UTC Fire and Security Kidde Fire Systems Gemini II Multi-Hazard User manual

A UTC Fire & Security Company
Effective: March 2007
K-84-003
Gemini™ II Multi-Hazard
Conventional Suppression Control System
P/N 84-32200X-X0X
FEATURES
• Agency Approvals
• UL 864 Listed # S2422/S3743
• ULC-S527-99 Listed # S2422/ULC CS1010
• FM Approved # 3008679 (3010)
• CSFM Approved # 7165-1076:160
• MEA (NYC) Accepted # 140-02-E
• Microprocessor Based
• Conventional Control with Intelligence
• Completely and Easily Field Programmable
• Distributed Remote Hazard Control
• Remote Display Units in Local or Global Mode
• 80-Character Alphanumeric LCD Display
• 270-Event History Log
• Digital Release Countdown
• Listed for a Wide Range of Suppression Systems
• Kidde FM-200® , FE13™ , CO2& Halon Clean Agent
Suppression Systems
• Kidde IND™ Dry Chemical & WHDR™ Wet
Chemical Systems
• Sprinkler Supervisory, Deluge/Preaction &
Foam/Foam-Water Systems
DESCRIPTION
The Kidde Gemini II Multi-Hazard is the technologically
most advanced Conventional Suppression (agent releas-
ing) Control System available to the suppression industry
today. Employing distributed intelligence architecture, the
Kidde Gemini II system enables highly reliable monitoring
and suppression control for up to eight separate hazards.
The system consists of a master Main Control Panel
(MCP) which is a microprocessor based, field-config-
urable single hazard panel with a plethora of intelligent
features including LCD Display, digital Release Count-
down, password protected Menu System, Event History
Log, Configuration Log, Walk Test and Remote Battery
Test capability. As shown in Figure 1, this basic system
can be field-expanded to be a large eight hazard Control/
Display System with up to seven Remote Hazard Units
(RHU) and sixteen Remote Display Units (RDU), all of
which reside on a fault tolerant communications network.
The MCP and each RHU is intended to be physically
located in the space it is meant to protect. Since the MCP
and RHUs are computer-controlled, each one can act in
stand-alone mode in the event of damage to any of the
other panels. Under worst case fault conditions the only
protection threatened is within the space where the dam-
age occurred. All other protected areas continue to func-
tion normally. System reliability is substantially improved
since wiring for each protected space is only run a short
distance to the local panel.
Featuring a compact and aesthetically pleasing design,
the Gemini II is ideally suited for modern commercial,
high-tech and industrial applications. It is approved for
Kidde FM-200®, FE-13™ and CO2Clean Agent Systems
as well as Kidde IND™ Dry Chemical & WHDR™ Wet
Chemical Systems. The Gemini II is also listed for Sprin-
kler Supervisory Service and for Halon, Foam/Foam-
Water and Deluge/Pre-Action Systems.
MAIN CONTROL PANEL (MCP)
MCP POWER SUPPLY
The MCP operates on 120/240 Vac 50/60 Hz Power Sup-
ply. The Power Supply Unit is rated 4 Amps at 24 Vdc
and is provided with a Battery Charger to charge a 24
Vdc backup battery with a capacity 12 to 66 AH. The bat-
tery may be sized for 24 hour standby with 5 minutes
alarm or for 90 hour standby with 10 minutes alarm,
depending on the suppression system. The Power Sup-
ply is supervised and causes an immediate changeover
to battery in the event of loss of AC input or drop in input
voltage.

