UTC Fire and Security Chubb VS-MKII User manual

V
V
VS
S
S-
-
-M
M
MK
K
KI
I
II
I
I
C
C
Co
o
on
n
nt
t
tr
r
ro
o
ol
l
l
S
S
Sy
y
ys
s
st
t
te
e
em
m
m
Installation, Operation and
Maintenance Manual
© Chubb Fire Safety 2010 Company Confidential

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 2 of 63
Publication Information
Development
Craig Hafey
Technical Manager - Vehicle Fire Suppression
Chubb Fire & Security Pty Ltd
149-155 Milton St
Ashfield NSW 1800
Tel: +61 (2) 9581-6364
Publication:
Version: Version 1.1
Date: 10-09-12
Title: VS-MKII Control System – Installation, Operation and Maintenance Manual
© Chubb Fire and Security Pty Ltd 2012. All rights reserved.
This work is copyright. Permission is given to Chubb Fire & Security personnel to make copies of this work or part thereof. This work or
part thereof may not be reproduced for the purpose of resale or hire to third parties. For permissions outside the conditions described in
the Australian Copyright Act 1968, apply in writing to Chubb Fire & Security Pty Ltd (ACN 000 067 541).
Chubb Fire & Security Pty Ltd does not give warranty nor accept responsibility or liability in any relation to the content of this work.
Contact information and web addresses were correct at the time of publication.

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 3 of 63
Pre-Face
Document History:
Version
Summary of Change
1.0
Original
1.1
Page 3 - Changed contact number
Page 8 - Primary power monitoring - changed “<20 Volts” to “<17 Volts”
Page 11 - Updated figure 9
Page 13 - Updated tables 2 & 3
Page 24 – Updated table 9
This manual is an uncontrolled document. Chubb Fire & Security Pty Ltd (“Chubb”) reserves the
right to alter this manual at any time in accordance with our policy of continuous development.
Chubb welcomes feed back regarding this manual and associated equipment. For further
information or feedback, contact Chubb Fire & Security on 1300 369 309.

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 4 of 63
General Information
Contents:
Publication Information ...................................................................................................................2
Pre-Face.........................................................................................................................................3
General Information........................................................................................................................4
Topic 1: VS-MKII Control System....................................................................................................6
Introduction .................................................................................................................................6
Standard features........................................................................................................................7
Models ........................................................................................................................................7
Power Supply..............................................................................................................................8
Primary power monitoring 8
Rechargeable back up battery 9
Topic 2: Installation.......................................................................................................................10
Control Module..........................................................................................................................11
Inputs 11
Outputs 11
Configuring the module 12
Channels 13
Programming - configuration channels 14
Configuration channels (A-Y) 17
Jumper links 29
Shutdown bypass 30
Installing the MKII Module 31
VS-MKII Display Panel & Audible Alarm....................................................................................31
Display settings 31
Display controls and indicators 33
Audible Alarm 34
Installing the display and audible alarm 34
Electrical Manual Release Unit..................................................................................................36
Operation 37
Installing the electrical manual release unit 37
Installation – Multiple Units 38
Solenoids ..................................................................................................................................40
Installing a solenoid 41
Linear Heat Detection Cable (LHD)...........................................................................................42
Installing LHD cable 42
Pressure switches.....................................................................................................................44
Pressure low switch 44
Discharge pressure switch 44
Multiple PEFS Cylinder Installations 45
Topic 3: Commissioning................................................................................................................47
Acceptance of Test 47
Topic 4: Troubleshooting...............................................................................................................48
Display Panel – Fault Indications 48
Control module – Fault Indications 49
Replacing the internal back up battery 51
Troubleshooting with Terminal software ....................................................................................53
TeraTerm commands 56
Troubleshooting Tables.............................................................................................................60
Power supply problems 60
Alarm problems 60
Other fault indicators 61
Hardware Problems 62
Feedback Form.............................................................................................................................63

