UNITED Fire Systems STANDPIPE-PAC SSS-101 User manual

MODEL SSS-101
DESIGN, INSTALLATION, OPERATION,
AND MAINTENANCE MANUAL
Serial Number _______________________________________________
Date of Installation ____________Date of Commissioning ___________
UNITED Fire Systems
Division of UNITED Fire Protection Corporation
1 Mark Road
Kenilworth, NJ USA 07033 Manual Part Number 10-540101-001
908-688-0300 Revision 2.00
www.unitedfiresystems.net January 2019

(THIS SURFACE DELIBERATELY LEFT BLANK)

UNITED FIRE SYSTEMS
STANDPIPE-PAC™MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
i
INDEX
Section
Description
Page
INDEX
i
List Of Figures
ii
List Of Tables
iii
Safety Information
iii
Foreword
iv
Limited Warranty
v
1.
GENERAL INFORMATION
1.1
System Purpose
1
1.2
Boston FD TCM3-51725
1
1.3
Functional Description
1
2.
DESIGN
2.1
Determining Internal Volume of Standpipe
4
2.2
Determining Desired Fill Time
4
2.3
Determining Proper STANDPIPE-PAC™ To Use
5
2.4
Example 1
6
2.5
Example 2
7
2.6
Options
8
2.6.1
Additional Audible Signals
8
2.6.2
Off-Site Signaling Via Dialer
8
3.
INSTALLATION
3.1
Unpacking
9
3.2
Location
9
3.2.1
Temperature
9
3.2.2
Engineering Drawings (if available)
9
3.2.3
Proximity
9
3.2.4
Weight
9
3.2.5
Noise
10
3.2.6
Clearance
10
3.3
Installation
10
3.3.1
Mounting
10
3.3.2
Piping
11
3.3.3
Manual Air Release Bleed Valve
11
3.3.4
Auxiliary Condensate Drain Device
12
3.3.5
Electrical Installation
13
3.3.5.1
Codes
13
3.3.5.2
Personnel
13
3.3.5.3
Power Wiring
13
3.3.5.4
Battery Wiring
14
3.3.5.5
Signal Wiring
15
3.3.6
Optional Dialer Wiring
21
3.4
Commissioning
21

UNITED FIRE SYSTEMS
STANDPIPE-PAC™MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
ii
3
INSTALLATION (Continued)
3.4.1
Required Supervisory Pressure
21
3.4.2
Startup
22
3.4.3
Testing
23
3.4.4
Placing In Service
24
3.4.5
Troubleshooting
24
4.
OPERATION
4.1
Indicators
29
4.2
Controls
29
4.3
Indications
30
4.3.1
Normal Operation
30
4.3.2
Low Pressure In Standpipe
30
4.3.3
High Pressure in Standpipe
31
4.4
Procedures
32
4.4.1
Normal Operation
32
4.4.2
To Silence Piezo Sounder
32
4.4.3
To Silence Signal Horn(s)
32
4.4.4
For Fire Department Use Of Fire Standpipe
32
4.4.5
To Refill Standpipe With Air Pressure After Fire Department Use
33
4.4.6
To Test Standpipe with Water Pressure
34
5.
MAINTENANCE
36
5.1
Weekly
37
5.2
Monthly
37
5.3
Quarterly
38
APPENDICES
Appendix A
Instructions –EPS10 Pressure Switch
Appendix B
Instructions –EPS40 Pressure Switch
Appendix C
Instructions –Desiccant Dryer Service
Appendix D
Manual –411UDAC Fire Alarm Communicator
Appendix E
Instructions –General Air Compressor
LIST OF FIGURES
Figure No.
Description
Page
1
STANDPIPE-PAC™ Unit
2
2
Manual Air Release Bleed Valve
3
3
Remote Weatherproof Audible / Amber Visual Device
3
4
Auxiliary Condensate Drain Device
3
5
Estimating Standpipe Fill Time
5
6
Design Example 1
6
7
Design Example 2
7
8
Dimensions –STANDPIPE-PAC™ Unit
10
9
STANDPIPE-PAC™ Installation
11
10
Auxiliary Condensate Drain Device
12