- 2 -
MCP DISPLAY-CONTROL MODULE
The MCP Display-Control Module is provided with an 80-
character alphanumeric LCD Display, status LEDs and
System Control and Menu Control buttons as shown in
Figure 2.
Figure 2. MCP Display-Control Module
MCP INPUT AND OUTPUT CIRCUITS
The MCP is a Single Hazard Control Panel and is pro-
vided with the following Input and Output Circuits:
• 2 Style B Class B or Style D Class A Initiating Cir-
cuits
>> Up to 40 Conventional Fenwal Ionization and
Photoelectric Smoke Detectors and any number
of contact-closure Heat Detectors on each cir-
cuit.
>> Wiring style selection is by on-board links without
any additional hardware.
>> Programmable to release agent either on single
or cross-zone input.
>> Also programmable to delay Agent Release by 0
to 60 seconds.
•1 Style B Class B Manual Release Circuit
>> Overrides any Abort Input
>> Programmable to delay Agent Release by 0 to
30 seconds.
• 1 Style B Class B Abort Circuit
>> May be disabled for CO2 and Deluge/Pre-Action
systems.
>> Programmable for up to four different Abort
Modes.
>> Also programmable to generate Abort pulse tone
when activated.
• 1 Style B Class B Supervisory Circuit
• 1 Style B or Style D Class A Waterflow Circuit
>> Wiring style selection is by on-board links without
any additional hardware.
>> Provides Non-Silenceable notification.
•2 Style Y Class B or Style Z Class A Indicating
Appliance Circuits
>> Wiring style selection is by on-board links without
any additional hardware.
>> Rated 2.5 Amps total at 24 Vdc for polarized
Audio-Visual devices.
>> Individually programmable to operate on 1st
Alarm, Waterflow, Agent Pre-Release, Manual
Release and Agent Release conditions and to
generate Silent, Steady, 60 bpm Pulse, 120 bpm
Pulse and Temporal sound patterns either in
Silenceable or Non-Silenceable mode.
MAIN
CONTROL
PANEL
POWER ON ALARM TROUBLE
SUPERVISORY SIGNAL
SILENCED
RESET ALARM
SCROLL
SYSTEM
CONTROLS
SIGNAL
SILENCE SUP/TBL
SCROLL
MENU
CONTROLS
CANCEL
ACCEPT
09-17-02
ALM00 SUP0 TBL00
MCP v1.AD
SYSTEM STATUS NORMAL
12:00
R
R
RHU#1
w/ Display
RDU # 1 for MCP
RDU # 2 for RHU # 1
Main Control Panel
RHU#2
w/o Display
Class A, Style 7
RS-485 Data Pairs. Max.
length 4,000 ft. each.
120/240
Vac
24 Vdc
24 Vdc
24 Vdc
RDU # 4 for RHU # 2
RDU # 3 for RHU # 2
RHU#2
RDU # 5 for
120/240
Vac
120/240
Vac
Note: The system must comprise 1 MCP.
To expand, add up to 7 RHUs and
up to 16 RDUs to the network.
POWER
REMOTE DISPLAY UNIT
R
R
ALARM
SCROLL
SUP/TBL
SCROLL
SYSTEM
CONTROLS
POWER
REMOTE DISPLAY UNIT
R
R
ALARM
SCROLL
SUP/TBL
SCROLL
SYSTEM
CONTROLS
POWER
REMOTE DISPLAY UNIT
R
R
ALARM
SCROLL
SUP/TBL
SCROLL
SYSTEM
CONTROLS
POWER
REMOTE DISPLAY UNIT
R
R
ALARM
SCROLL
SUP/TBL
SCROLL
SYSTEM
CONTROLS
POWER
REMOTE DISPLAY UNIT
R
R
ALARM
SCROLL
SUP/TBL
SCROLL
SYSTEM
CONTROLS
MAIN
CONTROL
PANEL
POWER ON ALARM TROUBLE
SUPERVISORY SIGNAL
SILENCED
RESET ALARM
SCROLL
SYSTEM
CONTROLS
SIGNAL
SILENCE SUP/TBL
SCROLL
MENU
CONTROLS
CANCEL
ACCEPT
R
R
SIGNAL
SUPERVISORYPOWER ON ALARM
UNIT
TROUBLE SIGNAL
SUP/TBL
SCROLL
REMOTE
HAZARD ALARM
SCROLL
CONTROLS
SYSTEM
RESET
SILENCE
SILENCED
R
R
Figure 1. Typical System Block Diagram