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 5 of 63
About this manual:
This manual is written for those who perform tasks associated with the installation, operation and
maintenance of the VS-MKII Control System.
Chubb Fire & Security Pty Ltd (“Chubb”) assumes no responsibility for the application of any systems other
than those addressed in this manual. The technical data contained herein is limited strictly for informational
purposes only. All information contained in this manual is based on the latest product information available
at the time of preparation and Chubb reserves the right to make changes at any time without notice. Chubb
believes this data to be accurate, but it is published and presented without any guarantee or warranty.
Chubb disclaims any liability for any use that may be made by the data and information contained herein by
any party.
Systems are to be inspected, maintained, and tested only by qualified, trained personnel.
IMPORTANT: No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any
form or by any means, electronic, mechanical, photocopying, or otherwise without the prior written approval of
Chubb.
Warranty:
Chubb warrants to the original system purchaser (“Customer”) that each new fire system is free from defects
in material and workmanship under normal use for a period of twelve (12) months from the date of
commissioning. This warranty does not cover damage resulting from a party’s negligence, fault, misuse,
neglect or incorrect use of the product, abuse or fair wear and tear. In addition, the warranty does not cover
work required to be done to repair a defect or damaged caused by vandalism, fire, water, damage, power
surge or other circumstance outside of Chubb’s control. This warranty is conditional upon documented
evidence of proper maintenance, performed in accordance with the Fire System Owner’s Manual and
Maintenance Manual by qualified and trained personnel, using replacement parts that conform to original
design specifications. This warranty will be voided upon modification of the (i) installed and commissioned
System; (ii) use, condition and environment of the Customer’s equipment. Chubb will have no liability for any
statements, representations, guarantees, conditions or warranties not expressly stated in writing by Chubb.
Nothing in this warranty excludes, restricts or modifies the application of the provisions of any statute
(including the Trade Practices Act 1974 (Cth)) where to do so would contravene that statute or cause any
part of this warranty to be void.
Notwithstanding anything else in this document, Chubb will not be liable for:
4. any indirect, consequential or special or economic loss, cost, liability, damage or expense howsoever
arising; or
5. loss of profit, loss of use, loss of income, loss of rental or other benefit, loss of production, loss of actual
or potential business opportunity or loss of reputation.
Intended use:
A VS-MKII Control System is installed as part of a fire risk reduction strategy, as defined in a Fire Risk
Assessment.

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 6 of 63
Topic 1: VS-MKII Control System
Introduction
Designed to comply with and tested to the requirements AS 5062, the VS-MKII Control System (“MKII”)
comprises a control module, a remote display panel and audible alarm unit. The display panel provides
visual indication of system status, alarms, and faults and also allows manual extension of the equipment
shutdown delay.
Most industrial environments produce high levels of electrical noise, so the MKII has been compliance tested
to Australian Standard AS 61000.6.2:2006 for immunity to electromagnetic interference.
To minimize the effects of electromagnetic emissions from high energy sources the MKII input cables should
NOT be run parallel, or in close proximity to any cables or equipment that may produce high RF (radio
frequency) energy, e.g. cabling for RF transceiver antennas, inverters, motors etc.
Figure 1 – Typical MKII layout
All wiring and electrical connections must be installed in accordance with the customers requirements and/or
the equipment manufactures specifications. Power supply and equipment shutdown connections should
either be completed by the Customer/OEM or an approved contractor.
The MKII incorporates a rechargeable back up battery which will ensure a reliable alternative power source if
required.
The system design allows multiple configuration and programming options.

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 7 of 63
Standard features
•IP 65 rated control box •Variable engine shutdown delay periods 0 - 240 seconds
•Cylinder low pressure switch input •Variable shutdown delay extension period 0 - 240 seconds
•Discharge pressure switch input •Slimline operator display
•Equipment shutdown output •Ultrabrite mini LED's
•AS 5062 compliant features •Auto diming of LED's
•Supervised primary power supply •Manual dim push button
•Rechargeable Battery back-up •Discharged confirmation LED
•Supports electrical detection •System isolated LED
•Supervised detection circuit inputs •Varying audible alarms dependant upon operating state
•Single or dual circuit detection options •Vibration and shock tested
•Supervised electrical manual release
input •Event log with time and date stamp
•Supports electrical actuation •IP65 rated Deutsch connectors
•Supervised actuation output •
Operates audible and visual alarms and engine shutdown
even when manually discharged
Models
The VS-MKII control system is available in kit form and can be configured with one or two actuation outputs
(for use with Dual agent systems).
Figure 2 - VS-MKII Control System kit - Part No. 001-998
Figure 3 - VS-MKII Dual Control System kit- Part No. 001-999