UNITED FIRE SYSTEMS
STANDPIPE-PAC™MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
iii
LIST OF FIGURES (continued)
11
Battery Wiring
14
12
Wiring Diagram-Notification Appliance Circuit
16
13
Signal Horn Installation Steps
17
14
Required Supervisory Pressure
21
15
Desiccant Air Dryer
39
16
Compressor Filter
40
LIST OF TABLES
Table No.
Description
Page
1
Available STANDPIPE-PAC™ Units
4
2
Determining Internal Volume of Standpipe
4
3
Current Requirements –STANDPIPE-PAC™ Units
13
4
STANDPIPE-PAC™ Notification Appliance Circuit (NAC) Limitations and
Other Parameters
16
5
Do’s and Don’ts
20
SAFETY INFORMATION
This manual contains safety information that is important to know and understand. This information is provided for the
safety of installers, operators, and users of the UNITED Fire Systems STANDPIPE-PAC™ equipment. Carefully read,
understand, and follow instructions identified by these symbols.
DANGER
The use of the word “DANGER” identifies an immediate hazard with a likelihood of death or serious personal injury
if instructions, including recommended precautions, are not followed.
WARNING
The use of the word “WARNING” identifies the presence of hazards or unsafe practices that could result in death,
personal injury, or serious property damage if instructions, including recommended precautions, are not followed.
CAUTION
The use of the word “CAUTION” identifies possible hazards or unsafe practices that could result in personal injury
or property damage if instructions, including recommended precautions, are not followed.
IMPORTANT
The use of the word “IMPORTANT” identifies special instructions, not related to hazards, that should be followed.

UNITED FIRE SYSTEMS
STANDPIPE-PAC™MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
iv
FOREWORD
This manual is written for those who install, operate and maintain UNITED Fire Systems STANDPIPE-PAC™
standpipe supervisory systems. The manual contains installation, operation, and maintenance information for the
system. This manual must be read thoroughly and completely understood before installation and operation of
UNITED Fire Systems STANDPIPE-PAC™ equipment. All appropriate safety standards as determined by local or
national laws and regulations should be followed at all times. When handling, installing, or operating this equipment,
personnel must employ safe engineering practices and observe all related local regulations, health, and safety
procedures, and legal requirements for safety. Ensure that the equipment is depressurized and electrically isolated
before carrying out any of the scheduled maintenance instructions specified in this manual.
IMPORTANT
UNITED Fire Systems assumes no responsibility for the installation, operation, or maintenance of any systems
other than those addressed in this manual. The data contained in this manual is for information purposes only.
UNITED Fire Systems believes this data to be accurate at the time of publication, but the data is published and
presented without any guarantee or warranty whatsoever. UNITED Fire Systems disclaims any liability for any use
that may be made of the data and information contained in this manual by any and all parties.
IMPORTANT
The UNITED Fire Systems STANDPIPE-PAC™ standpipe supervisory system is a vital part of the fire protection
of any facility where these units are installed. Life safety and property protection depends on continuing proper
operation of the assembly. The owner of the STANDPIPE-PAC™ is responsible for the condition of the assembly
and its continued proper operation. UNITED Fire Systems strongly recommends that all owners of STANDPIPE-
PAC™ systems engage the services of qualified, trained fire protection professionals to design the system
containing the assembly, and to install and maintain the assembly.
CAUTION
Read all of the safety information in this manual before installing, operating, or maintaining this equipment. Use of
the equipment in a manner not specified within this manual may impair the protection provided by this equipment
and could result in serious injury or damage. Only competent personnel should perform installation, operation, and
maintenance procedures.
WARNING
DO NOT install, operate, or maintain unit if damage has occurred during shipping, handling, or use. Contact
UNITED Fire Systems immediately. Failure to do so could result in death, personal injury, or serious property
damage.

