Unitronics Jazz JZ20-UA24 User manual

Unitronics
1
Jazz™PLC+HMI
Micro-PLC+HMI Installation Guide
JZ20-UA24
JZ20-J-UA24
9 Digital Inputs including one HSC, 2 Analog/Digital inputs,
2 Analog Inputs, 2 PT100/TC,
5 Relay Outputs, 2 Transistor Outputs, 2 Analog Outputs
Before using this product, the user must read and understand this document.
For additional information regarding this product, refer to the user guide and technical specifications.
All examples and diagrams are intended to aid understanding, and do not guarantee operation.
Unitronics accepts no responsibility for actual use of this product based on these examples.
Please dispose of this product according to local and national standards and regulations.
Only qualified service personnel should open this device or carry out repairs.
Failure to comply with appropriate safety guidelines can cause severe injury or property damage.
Do not attempt to use this device with parameters that exceed permissible levels.
To avoid damaging the system, do not connect/disconnect the device when power is on.
Environmental Considerations
Do not install in areas with: excessive or conductive dust, corrosive or flammable gas,
moisture or rain, excessive heat, regular impact shocks or excessive vibration.
Ventilation: 10mm space required between the PLC+HMIs’ top/bottom edges & enclosure
walls.
Do not place in water or let water leak onto the unit.
Do not allow debris to fall inside the unit during installation.
Mounting
Dimensions
* Note that for JZ20-J modules those dimensions are 7.5 mm (0.295”).

07/16
2
Unitronics
Add-on modules-
Available by separate order for
communication and cloning.
Integral USB Port
This may be used for
programming purposes.
Note: the USB port and an Add-on module cannot be physically connected at the same time.
Add-on: during installation
Add-on: after installation
USB Port
Installing an Add-on module requires sufficient clearance space
72 mm (2.835")
27.5 mm
(1.083")
38 mm
(1.496")
35.8 mm
(1.409")
DIN-rail mounting
Snap PLC onto the DIN rail
Panel mounting
Cut-out: 117 x 89mm
(WxH)(4.606”x 3.504”)
Notes: Removing the unit requires clearance space. Recommendation: approximately 40mm (1.58”)
For UL listed module, in order to meet the UL508 standard, panel-mount this device on
the flat surface of a Type 1 enclosure.
Wiring
This equipment is designed to operate only in SELV/PELV/Class 2/Limited Power
environments.
All power supplies in the system must include double insulation. Power supply outputs
must be rated as SELV/PELV/Class 2/Limited Power.
Do not connect either the ‘Neutral or ‘Line’ signal of the 110/220VAC to device’s 0V pin.
Do not touch live wires.
All wiring activities should be performed while power is OFF.
Install an external circuit breaker. Guard against short-circuiting in external wiring.
Use appropriate circuit protection devices.
Unused pins should not be connected. Ignoring this directive may damage the device.
Double-check all wiring before turning on the power supply.
Caution
To avoid damaging the wire, use a maximum torque of 0.5 N·m (5 kgf·cm).
Do not use tin, solder, or any substance on stripped wire that might cause the wire
strand to break.
Install at maximum distance from high-voltage cables and power equipment.

07/16
Unitronics
3
Wiring Procedure
Use crimp terminals for wiring; use 3.31 mm ² –0.13 mm² wire (12-26 AWG):
1. Strip the wire to a length of 7±0.5mm (0.270–0.300“).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.
Wiring Guidelines
Use separate wiring ducts for each of the following groups:
oGroup 1: Low voltage I/O and supply lines, communication lines.
oGroup 2: High voltage Lines, Low voltage noisy lines like motor driver outputs.
Separate these groups by at least 10cm (4"). If this is not possible, cross the ducts at a 90˚angle.
For proper system operation, all 0V points in the system should be connected to the system 0V
supply rail.
Allow for voltage drop and noise interference with input lines used over an extended distance.
Use wire that is properly sized for the load.
Earthing the product
To maximize system performance, avoid electromagnetic interference as follows:
Use a metal cabinet.
Connect the 0V terminal directly to the earth ground of the system.
Use the shortest, less than 1m (3.3 ft.) and thickest, 2.08mm² (14AWG) min, wires possible.
Inputs
This model comprises a total of 15 inputs in 4 groups.
1. I0 to I8 are digital inputs. They may be wired, in a group, as either npn or pnp.
2. I9 and I10 may be wired as either digital or analog inputs. These may be wired as either:
npn digital inputs
pnp digital inputs
analog (voltage) inputs
In addition, 1 input may be wired as a pnp input, while the other is wired as an analog input.
Note that if 1 input is wired as an npn input, the other may not be wired as an analog input.
3. AN2 and AN3 are analog (current) inputs that may be wired using 2, 3, or 4 wires.
4. Analog Input 0 and 1 can function as either thermocouple or PT100 inputs; each PT100 signal
has its own CM signal.

