VAMP VAMP 135 Quick guide

VAMP 135
Over-, under-, residual voltage and
frequency relay
Operation and configuration
instructions
Technical description

VAMP 135 Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP Ltd
2
VAMP 24h support phone : +358 (0)20 53 3264
VM135.EN008

VAMP Ltd Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP 135
VM135.EN008 VAMP 24h support phone : +358 (0)20 53 3264
3
Table of Content
1 General 4
1.1. Relay features......................................................................4
1.2. Operating safety .................................................................5
2 User interface 6
2.1. General.................................................................................6
2.2. Local panel ..........................................................................6
2.2.1. Display .........................................................................
2.2.2. Key pad.......................................................................
2.2.3. Indicators ....................................................................8
3 Local panel operations 9
3.1. Navigation in the menus....................................................9
3.1.1. Function menu table...............................................11
3.1.2. Basic menu structure of protection functions .....12
3.2. Operating levels ................................................................12
3.2.1. Opening operating levels ......................................13
3.2.2. Changing of passwords..........................................13
4 Operating measures 14
4.1. Measured data .................................................................14
4.2. Operation indicators ........................................................15
4.3. Reading of event register ................................................16
4.4. Forced control (Force) .....................................................1
4.5. Setting range limits............................................................18
4.6. Adjusting display contrast and scroll speed .................18
4. . Setting date and time ......................................................18
5 Configuration and parameter setting 19
5.1. Principle of parameter setting ........................................20
5.2. Enabling and disabling protection functions (ENABLE)
.............................................................................................21
5.3. Setting protection function parameters........................21
5.4. Scaling of measuring transformers .................................21
5.5. Configuring digital outputs DOUT...................................22
5.6. Configuring blocking matrix BLOCKING........................22
5. . Configuring the digital input DIGITAL IN ........................22
5.8. Configuring communication protocols COM ..............22
5.9. Analog output mA OUTPUT .............................................24
5.10. Disturbance recorder menu RECORDER ......................24
5.11. Service menu SERVICE.....................................................25
6 PC software 26
6.1. PC user interface...............................................................26
6.1.1. Using the VAMPSET program..................................26
6.2. Remote control connections ..........................................26
7 Commissioning configuration 27
.1. Factory settings..................................................................2
.1.1. Configuration during commissioning....................2
.1.2. Configuration examples.........................................28

VAMP 135 Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP Ltd
4
VAMP 24h support phone : +358 (0)20 53 3264
VM135.EN008
1 General
This part of the manual describes the general functions of the
over-, under-, residual voltage and frequency relay VAMP 13
and includes the relay operation instructions. It also includes
instructions on parameterization and configuration of the relay
and instructions on changing of settings.
The second part of the publication includes detailed protection
function descriptions as well as application examples and
technical data sheets.
The Mounting and Commissioning Instructions are published
in a separate publication, with the code VMMC.EN0xx.
1 1 Relay features
The over-, under-, residual voltage and frequency relay VAMP
13 is ideal for power plant, utility and industrial applications.
It features the following protection functions:
•
Three overvoltage stages
•
Three undervoltage stages
•
Two residual overvoltage stages
•
Two overfrequency stages
•
Two underfrequency stages
•
Circuit breaker failure protection
The VAMP 13 relay can be connected to the system to be
protected using three alternative modes, which are selected
during commissioning. The following modes can be selected:
Line, Line+U
0
and Phase. For more detailed information, see
Chapter 2.2 in this manual and Chapter . in the Technical
description part of this manual.
The VAMP 13 relay is equipped with a voltage measuring
transducer. The output signal of the transducer can be wired to
an external meter or a local automation system. Further VAMP
13 includes a disturbance recorder.
The relay communicates with other systems using common
protocols, such as the Modbus RTU, Profibus DP, Modbus/TCP,
IEC-103 and it can be connected to the fibre-optic SPA bus.

VAMP Ltd Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP 135
VM135.EN008 VAMP 24h support phone : +358 (0)20 53 3264
5
1 2 Operating safety
The terminals on the rear panel of the relay may
carry dangerous voltages, although the auxiliary
voltage is switched off. A live current transformer
secondary circuit must not be opened.
Disconnecting a live circuit may cause dangerous
Disconnecting a live circuit may cause dangerous Disconnecting a live circuit may cause dangerous
Disconnecting a live circuit may cause dangerous
voltages!
voltages!voltages!
voltages! Any operational measurements must be
carried out according to national and local handling
directives and instructions.
Carefully read through the relay operation instructions before
any relay operational measures are carried out.