UNITED FIRE SYSTEMS
STANDPIPE-PAC™MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
v
UNITED Fire Systems STANDPIPE-PAC™ standpipe supervisory systems are to be installed, operated, and
maintained by qualified, trained personnel in accordance with:
This Installation, Operation, and Maintenance Manual P/N 10-540101-001 Revision 2.00.
National Fire Protection Association No. 14, “Standard for the Installation of Standpipe and Hose
Systems.”
National Fire Protection Association No. 25, “Standard for the Inspection, Testing, and Maintenance
of Water-Based Fire Protection Systems.”
National Fire Protection Association No. 70, “National Electrical Code®”.
Any questions on the information in this manual should be addressed to:
UNITED Fire Systems, Division of United Fire Protection Corporation
1 Mark Road, Kenilworth, NJ USA 07033
908-688-0300 www.unitedfiresystems.net
LIMITED WARRANTY
STANDPIPE-PAC™
What Does This Warranty Cover?
This warranty covers all manufacturing defects in material and workmanship in your new STANDPIPE-PAC™.
How Long Does The Coverage Last?
This warranty lasts for ninety (90) days from the date of shipment to the original purchaser.
What Will UNITED Fire Systems Do?
UNITED Fire Systems will repair, replace, or refund the purchase price of, at its option, any defective
STANDPIPE-PAC™ at no charge.
What Does This Warranty Not Cover?
STANDPIPE-PAC™s that have NOT been commissioned by UNITED Fire Systems or a trained distributor are
not covered under this warranty. If you modify, change, or alter your STANDPIPE-PAC™ without instructions
from UNITED Fire Systems, the STANDPIPE-PAC™ is not covered. If you break tamper seals applied by
UNITED Fire Systems, the sealed parts are not covered. Any problem that is caused by abuse, misuse, or an
act of God (such as a flood) is not covered. Also, consequential and incidental damages are not recoverable
under this warranty. Some states do not allow the exclusion or limitation of incidental or consequential damages,
so the above limitation or exclusion may not apply to you.
How Do You Obtain Service?
In order to be eligible for service under this warranty, your STANDPIPE-PAC™ must have been commissioned
by UNITED Fire Systems or a trained distributor. If something goes wrong with your STANDPIPE-PAC™,
contact:
UNITED Fire Systems
Division of UNITED Fire Protection Corporation
1 Mark Road
Kenilworth, NJ 07033 USA
Phone: 908-688-0300
Fax: 908-481-1131
= OR =
Your
Trained
Distributor
UNITED Fire Systems or your trained distributor will contact you within 24 hours to arrange for evaluation of your
STANDPIPE-PAC™.
Is This Warranty Transferable?
If the STANDPIPE-PAC™ is moved from one to another installation during the time period of warranty coverage,
the STANDPIPE-PAC™ must be re-commissioned by UNITED Fire Systems or your trained distributor to be
eligible for continuing coverage. You must pay a quoted charge for this re-commissioning.
Is This The Entire Warranty?
This limited warranty is the entire warranty given by UNITED Fire Systems to the purchaser of a new
STANDPIPE-PAC™. There are no other warranties expressed or implied, beyond those required by law.
How Do State and Federal Laws Apply?
This warranty gives you specific legal rights per Federal law. You may also have other rights which vary from
state to state.