07/16
4
Unitronics
Digital Inputs, Controller’s Power Supply
Note: The inputs are arranged in two groups. You can wire one group as npn and the other as pnp,
or wire both groups as npn, or as pnp. In either case, the npn/pnp pins must be connected.
Input wiring, npn (sink)
Input wiring, pnp (source)
Input wiring (I0-I8), pnp (source), (I9-I10), npn (sink)
Analog Inputs
Note: Shields should be connected at the signal source.
Analog Input wiring, current, 2 or 3 wire, AN2
and AN3
Analog Input wiring, current, 4 wire, AN2 and
AN3
Analog Input wiring, voltage, AN4 and AN5
Note: If either I9 or I10 is wired as an npn digital input, the remaining input may not be wired as an
analog input.

07/16
Unitronics
5
Thermocouple
Type
Temp. Range
Wire Color
ANSI
(USA)
BS1843
(UK)
mV
-5 to 56mV
B
200 to 1820˚C
(300 to 3276˚F)
+Grey
-Red
+None
-Blue
E
-200 to 750˚C
(-328 to 1382˚F)
+Violet
-Red
+Brown
-Blue
J
-200 to 760˚C
(-328 to 1400˚F)
+White
-Red
+Yellow
-Blue
K
-200 to 1250˚C
(-328 to 2282˚F)
+Yellow
-Red
+Brown
-Blue
N
-200 to 1300˚C
(-328 to 3214˚F)
+Orange
-Red
+Orange
-Blue
R
0 to 1768˚C
(32 to 3214˚F)
+Black
-Red
+White
-Blue
S
0 to 1768˚C
(32 to 3214˚F
+Black
-Red
+White
-Blue
T
-200 to 400˚C
(-328 to 752˚F)
+Blue
-Red
+White
-Blue
Thermocouple 0: use T- Input as
negative input and T+ as positive.
Thermocouple 1: use T- Input as
negative input and T+ as positive.
RTD
PT100 (Sensor 0): use both inputs related to CM
signal
PT100 (Sensor 1): use both inputs related to CM
signal
4 wire PT100 can be used by leaving one of the
sensor leads unconnected.
Digital Outputs, Outputs’ Power Supply
PNP Outputs
+VO is the power supply input for pnp outputs O5–O6.

07/16
6
Unitronics
Relay Outputs
Increasing contact life span
To increase the life span of your contacts & protect the unit from potential damage by reverse-EMF,
connect:
A clamping diode in parallel with each inductive DC load
An RC snubber circuit in parallel with each inductive AC load
AC
DC
Analog Outputs
Current/voltage connections
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole
discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or
temporarily withdraw any of the forgoing from the market.
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of
merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in
this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising
out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other
third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them
DOC05014-B9 07/16
Other manuals for Jazz JZ20-UA24
1
This manual suits for next models
1
Table of contents
Other Unitronics Recording Equipment manuals
Popular Recording Equipment manuals by other brands

Siemens
Siemens Trunk Interface II Series installation instructions

DAELECTRONICS
DAELECTRONICS ICTRL-R-MINI Operational manual

Elan
Elan Z-025 installation manual

Nice
Nice BiDi-Shutter Instructions and warnings for installation and use

Fbt
Fbt MS02-CD3/DG Instructions for use

LAWO
LAWO mc256 MKII Technical manual