
2.2.3 System Control Principle
N o rm a l op era tio n
Normal mode: It means that the UPS has normal input mains, the rectifier and inverter operate normally, the load is supplied
by the inverter, the battery circuit breaker is closed, and the battery is in stable floating charge state.
Parallel System As the UPS single module outputs are connected in parallel, the system checks that the inverter control
circuits are perfectly synchronized with one another and with the bypass in terms of both frequency and phase, and that they
have the same output voltages. Current supplied to the load is automatically divided among UPSs. A warning message
appears while synchronization is in progress.
M ains ab no rm al
When the mains fails or is abnormal, the rectifier will stop working automatically, and the load will be catered by the battery
output (through inverter). The length of the operation time in battery mode depends on the load and the battery capacity.
During this period, if the battery voltage falls to the EOD voltage and the mains still has not been recovered, the inverter will
stop working automatically, and the UPS operator control and display panel will display corresponding alarm messages. If the
system uses split bypass configuration and the bypass is normal, the system will transfer to bypass.
M ains recovery
When the mains resumes normal within allowable time, the rectifier will start automatically and supply the load and charge the
battery again. Therefore, the power supply to the load will not be interrupted.
Battery disconn ection
To disconnect the external battery from the UPS system for maintenance, use the external isolating switch. At this time,
except for the battery backup function upon mains failure, other functions and all the steady state performance of the UPS
will not be affected.
U PS m od ule failure
In case of inverter failure and output fuse blowout, the load will automatically transfer to the bypass, and the output power
supply will not be interrupted. In this situation, please contact the local customer service center of Vertiv for technical support.
Parallel System In the event of a fault in a UPS module, it will automatically exit from the parallel system. If the system is still
capable of providing the required load, the remaining modules will continue to supply the load with no interruption. If the
remaining modules are no longer capable of fulfilling the power requirements, the load will automatically transfer to the
bypass.
O ve rloa d
If the inverter is overloaded or the inverter current remains outside the specifications (refer to Table 12.6 on page185) longer
than the specified time, the load will automatically transfer to the bypass without power interruption. If both the overload and
the current are reduced to a level within the specified range, then the load will be transferred back to the inverter. In case of
output short circuit, the load will be transferred to the bypass, and the inverter will shut down. Five minutes later, the inverter
will start up automatically. If the short circuit is removed at this point, the load will be transferred back to the inverter. The
transfer is determined first of all by the features of the protective device of the system.
In the above two situations, the UPS operator control and display panel will display alarm messages.
2 Overview
10
Vertiv™ Liebert® EXM2 UPS User Manual