UNITED FIRE SYSTEMS
STANDPIPE-PAC™ MODEL SSS-101
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 1
1. GENERAL INFORMATION
1.1.System Purpose. The UNITED Fire Systems STANDPIPE-PAC™ Model SSS-101 Standpipe Supervisory
System is a fully assembled standpipe supervisory system, including compressor, switches, alarm, and control
unit providing one complete zone of standpipe supervision in compliance with Boston FD TCM3-51725. All
components are mounted on a sturdy wooden backboard, suitable for hanging at a construction or demolition site.
1.2. Boston FD TCM3-51725
Boston FD TCM3-51725 was implemented in response to serious difficulties encountered when fire standpipes at
construction and demolition sites were damaged, rendering the standpipes unsuitable for fire department use.
The directive requires that all fire standpipes in vacant buildings, buildings undergoing demolition, and required
permanent or temporary standpipes in buildings under construction be equipped with a system to pressurize the
standpipe at all times, which then would sense the pressure loss if a portion of the standpipe was damaged or
completely removed. Detailed requirements for the system are specified in the directive. STANDPIPE-PAC™
has been designed to aid in compliance with the requirements in Boston FD TCM3-51725. IMPORTANT:
Boston FD TCM3-51725 requires that an application to install an air pressurized alarm system be filed by a
registered design professional, and a permit obtained by a licensed sprinkler contractor. A licensed electrician
shall obtain all required electrical permits. Install STANDPIPE-PAC™ after application is made and accepted,
and all permits received. To review Boston FD TCM3-51725 in its entirety, go to: www.unitedfiresystems.net.
1.3. Functional Description. See Figures 1, 2, 3, and 4. STANDPIPE-PAC™ consists of the following:
(1) Air compressor with automatic control switch. The air compressor compresses atmospheric air for
pressurizing the standpipe. The automatic control switch starts the compressor when the pressure is below
13 PSIG, and stops the compressor when the pressure exceeds 18 PSIG.
(2) Desiccant air dryer. The desiccant air dryer dries the compressed air before entry into the standpipe, as
required by Boston FD TCM3-51725.
(3) Low-limit pressure sensing switch. This switch senses when the pressure in the standpipe drops below 7
PSIG, as would happen if a standpipe valve was inadvertently opened, or a portion of the piping was
inadvertently removed. This switch sends its signal to the control unit (8).
(4) High-limit pressure sensing switch. This switch senses when the pressure in the standpipe exceeds 23
PSIG, as may happen if the automatic control switch on the air compressor (1) fails. This switch sends its
signal to the control unit (8).
(5) Pressure gauge. The pressure gauge indicates the approximate pressure in the system in PSIG.
(6) Check valve. The check valve prevents entry of water into the STANDPIPE-PAC™ when the Fire
Department pumps water into the standpipe. This device is required by Boston FD TCM3-51725
(7) Lockable shutoff valve. This valve permits maintenance on the STANDPIPE-PAC™ without de-pressurizing
the entire standpipe. This device is required by Boston FD TCM3-51725, and per this directive, shall be
locked in the OPEN position.
(8) Control unit with power supply, backup battery, silence switch, and automatic dialer. The control unit accepts
the signals from the pressure sensing switches (4) and (5), and operates the signal horn (9). The silence
switch allows the signal horn (9) to be silenced. The power supply is dedicated to the system as required by
Boston FD TCM3-51725, and provides for backup battery power for the control unit. This device also
provides an automatic dialer for connection of telephone lines for off-site notification.
(9) A signal horn. Additional signal horns may be connected so that signaling may be heard throughout the site.
(10) A junction box for connection of 120 VAC, 60 Hz, single phase power for both the air compressor (1) and
the control unit (8). Connection of 120VAC 60 Hz single phase in this box provides power for both the air
compressor (1) and the control unit (10).
(11) An outlet for connection of piping to the dry standpipe. 1/2” NPT pipe (provided by installer) is run from the
outlet to a connection point on the standpipe.
(12) A disconnect switch to remove power from the air compressor (1). This switch facilitates testing and
maintenance of the system.
(13) A test / service device. See instructions in this manual for use of this device.
(14) A serial number nameplate.

