WARNING!
SYSTEM MUST BE INSTALLED IN ACCORDANCE WITH LOCAL AND NATIONAL
ELECTRICAL CODES
For indoor installations.
Risk of Electric Shock. All servicing should be performed by qualied service personnel.
To reduce the risks of electric shock disconnect power supplies before servicing.
Be aware that Line Voltage Connections may be 120VAC or 277VAC or 347VAC
IMPORTANT SAFEGUARDS
• READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
• Do not use outdoors.
• Do not mount near gas or electric heaters.
• Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by
unauthorized personnel.
• The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
• Do not use this equipment for other than intended use
• Wireless devices are only for lighting control
• Wireless controls cannot be used with portable heating appliances
• Insulate unused leads individually
SAVE THESE INSTRUCTIONS
A UDLA Company A UDLA Company

Page 3
Table of Contents
1. INTRODUCTION......................................................................................................................................................4
1.1. GENERAL DESCRIPTION.....................................................................................................................4
2. DESIGN FEATURES................................................................................................................................................4
3. SPECIFICATIONS....................................................................................................................................................5
POWER .........................................................................................................................................................5
LOAD RATINGS............................................................................................................................................5
OUTPUTS......................................................................................................................................................5
WIRELESS RANGE......................................................................................................................................5
OPERATING ENVIRONMENT ......................................................................................................................5
APPROVALS.................................................................................................................................................5
WARRANTY ..................................................................................................................................................5
4. DIMENSIONS...........................................................................................................................................................6
5. INSTALLATION FEATURES....................................................................................................................................6
6. INSTALLATION / WIRING / COMMISSIONING ......................................................................................................7
A UDLA Company A UDLA Company

Page 4
1. INTRODUCTION
1.1. General Description
The Bluetooth® Controller (part number BT-PP20-A) is a Bluetooth enabled lighting xture controlling device. The device
provides individual or multi-xture control based on the wiring conguration (one-to-one or one-to-many). The device
provides ON/OFF and 0-10v dimming control of the xture(s).
Each device is capable of communicating with other Douglas Lighting Controls Bluetooth enabled devices (occupancy
sensors, gateways, and wall station switches) via the Bluetooth mesh network.
Commissioning is conveniently done at deck level with our free smartphone App using Bluetooth communication
(smartphone must have Bluetooth capability).
2. DESIGN FEATURES
• Tinned and snipped, colour coded wires
• Threaded ½” knockout chase nipple with lock ring washer
• Bluetooth enabled for deck level conguration and wireless mesh networking
• LED status indicator
• 12VDC output to power DLC Bluetooth Sensor ( BT-WOR-A )
• Demand Response Ready
12VDC output
for
BT-WOR-A
LED Status
Indicator
Factory Reset
A UDLA Company A UDLA Company

Page 5
3. SPECIFICATIONS
Power
• Line Voltage: 120/277/347VAC
• Frequency: 60Hz
Load Ratings
• 800W @ 120VAC standard ballast
• 1200W @ 277VAC standard ballast
• 3300W @ 277VAC electronic ballast
• 1500W @ 347VAC standard ballast
• Relay: 20A General Use
Dimming Control
• 0-10V analog dimming, 100mA sinking capable
Outputs
• 12VDC, 30mA
• for Douglas Lighting Controls Bluetooth Occupancy/Daylight sensor BT-WOR-A (max. 2)
Wireless Range
• 150’ clear line of site, 50’ through standard walls (distances may vary based on location and environment. Additional
devices may be required at time of commissioning to ensure Bluetooth network integrity)
Operating Environment
• Indoor, stationary, non-vibrating, non-corrosive atmosphere and non-condensing humidity
Operating Temperature
• 32°F to 104°F (0°C to 40°C)
Approvals
• ETL Listed
• Conforms to UL STDS. 508, 1310, and 924
• Certied to CSA STD. C22.2 #14 and #223
• ETL Classied
• Conforms to UL STD. 2043
• Certied to ULC/ORD STD C2043
• ASHRAE 90.1 Compliant
• CEC Title 24 Compliant
• WSEC Compliant
• Contains IC: 8254A-B1010SP0
• Contains FCC ID: W7Z-B1010SP0
Warranty
• Standard 1-year warranty – see Douglas Lighting Controls’ warranty policy for complete details
A UDLA Company A UDLA Company