- 3 -
• 1 Style Y Class B Agent Release Circuit
>> Programmable to operate (a) 1 or 2 ganged 24
Vdc Kidde Solenoid Control Heads for clean
agent or CO2systems or (b) 1 FM Group A, B, D,
E or G Solenoid for Deluge/Pre-Action Systems.
>> A second programmable Release Circuit is also
provided to operate 1 Stop Valve for systems
using Clustered Agent Cylinders (a common cyl-
inder bank protects multiple hazards and Stop
Valves direct Agent to the affected area).
• Relay Outputs
>> 1 Form C System Alarm Relay
>> 1 Form C System Trouble Relay
>> 1 Form C Programmable Relay
• Optional Relay Board (ORB)
>> 5 Form C Programmable Relays
MCP CONSTRUCTION
The MCP enclosure is designed for surface mounting
and is rated NEMA 1 for indoor use. It is constructed of
18 Gauge steel, painted red and kept closed by a steel
door with a key-lock. All operator interface switches and
indicators are located behind the locked cover. The
enclosure is large enough to house two 12 AH 12 Vdc
batteries for backup power supply. Battery Enclosures
are available for larger capacity batteries. A trim-ring is
available for flush mounting.
REMOTE HAZARD UNIT (RHU)
RHU POWER SUPPLY
The Power Supply Unit in the RHU is the same unit as in
the Main Control Panel.
RHU DISPLAY-CONTROL MODULE
Remote Hazard Units are available either with or without
a Display-Control Module. When used, as shown in Fig-
ure 4, the RHU Display-Control Module is similar to that
of the MCP with the exception of the Menu Control but-
tons, which are provided only on the MCP. RHU Displays
can be programmed to operate either in local or global
mode.
Figure 4. RHU Display-Control Module
RHU INPUT AND OUTPUT CIRCUITS
Each RHU is also a Single Hazard Panel and is similar to
the Main Control Panel being provided with the same
Input and Output Circuits (with the exception of the three
System Relays). The Optional Relay Board (ORB) can
also be mounted to the RHU.
RHU CONSTRUCTION
When using the optional Display-Control Module, the
RHU Enclosure is similar to that of the MCP. If this option
SIGNAL
SUPERVISORYPOWER ON ALARM
UNIT
TROUBLE SIGNAL
SUP/TBL
SCROLL
REMOTE
HAZARD ALARM
SCROLL
CONTROLS
SYSTEM
RESET
SILENCE
SILENCED
R
R
RHU v1.AD
LOCAL STATUS NORMAL
12:00
ALM00 SUP0 TBL00
09-17-02
Detection Circuit # 1
Style B or D
Detection Circuit # 2
Style B or D
Smoke and
Heat Detectors
Waterflow Input
Style B or D
Sprinkler System
Pull Station
Manual Release
Abort
Style B
Abort Station
Supervisory Signal
Release Circuit
Auxiliary Power 1
24 Vdc 24 Vdc
(Not resettable) Auxiliary Power 2
Inputs from
field devices
Outputs
RS485
Port
RS-485 Data Highway
1 or 2 Clean Agent Control Heads
1 Deluge System Solenoid
1 or 2 C System Control HeadsO2
To Remote Display Units
To and from other
System Units
Form C Alarm Relay
Form C Trouble Relay
Form C Prog. Relay
Auxiliary Functions
- Equipment Shutdown
- Repeat Annunciation
- DACT (MCP only)
PUSH
PULL
FIRE FIRE
PUSH / HOLD
SUPPRESSION
SYSTEM ABORT
Style B
Style B
5 Form CProg. Relays
on Option Relay Board
Indicating Circuit # 1
Style Y or Z
Indicating Circuit # 2
Style Y or Z Audible and Visual
Indicating Devices
All relays except those on ORB
are applicable to the MCP only.
KIDDE
Style Y
AGENT RELEASING LOGIC
Figure 3. MCP and RHU Hazard Block Inputs and Outputs