UNITED FIRE SYSTEMS
STANDPIPE-PAC™ MODEL SSS-101
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 2
(15) A manual air release bleed valve for Fire Department use. This device is to be installed near the siamese
connection feeding the standpipe. A cap and chain is provided to protect the outlet. An instruction
nameplate is also provided. This nameplate is to be securely fastened near the valve.
(16) A remote weatherproof audible / amber visual device with weatherproof backbox and identification
nameplate. This device is required by Boston FD TCM3-51725. The installer must locate this device
immediately outside the location of the STANDPIPE-PAC™, and wire the device in accordance with the
instructions in this manual.
(17) An auxiliary condensate drain device. This device permits manual draining of water in the piping near the
STANDPIPE-PAC™ unit, to help prevent water entry into the unit and pipe blockage without removing all
air from the standpipe. (Figure 4)
Figure 1 –STANDPIPE-PAC™ Unit
(9)
SIGNAL HORN
(10)
JUNCTION BOX
FOR CONNECTION
OF 120 VAC
(12)
POWER DISCONNECT
SWITCH FOR
AIR COMPRESSOR
(4)
HIGH-LIMIT
PRESSURE SENSING
SWITCH
(13)
TEST / SERVICE
DEVICE
(3)
LOW-LIMIT
PRESSURE SENSING
SWITCH
AUTOMATIC CONTROL
SWITCH FOR
AIR COMPRESSOR
(1)
AIR COMPRESSOR
(8)
CONTROL UNIT
(BATTERY INSIDE)
OPERATING
INSTRUCTIONS
LABEL
(6)
CHECK VALVE
(7)
LOCKABLE
SHUTOFF VALVE
(11)
OUTLET FOR
PIPING CONNECTION
(5)
PRESSURE GAUGE
(2)
DESICCANT
AIR DRYER
(14)
SERIAL NUMBER
NAMEPLATE

UNITED FIRE SYSTEMS
STANDPIPE-PAC™ MODEL SSS-101
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 3
INSTRUCTION
NAMEPLATE
(15)
MANUAL AIR RELEASE
BLEED VALVE
CAP AND CHAIN
Figure 2 –Manual Air Release
Bleed Valve
Figure 4 –Auxiliary Condensate
Drain Device
(17)
AUXILIARY CONDENSATE
DRAIN DEVICE
Figure 3 –Remote Weatherproof
Audible / Amber Visual Device with
Weatherproof Backbox

UNITED FIRE SYSTEMS
STANDPIPE-PAC™ MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 4
2. DESIGN. The specific STANDPIPE-PAC™ to use is chosen based on the internal volume of the standpipe to
be protected, and the desired fill time. See Table 1. Four (4) different units are available, based on compressor
size.
STANDPIPE-PAC™ Part Number
Compressor Size, HP
SSS-101-16
1/6
SSS-101-13
1/3
SSS-101-12
1/2
SSS-101-34
3/4
2.1. Determining Internal Volume of Standpipe. See Table 2. The internal volume of the standpipe, in gallons,
is determined by multiplying the length of each pipe, by size, by the internal volume per foot, in gallons.
Nominal Pipe Size
Pipe Length in Feet
Gallons per Foot
Gallons
1-1/2”
X
0.106
2”
X
0.174
2-1/2”
X
0.248
3”
X
0.383
4”
X
0.660
6”
X
1.500
8”
X
2.600
Other
X
TOTAL =
2.2. Determining Desired Fill Time. Per Boston FD TCM3-51725, any impairment lasting 4 hours or more
requires shutdown of the construction / demolition site and notification to the Boston Fire Department. The
usual criterion is to fill / refill the standpipe in less than 4 hours, with margin for work performed for
construction / demolition. NOTE: The NFPA 13 sprinkler system rule of 30 minutes “fast-fill” DOES NOT
apply to standpipes.
Table 1 –Available STANDPIPE-PAC™ Units
Table 2 –Determining Internal Volume of Standpipe

