
Window Sprinklers may be used in either a sprinklered or unsprinklered building to protect
nonoperable window openings that are in an interior re separation, the window sprinklers
are installed on both sides of the window in the re separation.
INSIDE
INSIDE
When acceptable to the Authority Having Jurisdiction the Model WS Specic Application
Window Sprinklers may be used in either a sprinklered or unsprinklered building to protect
nonoperable window openings that are part of a re separation provided in jurisdictions
where exterior spatial separation is dened as protecting an adjacent building from a re
in your building, window sprinklers are installed on the interior side of the glass.
INSIDE
OUTSIDE
EXPOSURE
SIDE
When acceptable to the Authority Having Jurisdiction the Model WS Specic Application
Window Sprinklers may be used in either a sprinklered or unsprinklered building to protect
nonoperable window openings that are part of a re separation provided in jurisdictions
where exterior spatial separation is dened as protecting your building from a re in an
adjacent building, open window sprinklers are installed on the exterior side of the glass.
OUTSIDE
INSIDE
EXPOSURE
SIDE
FIGURE 3A (A-1 TO A-3)
TYPICAL NON-OPERABLE WINDOW OPENINGS

TFP620
Page 5 of 8
FIGURE 3B-1 - MULTIPLE WINDOWS SEPARATED BY MULLIONS
FIGURE 3B-2 - MULTIPLE WINDOWS SEPARATED BY BUTT JOINTS
FIGURE 3B-3 - WINDOWS WITH HORIZONTAL MULLIONS
6'-0" (1,83 m)
sufcient depth to act as a
(1,83 m) unless separated
Minimum distance between
Window Sprinklers is 6'-0"
*
bafe.
by a bafe or mullion of
MULLION
MINIMUM *SPRINKLER
MODEL WS
OR VERTICAL
HORIZONTAL
0'-4" (101,6 mm) MINIMUM
4'-0" (1,22 m) MAXIMUM
8'-0" (2,44 m)
MAXIMUM
6'-0" (1,83 m)
MULLION
MINIMUM
SPRINKLER
MODEL WS
OR VERTICAL
HORIZONTAL
0'-4" (101,6 mm) MINIMUM
4'-0" (1,22 m) MAXIMUM
8'-0" (2,44 m)
MAXIMUM
required to be located with
Window Sprinklers are NOT
respect to horizontal or
vertical butt joints.
BUTT JOINT
when intermediate horizontal
Window Sprinklers are NOT
listed to protect windows
mullions are present.
MULLION
WS SPRINKLER
VERTICAL MODEL
INTERMEDIATE
MULLION
HORIZONTAL OR
FIGURE 3B (B-1 TO B-3)
WINDOW MULLIONS AND BUTT JOINTS

TFP620
Page 6 of 8
Installation
The TYCO Model WS Specic
Application Window Sprinklers must
be installed in accordance with this
section.
General Instructions
Do not install any bulb-type sprinkler if
the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in. (1,6
mm).
A leak-tight 1/2 inch NPT sprinkler
joint should be obtained by applying a
minimum-to-maximum torque of 7 to
14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque may distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler.
Step 1. Install the pendent vertical side-
wall sprinkler only in the pendent posi-
tion with the center-line of the sprinkler
parallel to the glass surface. Orient the
sprinkler so that the direction of ow
indicated on the sprinkler deector is
facing the window.
Step 2. Install the horizontal side-
wall sprinkler only in the horizontal
position with the center-line of the
sprinkler perpendicular to the glass
surface. Orient the sprinkler so that the
word “Top” indicated on the sprinkler
deector is facing the top of window
frame.
Step 3. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
tting.
Step 4. With reference to Figures 1 or
2, apply End A of W-Type 20 Sprinkler
Wrench only (Figure 4) to the sprinkler
wrench ats and tighten the sprinkler
into the sprinkler tting.
INSTALLATION NOTE:
STRUCTURE
BUILDING
MODEL WS SPRINKLER
GLAZING FOR CLARITY
SHOWN ON ONE SIDE OF
2" (50,8 mm)
± 1" (25,4 mm)
NO MAXIMUM
DISTANCE
FOR GLASS TYPES
OTHER THAN FIRELITE
PLUS WS CERAMIC GLASS
BY TGP, ALL COMBUSTIBLE
MATERIALS SHALL BE
KEPT 2" (50,8 mm) MINIMUM
FROM SPRINKLERED FACE
OF GLAZING. THIS MAY BE
DONE THROUGH USE OF
MINIMUM 3'-0" (0,9 m)
PONY WALL
NON-OPERABLE
GLASS WINDOW
TO GLAZING
1/2" (12,7 mm)
TO 4" (101,6 mm)
ALIGNED VERTICALLY
DEFLECTOR FACING
AND PARALLEL
AND MARKED SIDE OF
WITH FRAME ARMS
POSITION SPRINKLER
MAXIMUM
NO
HEIGHT
(3,96 m)
GLAZING
MAXIMUM
EXPOSED
HEIGHT
13'-0"
FRAME
WINDOW
SPRINKLER DEFLECTOR
INDICATED ON
"TOP"
FIGURE 3C
MODEL WS HORIZONTAL SIDEWALL SPRINKLER
TYPICAL INSTALLATION

