Luminaire Package contains:
Foil SRD Luminaire
Connuous mounng kit
Suspension kit (supplied separately)
contains:
4x Clutches
4x suspension wires
4x ceiling cup sets.
Installaon procedure:
1. Mark out and install
suspension wires. See table
for xing centers (xings by
others).
2. Fit clutches to luminaire.
Ensure that the security tab is
returned to a level posion
to prevent accidental release
of the clutch.
3. Oer up the
luminaire
and feed
wires into
clutches. NB
Check body
orientaon—arrows must be aligned to
each other.
4. Level to nal posion.
5. Fix to wall if required at start of run:
(xings by others).
6. Fix to adjacent luminaires or inlls using
connecng screws supplied.
For 400 and 800mm inlls fold securing
tabs to support the body on adjacent
luminaires during xing.
For 1200, 1800
and 2200mm
inlls, use wire
suspension kit
as with
luminaires.
Do not remove acousc pads—move
aside to access xings.
7. Remove the terminal access screw and
bend up the tab to access terminal blocks.
If luminaire is equipped with EM or EP,
remove 5 screws to release enre
geartray.
8. Make electrical connecons. Add supply
to next luminaire as required (Flex and
addional gland by others). Connect
baery wires on EM/EP ngs (see dia)
9. Re-t the terminal access screw. For EM/
EP luminaires, ret 5 screws to secure
geartray. Ensure serrated washer is re-
ed for earth connuity.
10. Fit endcap at end of row using nuts
supplied.
Product length
(A)
Suspension
centers (B)
Suspension
centers (C)
Weight
(Kg)
Weight with
EM (Kg)
luminaires 2200 2000 250 23.4 23.6
Inll 400 400 200 250 4-
Inll 800 800 600 250 8-
Inll 1200 1200 1000 250 12 -
Inll 1800 1800 1600 250 18 -
Inll 2200 2200 2000 250 22 -
Terminal access
Uplight diuser
Wiring
channel
Main geartray
assembly
Wire dy tabs
Acousc absorber
Suspension Clutch
Endcap
(supplied
separately)
Sensor/EM
head locaon
12
34
Terminal
access
screw
EM Baery
locaon on
reverse
For emergency fittings the Florin downlight will be supplied with an "open area" lens, the "escape route" lens (corridor) will be packaged separately and can be swapped as appropriate.
Florin with open area lens