UNITED FIRE SYSTEMS
STANDPIPE-PAC™ MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 5
2.3. Determining Proper STANDPIPE-PAC™ To Use. See Figure 5.
2.3.1. Find the desired fill time at the bottom of the graph.
2.3.2. Find the standpipe internal volume at the left of the graph.
2.3.3. Determine the intersection of the lines from these two values.
2.3.4. Choose the next-highest compressor horsepower.
2.3.5. Determine the P/N of the appropriate STANDPIPE-PAC™ from Table 1.
Figure 5 –Estimating Standpipe Fill Time
Estimation of Standpipe Fill Time
Based on Compressor Size - HP

UNITED FIRE SYSTEMS
STANDPIPE-PAC™ MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 6
2.4. Example 1.
Nominal Pipe Size
Pipe Length in Feet
Gallons per Foot
Gallons
6”
750
X
1.500
1125
TOTAL =
1125 gallons
Required work can be performed in 1/2 hour (30 minutes), so a fill time of 1-1/2 hours (90 minutes) is
satisfactory
Figure 6 –Design Example 1
Required compressor = 1/3 HP
STANDPIPE-PAC™ to use = SSS-101-13

UNITED FIRE SYSTEMS
STANDPIPE-PAC™ MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 7
2.5. Example 2.
Nominal Pipe Size
Pipe Length in Feet
Gallons per Foot
Gallons
2”
80
X
0.174
14
6”
100
X
1.500
150
8”
550
X
2.600
1430
TOTAL =
1594 gallons
Fill time of 1 hour (60 minutes) required.
Figure 7 –Design Example 2
Required compressor = 3/4 HP
STANDPIPE-PAC™ to use = SSS-101-34
NOTE: A 1/2 HP compressor (SSS-101-12)
would give a fill time of
approximately 68 minutes.

UNITED FIRE SYSTEMS
STANDPIPE-PAC™ MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 8
2.6.Options.
2.6.1. Additional Audible Signals. Additional audible signals can be added to the Notification Appliance Circuit
(NAC) of the STANDPIPE-PAC™ unit to permit hearing the alarm throughout the facility. Consult Appendix A of
this manual for further information. See Paragraph 3.3.5.5 for installation instructions.
2.6.2. Off-Site Signaling Via Dialer. The STANDPIPE-PAC™ control unit is equipped with a built-in dialer for off-site
signal notification. See Appendix D for proper hookup of telephone lines for this purpose.
IMPORTANT
Signals from the STANDPIPE-PAC™ unit are NOT fire alarm signals. UNITED Fire Systems recommends that all
devices connected to the Notification Appliance Circuit (NAC) of the STANDPIPE-PAC™ unit
be clearly differentiated from any fire alarm signals present in the building.