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 8 of 63
Power Supply
The MKII operates on a 24 Volt primary power supply (20-30 Volt range). If the system is installed in
equipment that uses a 12 Volt power supply, a separate voltage converter will need to be installed to boost
the voltage. The system is protected from voltage surges up to 58 Volts
Figure 4 – Control module connections
The preferred power supply arrangement for the MKII is through an isolator or ignition circuit (Fig. 5).
Figure 5 – Power connector
Primary power monitoring
•When primary power is low (<17 Volts), lost or isolated a visual and audible power fault will initiate
after 10 seconds.
•All power faults are non-latching.
•The fault reporting of over a voltage condition is masked to allow for equipment that may be prone to
power fluctuations during normal and peak operation
Input & Output Connectors
Power Connector

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 9 of 63
•When the panel receives > 31 volts for a period in excess of 10 seconds the amber ‘POWER’ LED
will light up (Fig. 6) but no audible or visual fault will be generated. In this state, the batteries will not
be under charge.
Figure 6 – Over voltage
Note: The green ‘POWER’ LED remains lit in this state to indicate that the panel is operable
but visually the amber LED will appear brighter.
Rechargeable back up battery
The rechargeable battery pack provides an emergency power supply in the event that primary power is lost
or isolated. The system will be in fault when it is being powered by the back up battery but will still be
operable for a minimum 96 hours (typical) provided that the battery is fully charged (2 hour charge time).
Figure 7 – Back up battery
When the battery voltage drops below 11 volts the Amber Power LED will flash continuously until the voltage
drops below 9.8 volts. At which time the system will shutdown to prevent over discharge or damage to the
battery.

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 10 of 63
Topic 2: Installation
Depending on the type and size of equipment requiring protection, the MKII can be configured with multiple
actuation and detection devices.
Figure 8 – Typical fire system configuration
The MKII can be customised to suit just about any application. The settings that can be altered and the
degree to which they can be customised are detailed in the ‘Channels’ section on Page 11.
Each component of the MKII must be located and positioned according to its function.
Before installing any system component you should assess the intended location will;
•Provide access for operational and maintenance purposes.
•Provide a high degree protection from potential damage
•Be compliant with the Chubb specifications and customers requirements.
The recommended wire gauge size for all power, inputs and outputs of the MKII is as per the following table;
Diameter AWG size Amp Capacity
0.75mm 18 6
Table 1 – Wire gauge

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 11 of 63
Control Module
The control module (Fig. 4) comprises an IP65 rated enclosure and IP69 rated Deutsch DT series
connectors and is the heart of the system. It can be installed with the factory (“default”) settings or configured
to suit a specific requirement. The modules’ pin configuration is displayed in Figure 9.
Inputs
•2 x detection circuit inputs (supervised). Suitable for linear heat detection cable or
thermal probes. The control panel can be configured for four different detection functions.
The default configuration is single circuit detection.
•1 x manual discharge input (supervised). Operation of a switch connected to this input will
initiate alarm, system discharge and equipment shutdown functions.
•Cylinder pressure switch input
•Discharge pressure switch input
Note: both pressure switch inputs are configurable for N/O or N/C operation. The default
configuration is N/C (contacts closed = normal operation, contacts open = fault/discharge).
Outputs
•Actuation output (supervised) 1A @12V DC. The actuation output is capable of operating:
oA singe 12V 12W solenoid, or
oUp to 5 x .5amp squibs.
Note: The MKII Dual system has a second actuation output with the same capability as
the first.
•Shutdown output. Selectable contacts, N/O or N/C (default N/O), latching 3 pole relay
clean contact capable of switching 2A @ 30V DC.
•Auxiliary output. Selectable N/O or N/C (default N/O), latching relay clean contact capable
of switching 2A @ 30V DC.
•Buzzer output (supervised). Used to power buzzer for audible notification of fault, alarm
and shutdown functions.
Figure 9 - Control module pin configuration

