Maintenance:
The CR Damper requires relatively minimal maintenance. However, if the device is installed
in a filterless exhaust application, maintaining access for future cleaning and inspection is
recommended. To clean the damper, remove the damper, wash it with soap and warm
water, dry the damper, and reinstall the product.
Issues and Solutions:
If Airflow is too Low:
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Model CR
(Constant Airflow Regulator)
Damper too close to fan; separate the two with a manual damper to lower pressure
through CR Damper, or move damper further away from fan.
Wrong CR Damper installed; check CFM requirements against damper label, replace
or adjust airflow rate if necessary.
Damper operating incorrectly; check damper for damage and replace if necessary.
Duct pressure too low; increase fan speed or replace fan if necessary.
Duct air leakage too high; seal any gaps with tape.
If Airflow or Noise is too High:
Damper operating incorrectly; check damper for damage and replace if necessary.
Wrong CR Damper installed; check CFM requirements against damper label, replace
or adjust airflow rate if necessary.
Duct pressure too high; decrease fan speed if necessary.
Adjustments:
CR Dampers have an airflow adjustment range, controlled with a bit Torx T10. To change the
airflow rate, unscrew the set screw and slide the damper section of the regulator up or down
as needed.
Lower Airflow Rate
Higher Airflow Rate
Airflow Adjustment