- 4 -
is not selected, the RHU Enclosure has no viewing win-
dow.
REMOTE DISPLAY UNIT (RDU)
RDU POWER SUPPLY
The RDU operates on 24 Vdc Power received from the
non-resettable Auxiliary 24 Vdc Power Output of the
MCP or associated RHU or any other UL Listed 24 Vdc
Power Supply Unit.
RDU DISPLAY-CONTROL MODULE
The RDU is a “display only” unit and can be programmed
to operate either in local or global mode. In local mode, it
mimics the Display of the MCP or the RHU to which it is
assigned. In global mode, it mimics the display of the
MCP. The RDU Display-Control Module provides a LCD
Display, one Power/Communication Status LED and Sys-
tem Controls as shown in Figure 5.
Figure 5. RDU Display-Control Module
RDU HAZARD BLOCK
RDUs do not control suppression systems, but optionally,
may be used to accept one Manual Release and one
Abort input from the local protected zone to which the
associated MCP or RHU is assigned.
RDU CONSTRUCTION
The RDU Backbox is constructed of 18 gauge steel,
painted beige and kept closed by the Display-Control
Module front plate. The front plate itself is constructed of
18 gauge steel and is painted red.
SPECIAL GEMINI II CONFIGURATIONS
As shown in Figure 6, due to special Canadian annuncia-
tion requirements, MCPs listed by ULC of Canada are
designed to be suitable for mounting one to three LED
Display Modules. Each LED Display Module pertains to
one zone of protection and provides 16 zone-specific
LEDs over and above the five System LEDs provided on
the MCP Display-Control Module. Enclosures of ULC
listed MCP and RHU units are provided dead-front pan-
els.
POWER
RDU v1.AD
SYSTEM STATUS NORMAL
12:00 09-17-02
ALM00 SUP0 TBL00
REMOTE DISPLAY UNIT
R
R
ALARM
SCROLL
SUP/TBL
SCROLL
SYSTEM
CONTROLS
ID
TBL - COMMS FAULT
TBL - PANEL AC POWER
ABORT CIRCUIT ON
SIGNAL SILENCED
ALM - WATERFLOW CKT
SUPERVISORY CKT ACTIVATED
TBL - DETECTOR ZONE 1
TBL - MANUAL RELEASE
ALM - MANUAL RELEASE
TBL - DETECTOR ZONE 2
TBL - WATERFLOW CKT
TBL - ABORT CKT
TBL - SUPERVISORY CKT
TBL - GROUND
ALM - DETECTOR ZONE 1
ALM - DETECTOR ZONE 2
ID
TBL - COMMS FAULT
TBL - PANEL AC POWER
ABORT CIRCUIT ON
SIGNAL SILENCED
ALM - WATERFLOW CKT
SUPERVISORY CKT ACTIVATED
TBL - DETECTOR ZONE 1
TBL - MANUAL RELEASE
ALM - MANUAL RELEASE
TBL - DETECTOR ZONE 2
TBL - WATERFLOW CKT
TBL - ABORT CKT
TBL - SUPERVISORY CKT
TBL - GROUND
ALM - DETECTOR ZONE 1
ALM - DETECTOR ZONE 2
ID
TBL - COMMS FAULT
TBL - PANEL AC POWER
ABORT CIRCUIT ON
SIGNAL SILENCED
ALM - WATERFLOW CKT
SUPERVISORY CKT ACTIVATED
TBL - DETECTOR ZONE 1
TBL - MANUAL RELEASE
ALM - MANUAL RELEASE
TBL - DETECTOR ZONE 2
TBL - WATERFLOW CKT
TBL - ABORT CKT
TBL - SUPERVISORY CKT
TBL - GROUND
ALM - DETECTOR ZONE 1
ALM - DETECTOR ZONE 2
SUPERVISORYPOWER ON ALARM
SCROLL
ALARM
SCROLL
SUP/TBL
CANCEL
ACCEPT
CONTROL
MAIN
PANEL
SILENCED
SIGNAL
TROUBLE
SILENCE
SIGNAL
CONTROLS
MENU
SYSTEM
CONTROLS
RESET
II
RTM
R
GEMINI
Figure 6. ULC Listed Main Control Panel

