G4 Filter Supply air, extract air Standard
F7 Filter Supply air Standard
FG HR bypass damper Manual Standard
NK Speed selector switch 4-step Standard
E Preheating unit Electric radiator 1.2 kW Standard
J Post-heating unit Electric radiator 1.2 kW Standard
HR Heat recovery cell Cross flow cell, efficiency 60% Standard
HK Maintenance switch Door switch Standard
S Supply air fan 105 l/s (100 Pa) Standard
E Extract air fan 125 l/s (100 Pa) Standard
W1 Pressure difference switch unit Adjustment range Option
Pressure guard on the supply air side 0…500 Pa (320 Pa)
W2 Pressure difference switch unit Adjustment range Option
Pressure guard on the extract air side 0…500 Pa (320 Pa)
T4 HR cell antifreeze thermostat (+4 °C) Standard
T3 Post-heating radiator Adjustment range 0…40 °C Standard
regulating thermostat
T5 Preheating radiator regulating (+5 °C) Standard
thermostat
T1 Overheat protector for the heating unit Automatic +40 °C Included in J
T2 Overheat protector for the heating unit 2 pcs, manually reset, +80 °C Included in J
T6 Overheat protector for the heating unit Automatic +30 °C Included in E
T7 Overheat protector for the heating unit, 2 pcs, manually reset, +55 °C Included in E
TK Fireplace switch Opening contacts, 15...20 min. Option
NK
SILENCER
SPEED SELECTOR
TK
FIREPLACE
SWITCH/BOOSTER
SWITCH
SILENCER UNIT
T3
HK
ES
W1
T5
T4
M
T1
T2
PREHEATING
RADIATOR M
DISTRIBUTION PANEL
INTERNAL ELECTRICAL AND CONTROL CONNECTIONS
VALLOX 132 E
16 A
T6
POST-HEATING
RADIATOR
HR
J
VENTILATION ZONE
5046500A 2010-05-31 KP
T7
F7
E
G4
W2
G4
FG
SILENCER
Code Name Technical data
(factory settings in parentheses)
Standard/Option
VALLOX 132 E
© VALLOX • We reserve the right to make changes without prior notification
What the units include can vary depending on the sales area. 11
CONTROL DIAGRAM and DESCRIPTION OF OPERATION/Electric radiator
VALLOX 132 E (electric post-heating radiator)
Control of operation
Power supply to the unit is controlled with the 0/1 switch in the distribution panel. There is also a
maintenance switch HK inside the unit. It stops power supply when the door of the unit is opened.
Fan speed adjustment
The S and E fans of the unit are controlled depending on operating conditions with a speed selector
switch NK in four steps.
Supply air temperature
Regulating thermostat T3 controls the operation of electric radiator J, keeping the supply air going
out from the unit at the setpoint.
Preheating
The preheating radiator can heat outdoor air and decrease the stopping of the fan. Thermostat T5
switches the radiator on before thermostat T4 stops the supply fan.
Preheating radiator overheat protection
Overheat protection thermostats T6 and T7 monitor the operation of preheating radiator E, preventing
the surface temperature of the radiator from exceeding the threshold. When temperature exceeds
the threshold, the overheat protector trips and power supply to the radiator stops. Overheat protector
T6 is reset automatically, whereas overheat protector T7 is reset manually.
Post-heating radiator overheat protection
Overheat protection thermostats T1 and T2 monitor the operation of post-heating unit J, preventing
the surface temperature of the radiator from exceeding the threshold. When temperature exceeds
the threshold, the overheat protector trips and power supply to the radiator stops Overheat protector
T1 is reset automatically, whereas overheat protector T2 is reset manually.
Heat recovery bypass
Summer-time bypass of heat recovery cell HR is done manually by turning the HR damper FG in the
bypass position for the summer.
Heat recovery antifreeze
Antifreeze thermostat T4 of the HR cell intermittently stops supply air fan S, preventing the freezing
risk of the HR cell. The fan restarts automatically as the risk of freezing passes. The threshold
temperature for the risk of freezing can be set at thermostat T4.
Alarms
Pressure difference switches W1 and W2 are options, designed to monitor pressure difference on the
supply and extract air sides. If the pressure difference rises too high because of dirty filters or clogged
ductwork, an indicator is lit on the front panel of the unit.
Booster or fireplace switch function
It is possible to mount an optional fireplace switch TK for the unit. The fireplace switch can be a 15...20
minute timer equipped with opening contacts.
Parts list Vallox 132 E (electric radiator model)