TFP620
Page 7 of 8
Care and
Maintenance
The TYCO Model WS Specic
Application Window Sprinklers must
be maintained and serviced in accor-
dance with this section.
Before closing a re protection system
main control valve for maintenance
work on the re protection system
that it controls, obtain permission to
shut down the affected re protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers - before,
during, and after installation. Sprinklers
damaged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section.)
The owner is responsible for the
inspection, testing, and maintenance of
their re protection system and devices
in compliance with this document, as
well as with the applicable standards
recognized by the Approval agency
(e.g., NFPA 25), in addition to the stan-
dards of any authorities having jurisdic-
tion. Contact the installing contractor or
sprinkler manufacturer regarding any
questions.
Automatic sprinkler systems are recom-
mended to be inspected, tested, and
maintained by a qualied Inspection
Service in accordance with local
requirements and/or national codes.
INSTALLATION NOTE:
NO MAXIMUM
ARROW POINTED MODEL WS SPRINKLER
GLAZING FOR CLARITY
SHOWN ON ONE SIDE OFTOWARD GLAZING
3" (76,2 mm)
± 1" (25,4 mm)
4" (101,6 mm)
HEIGHT
TO 12" (304,8 mm)
POSITION SPRINKLER
EXPOSED
HEIGHT
GLAZING
13'-0"
MAXIMUM
(3,96 m)
TO GLAZING AND
DEFLECTOR FLOW
ALIGNED PARALLEL
WITH FRAME ARMS
NON-OPERABLE
GLASS WINDOW
FLOW DIRECTION
DEFLECTOR
INDICATED ON
SPRINKLER
MAXIMUM
NO
FRAME
WINDOW
DISTANCE
STRUCTURE
CENTERLINE
OF SPRINKLER
WATERWAY
BUILDING
FOR GLASS TYPES
OTHER THAN FIRELITE
PLUS WS CERAMIC GLASS
BY TGP, ALL COMBUSTIBLE
MATERIALS SHALL BE
KEPT 2" (50,8 mm) MINIMUM
FROM SPRINKLERED FACE
OF GLAZING. THIS MAY BE
DONE THROUGH USE OF
MINIMUM 3'-0" (0,9 m)
PONY WALL
FIGURE 3D
MODEL WS PENDENT VERTICAL SIDEWALL SPRINKLER
TYPICAL INSTALLATION

TFP620
Page 8 of 8
Limited
Warranty
For warranty terms and conditions,
visit www.tyco-re.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Model WS HSW Window Sprinkler
with NPT Thread
Specify: Model WS Specic Application
Window Sprinkler TY3388, Horizontal
Sidewall, with (specify) temperature
rating, (specify) nish, and P/N (specify)
155°F (68°C)
Natural Brass .........P/N 50-305-1-155
Signal White (RAL9003)
Polyester ........... P/N 50-305-4-155
Chrome Plated ....... P/N 50-305-9-155
200°F (93°C)
Natural Brass ........ P/N 50-305-1-200
Signal White (RAL9003)
Polyester ...........P/N 50-305-4-200
Chrome Plated .......P/N 50-305-9-200
Model WS Pendent Vertical Sidewall
Window Sprinkler with NPT Thread
Specify: Model WS Specic Application
Window Sprinkler TY3488, Pendent
Vertical Sidewall, with (specify) temper-
ature rating, (specify) nish, and P/N
(specify)
155°F (68°C)
Natural Brass .........P/N 50-304-1-155
Signal White (RAL9003)
Polyester ........... P/N 50-304-4-155
Chrome Plated ....... P/N 50-304-9-155
200°F (93°C)
Natural Brass ........ P/N 50-304-1-200
Signal White (RAL9003)
Polyester ...........P/N 50-304-4-200
Chrome Plated .......P/N 50-304-9-200
Sprinkler Wrench
Specify: W-Type 20 Sprinkler Wrench,
P/N 56-000-1-106
INSTALLATION NOTE:
SHOWN ON ONE SIDE OF
GLASS WINDOW GLAZING FOR CLARITY
INSTALL VERTICAL AND
DO NOT PLACE BLINDS,
WINDOW COVERINGS
NONOPERABLE
AND GLAZING
BETWEEN SPRINKLER
TYPICAL
COVERING
WINDOW CEILING SPACES.
CURTAINS OR OTHER
WS SPRINKLERS
INTO RECESSED
HORIZONTAL MODEL
MODEL WS SPRINKLER
WINDOW
FRAME
SPACE
CEILING
RECESSED BUILDING
STRUCTURE
FOR GLASS TYPES
OTHER THAN FIRELITE
PLUS WS CERAMIC GLASS
BY TGP, ALL COMBUSTIBLE
MATERIALS SHALL BE
KEPT 2" (50,8 mm) MINIMUM
FROM SPRINKLERED FACE
OF GLAZING. THIS MAY BE
DONE THROUGH USE OF
MINIMUM 3'-0" (0,9 m)
PONY WALL
WRENCH RECESS
(USE END "A" FOR
MODEL WS)
FIGURE 3E
MODEL WS PENDENT VERTICAL SIDEWALL SPRINKLER
RECESSED CEILING TYPICAL INSTALLATION
FIGURE 4
W-TYPE 20 SPRINKLER
WRENCH
This manual suits for next models
2
Table of contents
Other Tyco Fire Alarm manuals
Popular Fire Alarm manuals by other brands

Hosiden Besson
Hosiden Besson Tri-Tone Sounder Installation details

Autronica
Autronica BS-310 Operator's handbook

FireClass
FireClass Precept EN Panel Installation & commissioning manual

GE
GE KILSEN KSA700 Series user guide

EMS
EMS FIRECELL quick start guide

Notifier
Notifier AVL-1 Operation and installation manual

Ei Electronics
Ei Electronics Ei413 instructions

MEDC
MEDC PBI Technical manual

Simplex
Simplex SafeLINC 4100U Installation & maintenance

Simplex
Simplex LifeAlarm 4005 Series Programming instructions

Mircom
Mircom MPS-800MP Series quick start guide

Fire-Lite Alarms
Fire-Lite Alarms UDACT-F Installation, operation, and programming manual