- 5 -
GEMINI II SYSTEM INTELLIGENCE
The Gemini II System allows operator access to its intelli-
gence via the Menu Control buttons on the Main Control
Panel. The Main Menu, which is enabled by pressing any
Menu Control Button (except Cancel) on the Main Con-
trol Panel (MCP), is structured per the architecture
shown in Figure 7. The Set, Isolate and Test functions
are password protected to limit access to authorized per-
sonnel only.
Figure 7. Menu Structure
The Set Function allows the operator to change pass-
word, set current date and time and the site-specific
operating configuration for the entire system. When the
System is initialized, the MCP downloads the operating
configuration to the RHUs and RDUs.
The List Function enables the operator to list the system
operating configuration, any isolated devices, registered
RHUs and RDUs and the Event History Log.
The Event History Log is a compilation of all Alarm,
Trouble, Supervisory and Event messages stored in non-
volatile memory. A maximum of 270 events can be stored
and the occurrence of a new event beyond the maximum
capacity erases the first. The Event Log can be cleared
by using the Gemini II ISP (In-Service Programming) Util-
ity CD-ROM.
The Isolate Function is used to isolate and de-isolate
input and output circuits on the MCP and all remote units.
The Test Function allows the operator to conduct a sys-
tem Walk test and Battery test on the MCP and all remote
units.
IN-SERVICE PROGRAMMING
The ISP Utility is a software program used to clear the
Event History Log of a Gemini II System and to upload
feature enhancements to its operating system. The ISP
Utility CD-ROM operates on IBM compatible computers
running Windows 95, 98, 2000, XP, ME or NT and is con-
nected to the ISP port on the MCP, RHU and RDU via
Kidde P/N 74-100016-003 PEGAsys™ Telephone Cable
with DB9 Adapter.
TECHNICAL SPECIFICATIONS
MAIN CONTROL PANEL (MCP)
REMOTE HAZARD UNITS (RHU)
REMOTE DISPLAY UNITS (RDU)
Main Menu
Set
List
Isolate
Test
Input Supply: 120/240 Vac 50/60 Hz
Current Draw: 3.0 Amps @ 120 Vac or
1.4 Amps @ 240 Vac
Output Rating: 4.0 Amps @ 24 Vdc
Charger Output: 3.5 Amps max @ 27.3 Vdc
Aux. Power Output: 0.5 Amps max @ 24 Vdc
Notification Output: 2.5 Amps total @ 24 Vdc
Quantity per System: One
Enclosure Rating: NEMA 1
Enclosure Material: 18 gauge steel, painted red
Dimensions (W x H x D) 15.5 in. x 15.5 in. x 5.0 in.
(393 mm x 393 mm x 127 mm)
Ambient Temperature: 32º to 120ºF (0º to 49ºC) max.
Relative Humidity: 93% non-condensing max.
Input Supply: 120/240 Vac 50/60 Hz
Current Draw: 3.0 Amps @ 120 Vac or
1.4 Amps @ 240 Vac
Output Rating: 4.0 Amps @ 24 Vdc
Charger Output: 3.5 Amps max @ 27.3 Vdc
Aux. Power Output: 0.5 Amps max @ 24 Vdc
Notification Output: 2.5 Amps total @ 24 Vdc
Quantity per System: Maximum 7 (3 for ULC Systems)
Enclosure Rating: NEMA 1
Enclosure Material: 18 gauge steel, painted red
Dimensions (W x H x D) 15.5 in. x 15.5 in. x 5.0 in.
(393 mm x 393 mm x 127 mm)
Ambient Temperature: 32º to 120ºF (0º to 49ºC) max.
Relative Humidity: 93% non-condensing max.
Input Supply: 24 Vdc (nominal)
Quantity per System: Maximum 16
Backbox Rating: NEMA 1
Backbox Material: 18 gauge steel, painted beige
Front Plate Material: 18 gauge steel, painted red
Dimensions (W x H x D): 8.0 in. x 4.45 in. x 2.25 in.
(203 mm x 113 mm x 57 mm)
Ambient Temperature: 32º to 120ºF (0º to 49ºC) max.
Relative Humidity: 93% non-condensing max.