UNITED FIRE SYSTEMS
STANDPIPE-PAC™ MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 9
3. INSTALLATION
3.1.Unpacking. Check shipment of the UNITED Fire Systems STANDPIPE-PAC™ system for damage. If there is
any damage or missing parts, the transportation company's agent should make a notation to the effect on the Bill
of Lading. Claims should be settled directly with the transportation company. Verify that all parts were received in
the shipment as ordered. Contact the factory immediately if there are any missing parts or discrepancies. The
following items should be with the shipment:
STANDPIPE-PAC™ unit –P/N SSS-101-XX (XX = compressor size)
Manual air release bleed valve –P/N 06-100004-000
Cap and chain for manual air release bleed valve –P/N 06-100004-001
Nameplate for manual air release bleed valve –P/N 10-440001-001
Standby battery (12 VDC 7.5 A-H) for control unit –P/N 03-100005-001
Weatherproof audible / amber visual device –P/N 03-100006-101 with amber lens attached.
Identification nameplate for audible / amber visual device –P/N 03-100008-101
Design, installation, operation, and maintenance manual –P/N 10-540000-001.
Auxiliary condensate drain device kit –P/N 10-220000-100
3.2. Location. Due consideration must be given to all of the following considerations when locating the STANDPIPE-
PAC™ unit.
3.2.1. Temperature.
Ensure that the STANDPIPE-PAC™ unit is installed in a location that will not drop below +32°F (0° C) at any
time. This may be accomplished by:
Choosing a location that will be supplied with building heat during cold weather, or;
Providing a space heater in the vicinity of the unit when cold weather is expected.
3.2.2. Engineering Drawings (if available). If a survey was conducted, and engineering drawings prepared, locate
all equipment per these drawings.
3.2.3. Proximity. The STANDPIPE-PAC™ unit should be installed in reasonably close proximity to the standpipe
being protected. The most logical location is in the same room as the riser. If necessary, the device may be
installed remotely. Documentation and signage should be clear to identify which equipment in remote locations
is connected together.
3.2.4. Weight. Ensure that the mounting surface is capable of supporting the weight of the STANDPIPE-PAC™ unit,
with a clear safety margin. Consult a structural engineer when necessary to verify suitability of location.
CAUTION
Understand and follow all safety recommendations when moving heavy pieces of equipment. Equipment may be
easily tipped over when moving. Failure to use caution can result in equipment damage and personal injury.
IMPORTANT
The STANDPIPE-PAC™ assembly is designed for use in areas where the temperature DOES NOT drop below
+32°F (0° C). DO NOT install STANDPIPE-PAC™ units in areas where the temperature can go below +32°F (0° C).
Failure to comply can result in unit malfunction and damage which is NOT covered by the warranty.

UNITED FIRE SYSTEMS
STANDPIPE-PAC™ MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 10
3.2.5. Noise. The STANDPIPE-PAC™ unit does emit noise when running. Consideration should be given to locating
equipment where normal operating noise does not interfere with building operations.
3.2.6. Clearance. Sufficient clearance should be available after installation for maintenance operations to take place.
Leave at least (3) feet of clearance for personnel to access equipment for maintenance.
3.3. Installation.
3.3.1. Mounting. See Figure 8. Mount the STANDPIPE-PAC™ in the chosen mounting location.
It is strongly recommended that the unit be mounted on a wall.
The unit weighs approximately 86 lbs. Choose a wall with construction capable of supporting this weight, with
a reasonable safety margin.
Use good standard practice and appropriate fasteners.
The back board may be drilled as needed for mounting. Do not drill holes too close to corners.
Leave a minimum of 3 feet of clearance in front of unit for personnel to perform maintenance.
Figure 8 –Dimensions –STANDPIPE-PAC™ Unit

UNITED FIRE SYSTEMS
STANDPIPE-PAC™ MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 11
3.3.2. Piping. See Figure 9. The piping in BLUE is to be installed by the STANDPIPE-PAC™ system installer. Use
Sch. 40 black pipe and Class 150 fittings. The tee to connect the STANDPIPE-PAC™ shall be located after the
check valve, and should be located before the drain valve. Connect 1/2” pipe to point labeled OUTLET on
STANDPIPE-PAC™ unit. Ensure that the standpipe is NOT PRESSURIZED prior to cutting in the tee at the
installation location.
All dry standpipes should always be maintained as dry as possible. This is to minimize internal corrosion year round,
as well as to minimize ice accumulation and blockage during cold weather.
To facilitate drainage, the low point of the standpipe must have a main drain valve, and all pipe should be pitched
towards that main drain valve. The main drain valve should be opened on a regular basis, permitting any water
accumulation or pooled water from testing to drain.
Dry standpipes installed with supervisory systems shall be installed per Figure 9 above. The diagram indicates several
important facts:
1. Where possible, the STANDPIPE-PAC™ should NOT be the low point of the dry standpipe system.
2. The piping from the STANDPIPE-PAC™ should be pitched away from the STANDPIPE-PAC™ so that
accumulated water drains away from the STANDPIPE-PAC™ outlet.
3. Install the Auxiliary Condensate Drain Device where shown on Figure 10, per 3.3.4.
3.3.3. Manual Air Release Bleed Valve. See Figure 2. Locate the manual air release bleed valve on the exterior of
the building in proximity to the fire department siamese connection feeding the standpipe protected by the
STANDPIPE-PAC™. Attach the cap and chain to the valve. Secure the provided nameplate to the building or the
valve so that the fire department can clearly identify the purpose of the valve and follow the instructions on the
nameplate.
Figure 9 –STANDPIPE-PAC™ Installation
CAUTION
Failure to confirm that the standpipe is NOT pressurized could result in personal injury and / or property damage.