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 12 of 63
Configuring the module
It is recommended that any configuration changes that are required to the default settings be carried out
before installation. It is preferable to use an external power supply to make configuration changes. When a
stable primary power supply is present the ‘PRIMARY POWER OK” LED on the PCB (Fig. 10) will be lit.
Figure 10 – Primary power LED
If an external power supply is not available, the back up battery circuit can be used to make the required
configuration changes. All MKII modules are supplied from the factory with a charged battery
To activate the back up battery on the MKII module (Fig. 11), a loop (Fig. 12) must be made between
terminal 3 & 4 (Fig. 13) on the module’s power supply connector (Fig. 14).
Figure 11
Figure 12
Figure 13
Figure 14
User interface
The default settings on the MKII can be changed via a software interface or manually via the user interface
which is located on the PCB. Settings are manually configurable using a simple channel and dip switch
system which is displayed in Figure 15.
Figure 15 – User interface module PCB
1
2
3
4
4
3
User Interface

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 13 of 63
The user interface is surrounded by a thick
white border and the controls and indicators
consist of;
•A push button labelled ‘Channel’.
•A push button labelled ‘PROG/SAVE’.
•A 7-segment display.
•8 LED indicators numbered 1 to 8 from left
to right.
•An 8-way DIP switch.
Figure 16 – User interface detail
Channels
There are two categories of ‘Channels’ used with the MKII.
1. Troubleshooting - Fault status, Test and Information channels
Channel #
Allocation
0 STATUS – Input / Output (I/O) Faults
1 STATUS – System Faults 1
2 STATUS – System Faults 2
3 STATUS – System Faults 3
4 STATUS – PSU Status
5
STATUS – Maintenance Log
6 STATUS – System Faults 4
7 ‘Reserved for future expansion’
8 TEST (LED’S & DIP Switches)
9 INFO – Firmware Version (Controller)
Table 2 – Troubleshooting channels
2. Programming - Configuration channels
Channel #
Allocation
A CONFIGURATION – I/O
b CONFIGURATION – I/O Modes
C
CONFIGURATION – Shutdown Delays
d CONFIGURATION – Discharge Delays
E CONFIGURATION – Battery Test
F CONFIGURATION – I/O Polarity
H CONFIGURATION – I/O Short Circuit
L CONFIGURATION – Miscellaneous
n CONFIGURATION – Acknowledge feature
o
CONFIGURATION – Trend logging
P CONFIGURATION – Presets
U CONFIGURATION – I/O Open Circuit
Y
SETTINGS
Table 3 – Programming channels
Each ‘Channel’ contains up to 8 different settings. When a channel is selected by the user, the
information/settings for that particular channel are shown on the LED’s. Settings are changed using the 8-
way dip switch and loaded into the MKII memory with the ‘PROG/SAVE’ button.
The troubleshooting channels will be covered in detail in Topic 4 – Troubleshooting.
LED’s
LED’s
7-Segment
display
Dip switches

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 14 of 63
Programming - configuration channels
If the factory default settings are acceptable, no additional programming is required to the MKII before
installation. If a new configuration is required your will need to re-program the system. It is recommended
that a stable and constant power supply be present when programming the MKII.
Using the interface
The segment display (1) may not be lit when you first
open the module cover or if the interface has been
inactive for more then 10 minutes.
Press the ‘Channel’ button (2) to activate.
The channels are ordered as listed in Table 2 & 3
and each press of the ‘Channel’ button will advance
to the next channel. You can also press and hold the
button to scroll automatically.
The current configuration of the channel is shown on
the LED indicators (3) when the channel is selected.
Figure 17 – User interface active
Programming
Step 1- Select a Channel
Press the ‘Channel’ button repetitively
(or hold) to advance through to desired
channel.
For example;
If you want to change
the shutdown
delay time from the default configuration
of 30 sec to 60 sec – stop advancing at
Channel ‘C’.
Figure 19 shows the table that lists all of
the configurations for Channel ‘C’. For a
complete list of each settings that are
available for each configuration you will
need to refer to the Configuration tables
from page 16 onwards.
Figure 18 - Channel button
Figure 19 - Example channel C
7-
Segment
Channe
l
LED’s
(1)
(2)
(3)