A UTC Fire & Security Company
400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
www.kiddefiresystems.com
This literature is provided for informational purposes only. KIDDE-FENWAL, INC.
assumes no responsibility for the product’s suitability for a particular application. The
product must be properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or ques-
tion, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
K-84-003 Rev AB © 2007 Kidde-Fenwal Inc. Printed in USA
ORDERING INFORMATION
For detailed design, installation, configuration and additional ordering information, refer to the Kidde Gemini II Design,
Installation, Operation & Maintenance Manual P/N 06-235975-001.
CONTROL PANELS PART
NUMBER
Gemini II Main Control Panel (MCP-ULI)
120/240 Vac 50/60 Hz Input. Stand-alone Unit controls 1 Hazard Block. NEMA 1 Enclosure will house two 12 Vdc 12 AH
Batteries (order selected batteries separately).
84-322001-001
Gemini II Main Control Panel (MCP-ULI/ULC)
120/240 Vac 50/60 Hz Input. Stand-alone Unit controls 1 Hazard Block. NEMA 1 Enclosure with 1 pre-mounted LED Dis-
play Module and dead-front will house two 12 Vdc 12 AH Batteries (order selected batteries separately).
84-322001-010
Gemini II Remote Hazard Unit with Display (RHU-ULI)
120/240 Vac 50/60 Hz Input. Networked Unit controls 1 Hazard Block. NEMA 1 Enclosure will house two 12 Vdc 12 AH Bat-
teries (order selected batteries separately).
84-322002-001
Gemini II Remote Hazard Unit w/o Display (RHU-ULI)
120/240 Vac 50/60 Hz Input. Networked Unit controls 1 Hazard Block. NEMA 1 Enclosure will house two 12 Vdc 12 AH Bat-
teries (order selected batteries separately).
84-322002-002
Gemini II Remote Hazard Unit with Display (RHU-ULI/ULC)
120/240 Vac 50/60 Hz Input. Networked Unit controls 1 Hazard Block. NEMA 1 Enclosure with dead-front will house two 12
Vdc 12 AH Batteries (order selected batteries separately).
84-322002-005
Gemini II Remote Display Unit (RDU) 24 Vdc Input. Networked Unit controls 1 Manual Release and 1 Abort Circuit. Com-
plete with Backbox. 84-322003-001
Gemini II Optional Relay Board (ORB) Mounted on MCP or RHU Board. Provides 5 Form C Programmable Relays. 84-322001-009
Gemini II LED Display Module (ULI/ULC) Mounted on MCP. Max 2 per Canadian system. 84-322001-013
ACCESSORIES
12 AH, 12 Vdc Sealed Lead Acid Battery (2 required for 24 Vdc, 4 required for 24 AH, 24 Vdc) 06-115915-047
17 AH, 12 Vdc Sealed Lead Acid Battery (2 required for 24 Vdc, 4 required for 34 AH, 24 Vdc) 06-115915-046
33 AH, 12 Vdc Sealed Lead Acid Battery (2 required for 24 Vdc, 4 required for 66 AH, 24 Vdc) 89-100052-001
Gemini II Battery Cabinet for 2 of 33 AH Batteries 84-322004-001
Resistor Kit (10 ea. 10 Kohm, 5%, 0.5 Watt, EOLRs, 5 ea. 3.9 Kohm, 5%, 0.5 Watt EOLRs and 1 ea. 2 Kohm, 5%, 1 Watt
Releasing Circuit Dummy Resistor)
06-129923-001
Gemini II Design, Installation, Operation and Maintenance Manual 06-235975-001
Gemini II In-Service Programming (ISP) Utility CD-ROM Rev AD 84-322005-001
Kidde is a registered trademark of Kidde-Fenwal, Inc.
Gemini and PEGAsys are trademarks of Kidde-Fenwal, Inc.
FM-200 is a registered trademark of the Great Lakes Chemical Corporation.
FE-13 is a registered trademark of DuPont.
This manual suits for next models
8
Table of contents
Other UTC Fire and Security Control System manuals
Popular Control System manuals by other brands

Cardin Elettronica
Cardin Elettronica ACD-148 manual

Minitech
Minitech Mini-Mill Series user guide

Uponor
Uponor I-75 installation guide

Phason
Phason AutoSort Connect Installation and getting started guide

OBSIDIAN CONTROL SYSTEMS
OBSIDIAN CONTROL SYSTEMS NETRON EN12 installation guide

Aritech
Aritech CS-152 user manual