Page 6
0.84’ (21mm) Fits 1/2” knockout
0.84’ (21mm)
3.0”
(77mm)
1.85”
(47mm)
3.4”
(87mm)
4. DIMENSIONS
5. INSTALLATION FEATURES
The device is designed to be mounted into a ½“ knockout in a listed light xture or electrical junction box or panel with an
opening that can t the threaded chase nipple
• Tinned and snipped, colour coded ying leads
• Threaded ½” knockout chase nipple with lock ring washer
• Bluetooth enabled for deck level conguration and wireless mesh networking
A UDLA Company A UDLA Company

Page 7
6. INSTALLATION / WIRING / COMMISSIONING
CAUTION
Risk of Electric Shock. All servicing should be performed by qualied service personnel. To reduce
the risks of electric shock disconnect power connections before servicing.
• BT-PP20-A shall be mounted to a listed light xture or electrical junction box or panel with an opening that can t a
½” threaded nipple
• Product must be installed in accordance with local electrical codes
• Install device into place and x into position using lock ring washer
• For installation with eld installed conductors of 60°C minimum rating.
• The following wire connections are provided:
• 0-10V connection (violet / grey): #20AWG
• Line Voltage/Relay connection (black / white / red): #14AWG
• Connect wires as shown on diagram.
• NOTE: for Emergency lighting, an Emergency Power Source (i.e. Generator / Battery Backup) that is capable
of maintaining 120VAC / 277VAC / 347VAC (depending on the application) for a MINIMUM of 30 minutes is
required.
• Use appropriate sized wire-nuts to connect eld installed conductors.
• Download free Douglas Lighting Controls Smartphone App: BT-APP.
• Commission as required
Emergency Test
• The BT-PP20 Emergency operation can be tested using a Smartphone loaded with the free Douglas Lighting Controls
Smartphone App: BTCC.
• To test Emergency operation, perform the following steps:
1. Ensure the emergency circuit is connected to the BT-PP20 and is energized.
2. Use the BTCC “Room Setup” function on the commissioning mobile device (eg. iPod) or use a Douglas Lighting
Controls Bluetooth switch to turn OFF the BT-PP20 under test.
3. Use the BTCC “System Setup” function on the commissioning mobile device to navigate to the commissioned
devices list and select the settings cogwheel for the BT-PP20 under test.
4. In the settings page for the BT-PP20, select the “Test Emergency Mode” button. The BT-PP20 will turn on to
100% brightness for approximately 30 seconds and then will return to its previous OFF state.
5. Use the “Cancel” button to exit the BT-PP20 Settings page WITHOUT saving the conguration parameters.
It is recommended to test devices congured for Emergency operation on a monthly basis.
A UDLA Company A UDLA Company

Page 8
Maximum number of Fixtures can not exceed Sinking Current (100mA) based on dimming control.
Single Fixture
Fixture
Fixture Fixture Fixture
Red (relay)
Red (relay)
Multiple Fixture
Violet
Violet
Gray
Gray
White - Neutral
White - Neutral
White - Neutral
Black - Hot
White - Neutral
Black - Hot
Wiring
Wiring
A UDLA Company A UDLA Company

Page 9
Fixture
Red (relay)
Supplied by
Others
Violet
Gray
White - NeutralWhite - Neutral
Black - Hot
Black & White
(Hot & Neutral)
Wiring
Wiring Example for Emergency Lighting
Line Power
Emergency
Power
Transfer
Switch
A UDLA Company A UDLA Company

Page 10
The Bluetooth®word mark and logos are registered trademarks owned by Bluetooth®SIG, Inc. and any use of such marks is under license.
Other trademarks and trade names are those of their respective owners.
DOUGLAS LIGHTING CONTROLS
3605 Gilmore Way Suite 280,
Burnaby, BC V5G 4X5, Canada
CUSTOMER SERVICE:
877-873-2797 ext. 0 (English)
514-342-6581 (French)
TECHNICAL SUPPORT:
877-873-2797 ext. 1 (English)
514-342-6581 (French)
WEBSITE: douglaslightingcontrols.com
EMAIL: [email protected]
It’s EASY
to REACH US...