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 15 of 63
Step 2 - Pre-programming
When the desired channel is selected,
change the dip switch positions using a
flat bladed screwdriver (Fig. 20) to mirror
the illuminated LED’s
. (On LED = On
switch.)
As some channels have
configurations for more then one
function, failure to perform this step may
result in a unde
sirable configuration
change
Note: Although the LED numbers are
linked to the corresponding numbered
switches they will not illuminate at this
stage.
Figure 20 - Dip switches
Step 3 - Program mode
Press and hold the “PROG/SAVE”
button (Fig. 21) for 3 seconds to activate
program mode.
The ‘dot’ indicator light (Fig. 22) on the
seven segment display (bottom right
corner) will begin to flash.
Figure 21 - PROG/SAV Figure 22 - Dot indicator
Step 4 - Changing a configuration
Now move the dip switches (on or off) to
match the positions in the desired row of
the configuration table.
In programming mode the LED’s will
now light up when their numbered switch
is turned on.
Following on from the example in step 1;
To change the ‘Shutdown Delay – Initial’
time from 30 seconds (default) to 60
seconds – Turn switch 1, 2 & 3 to the
ON position and switch 4 to the OFF
position.
Figure 23 - LEDS & Dip switches
Figure 24 - Example channel C

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 16 of 63
Step 5 - Saving changes
After you have set the dipswitches to the
desired positions, press and hold the
“PROG/SAVE” button for 3 seconds to
save the new configuration (Fig. 25).
The system will now generate a fault
which is designed to prompt a user to
perform the next step.
Figure 25 - ‘PROG/SAV’ button
Step 6 – System reset
Press and hold the “SYSTEM RESET”
button for 2 seconds to clear the fault
and commit the setting change to the
modules memory (Fig. 26)
This step is required for each
configuration change.
Note: If at any stage you need to cancel
programming mode press the Channel
button once.
A system reset can also be activated via
the display panel by using the “TEST”,
“DELAY” and “DIM” push buttons.
To prevent accidental operation, the
‘delay’ push button must be pressed
prior to the other two buttons:
1. Press and hold the ‘DELAY’ button
2. Press and hold the ‘TEST’ and ‘DIM’
buttons
3. Wait 1 second.
4. Release all three buttons.
Figure 26 - SYSTEM RESET Module
Figure 27 - SYSTEM RESET Display
Notes:

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 17 of 63
Configuration channels (A-Y)
A. Inputs and Outputs
1. The manual actuation input can be disabled when not in use.
2. The equipment shutdown output can be disabled when not in use. Upon alarm, the alarm
indicator on the Display will be activated and the buzzer output will start to sound once every
second but the shutdown sequence will not start and the shutdown indicators will remain in
inactive state.
3. The actuation output (solenoid or squib) can be disabled when not in use.
4. Actuation output 1 can be configured to operate a solenoid or a squib detonator
5. A second actuation output is available on MKII Dual model and can be disabled when not in use.
6. A second actuation output is available on MKII Dual model and can also be configured for a
solenoid or a squib detonator
7. The system discharged pressure switch input can be configured to operate for a normally open
or closed circuit
8. The system pressure monitoring switch input can be configured to operate for a normally open
or closed circuit
Channel
Switch No.
State
Function
A
1 ON (Default) Manual Release Enable
OFF Manual Release Disable
2 ON (Default) Shutdown O/P Enable
OFF Shutdown O/P Disable
3 ON (Default) Actuation O/P 1 Enable
OFF Actuation O/P 1 Disable
4 ON (Default) Actuation O/P 1 Solenoid
OFF Actuation O/P 1 Squib
5 ON Actuation O/P 2 Enable
OFF (Default) Actuation O/P 2 Disable
6 ON (Default) Actuation O/P 2 Solenoid
OFF Actuation O/P 2 Squib
7 ON (Default) System discharged I/P Enable
OFF Cylinder discharged I/P Disable
8 ON (Default) System Low I/P Enable
OFF Pressure Low I/P Disable
Table 4 – Inputs and Outputs 1
b. Detection Mode and Auxiliary Output Mode
There are two detection circuits which can either be disabled completely or configured for;
1. Single Mode - If single circuit detection is selected, detection circuit 2 is disabled. If
multiple detectors are required to cover additional hazard areas they will need to be
wired in series
Figure 28 – Single Mode

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 18 of 63
2. Single & Isolate Mode – As per single mode but detection circuit 2 is enabled to allow
interface with an external switch that would be fitted for the purpose of isolating the MKII,
thus preventing electrical actuation during routine maintenance on the equipment.
Figure 29 – Single and Isolate mode
3. Dual Detection, single zone - In this mode, one detector circuit operating will cause a fire
alarm condition. Once in alarm, operation of the second detection circuit will initiate a
system discharge. This configuration reduces the risk of an accidental discharge and
equipment shutdown but should only be used when both detections circuits are located
in the same hazard area.
Figure 30 – Dual detection, single zone
4. Single Detection, two zones - In this mode, either detector circuit operating will cause a
fire alarm and initiate a system discharge.
Figure 31 – Single detection, two zones
Upon any detector operation, the display panel and buzzer will initiate an audible and visual fire
alarm consisting of illumination and latching of the Alarm LED and sounding of the buzzer once per
second.