UNITED FIRE SYSTEMS
STANDPIPE-PAC™ MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 12
3.3.4. Auxiliary Condensate Drain Device
1. Determine the installation location of the Auxiliary Condensate Drain Device:
a. Locate the device in close proximity to the outlet of the STANDPIPE-PAC™.
b. The location of the STANDPIPE-PAC™ and the Auxiliary Condensate Drain Device MUST be in an area
protected from freezing temperatures (over +32°F (0° C)).
c. The device MUST be installed vertically –see Figure 9 and Figure 10.
d. No separate bracket is necessary –the inlet piping connection should be satisfactory to hold the device in
place.
2. Remove and discard plastic plug from device inlet (Valve 1).
3. See Figure 10. Attach a ½ inch close pipe nipple and the bull of a ½ inch pipe tee to device inlet.(Valve 1)
4. Install a convenient length of ½ inch threaded pipe between the outlet of the STANDPIPE-PAC™ and the run of
the tee attached to the device inlet.
5. See Figure 10. Connect ½ inch pipe to the remaining run of the tee attached to the device and the inlet to the dry
standpipe. Pitch the pipe to drain away from the device.
6. See Figure 4. Attach Instruction Nameplate to wall in close proximity to device.
IMPORTANT
The Auxiliary Condensate Drain Device does NOT take the place of a standpipe system main drain. Ensure that a
main drain valve is properly installed at the lowest point of the standpipe, in an accessible area, where all the water
from the standpipe may be properly drained.
Figure 10 –Auxiliary Condensate Drain Device

UNITED FIRE SYSTEMS
STANDPIPE-PAC™ MODEL SSS-101
DESIGN, INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
REVISION 2.00
P/N 10-540101-001
Page 13
3.3.5. Electrical Installation.
3.3.5.1. Codes. All STANDPIPE-PAC™ wiring and wiring methods shall be in strict compliance with NEC and local
codes.
3.3.5.2. Personnel. All wiring shall be performed by licensed electricians.
Part No.
Compressor Motor
And Control Unit
Voltage (V) /
Phase
Frequency (Hz)
Compressor
Motor
Horsepower
(HP)
Compressor
Motor
Current
(A)
Control
Unit
Current
(A)
STANDPIPE-PAC™
Total
Current
(A)
SSS-101-16
115 / 1 / 60
1/6
6.6
0.7
7.3
SSS-101-13
115 / 1 / 60
1/3
6.6
0.7
7.3
SSS-101-12
115 / 1 / 60
1/2
8.0
0.7
8.7
SSS-101-34
115 / 1 / 60
3/4
10.6
0.7
11.3
3.3.5.3. Power Wiring. See Table 3. Choose minimum conductor sizes and overcurrent protective device based on
total current shown in table. Connect power in junction box provided for the purpose –see Figure 1. When
connecting power, ensure circuit breaker is OFF. Do not turn on circuit breaker until installation is complete and
system is ready for commissioning.
DANGER
RISK OF ELECTROCUTION
Voltages and currents associated with STANDPIPE-PAC™ units are LETHAL. Follow all instructions provided.
Work on STANDPIPE-PAC™ unit power MUST be performed ONLY by qualified individuals. All required
precautions to prevent contact with live electrical conductors and equipment MUST be taken. Failure to comply with
these instructions is an immediate hazard with a likelihood of death or serious personal injury!
Table 3 –Current Requirements –STANDPIPE-PAC™ Units