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 19 of 63
Description - Auxiliary Mode
The MKII incorporates an auxiliary output ‘AUX’ that can be interfaced with the engine management
system of a third party device to signal one of the following events;
1. Alarm
2. System Fault
3. Alarm and/or Fault
4. Alarm and/or Fault and/or Isolation.
The auxiliary output will deactivate when the event is cleared.
.
Channel Function Detection
Input 2 Detection
Input 1
Switch No.
1 2 3 4 5 6 7 8
b
Detection
Mode
Disabled Disabled Disabled OFF OFF OFF
‘Unassigned’
‘Unassigned’
‘Unassigned’
Single Detection
(Default) Disabled Detection OFF ON OFF
Single Detection plus
External Isolate External Isolate Detection ON OFF OFF
Dual Detection Single
Zone
Detection Detection ON ON OFF
Both inputs are required to initiate
discharge
Single Detection
Two Zones
Detection Detection X X ON
Either input will initiate discharge
AUX
Output
Mode
Fault OFF OFF
Alarm (Default) ON OFF
Fault or Alarm OFF ON
Fault or Alarm or
Isolate ON ON
Table 5 - Detection Mode and Auxiliary Output Mode
Notes:

VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 20 of 63
C. Shutdown delays
Shutdown Delay – Initial
The default setting for the shutdown delay (the time it takes for the shutdown relay to operate after a
fire alarm) is 30 secs. Shutdown delay times can be chosen in 5 second intervals from 0 to 20
seconds, 10 second intervals from 20 to 40 seconds, 20 second intervals from 40 to 180
seconds and 30 second intervals from 180 to 240 seconds.
Shutdown Delay – Extension
The default setting for the shutdown time delay extension is 30 secs.
Shutdown extension times can be chosen in 5 second intervals from 0 to 20 seconds, 10 second
intervals from 20 to 40 seconds, 20 second intervals from 40 to 180 seconds and 30 second
intervals from 180 to 240 seconds.
The MKII control system is configured by default to allow only one time delay extension period to the
equipment shutdown. The number of engine shutdown delay cycles can be increased using
Channel L. The initial and extended delay periods can be independently set to different values. Both
delay periods should be kept as short as safely possible.
Channel Time
(Seconds)
Switch No.
1 2 3 4 5 6 7 8
Shutdown Delay – Initial Shutdown Delay - Extension
C
0 OFF OFF OFF OFF OFF OFF OFF OFF
5 ON OFF OFF OFF ON OFF OFF OFF
10 OFF ON OFF OFF OFF ON OFF OFF
15 125 ON OFF OFF ON ON OFF OFF
20 OFF OFF ON OFF OFF OFF ON OFF
30 (Default) ON OFF ON OFF ON OFF ON OFF
40 OFF ON ON OFF OFF ON ON OFF
60 ON ON ON OFF ON ON ON OFF
80 OFF OFF OFF ON OFF OFF OFF ON
100 ON OFF OFF ON ON OFF OFF ON
120 OFF ON OFF ON OFF ON OFF ON
140 ON ON OFF ON ON ON OFF ON
160 OFF OFF ON ON OFF OFF ON ON
180 ON OFF ON ON ON OFF ON ON
210 OFF ON ON ON OFF ON ON ON
240 ON ON ON ON ON ON ON ON
Table 6 – Shutdown delays
Notes:
Table of contents
Other UTC Fire and Security Control System manuals
Popular Control System manuals by other brands

PEHA
PEHA PHC MCC Installation and operating instructions

Mitsubishi Electric
Mitsubishi Electric BAC-HD150 Instruction book

OJ Electronics
OJ Electronics comfort system4 user manual

Siemens
Siemens SIMOTION Function manual

RTI
RTI It's Under Control CB-8 Installation and operation guide

JWM
JWM Patrol WM-5000X1 user manual