VAMP 135 Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP Ltd
6
VAMP 24h support phone : +358 (0)20 53 3264
VM135.EN008
2 User interface
2 1 General
The VAMP 13 relay can be controlled in three ways:
•
Locally with the push-buttons on the relay front panel
•
Locally with a PC connected to the serial port on the relay
front panel
•
Via the remote control port on the relay rear panel.
2 2 Local panel
Figure 2.2-1 below shows the location of the components of the
local user interface on the front panel of the relay.
Power
Error
Alarm
Trip
VY 058A
Over- and Undervoltage Relay
31
2
4
VAMP 135
Figure 2.2-1. Relay front panel.
1. Alpha-numerical LED display
2. Key pad
3. LED indicators
4. RS 232 serial communication port for a PC

VAMP Ltd Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP 135
VM135.EN008 VAMP 24h support phone : +358 (0)20 53 3264
2 2 1 Display
The VAMP 13 relay is provided with a clear 10 character
alphanumerical LED display, which normally shows a scrolling
text.
Use the SERVICE/Setup/Bright menu to set the brightness of
the display. The display is dimmed after a preset time.
Use the SERVICE/Setup/ScrolDelay menu to set the scrolling
speed of the display text.
2 2 2 Key pad
Use the key pad and the display to navigate through the menus
and to set the required parameters. The keypad comprises the
following keys:
LEFT, RIGHT, UP, DOWN and the ENTER key.
Figure 2.2.2-1. Components of the key pad.
1. Enter and confirmation key (ENTER)
2. UP/DOWN [INCREASE/DECREASE] arrow keys
(UP/DOWN)
3. LEFT/RIGHT arrow keys [for selection of digit position]
(LEFT/RIGHT)

VAMP 135 Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP Ltd
8
VAMP 24h support phone : +358 (0)20 53 3264
VM135.EN008
2 2 3 Indicators
The relay front panel holds 4 LED indicators:
toimintamerkit
Figure 2.2.3-1. Relay operation indicators.
Relay operation indicators:
Power on
Power onPower on
Power on
auxiliary voltage switched on
Error
ErrorError
Error
self-supervision fault, the self-supervision output relay
operates in parallel with the indicator
Alarm
AlarmAlarm
Alarm
starting of protection stage
Trip
TripTrip
Trip
tripping of protection stage

VAMP Ltd Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP 135
VM135.EN008 VAMP 24h support phone : +358 (0)20 53 3264
9
3 Local panel operations
The local panel can be used to read measured values, set
parameters and configure relay functions. However, please note
that some of the parameters can only be set by means of a PC
connected to the local communication port. Further, some
parameters are factory set.
3 1 Navigation in the menus
All setting, resetting, etc. functions are carried out via menu
functions:
1. Use UP and DOWN arrow keys to move up and down in the
main menu. The active menu is the one seen in the display.
The menu names are shown with their full length or
abbreviated, e.g. U STATUS = status display for the
different voltage stages.
2. Use the RIGHT key to move to the function level of the
required menu, e.g. U> Stat.
Use the LEFT key to cancel the selection.
3. Use the RIGHT key to move to the parameter level of the
selected function, e.g. SCntr.
Use the UP and DOWN keys to scroll through the other
parameters on the same function level.
4. Confirm the selection of setting state of the requested
parameter by pushing ENTER and by entering the
password corresponding to the setting level.
. Push LEFT for at least 2 s to exit from the setting state of a
parameter without changing the setting value or,
6. Push ENTER to confirm and store the parameter setting.

VAMP 135 Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP Ltd
10
VAMP 24h support phone : +358 (0)20 53 3264
VM135.EN008
MAIN MENU SUBMENUS
menurakenne_100sarja
Figure 3.1-1. The principle of the menu structure and navigation in the
menus.

VAMP Ltd Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP 135
VM135.EN008 VAMP 24h support phone : +358 (0)20 53 3264
11
3 1 1 Function menu table
The structure of the menu is clear and straightforward. The
main menu holds eighteen submenus, each with varying
numbers of submenus and parameters.
Figure 3.1.1-1. Main menu of the VAMP 13 relay.

VAMP 135 Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP Ltd
12
VAMP 24h support phone : +358 (0)20 53 3264
VM135.EN008
3 1 2 Basic menu structure of protection functions
Example U>:
U SETTING / U> SET:
U> 12000V Set value of protection function [V]
U> 120%Un
Set value of protection function [%Un]
t> 0.20s
ReleaseDly: 0.06s Release delay
Hysteresis: 3.0%
U STATUS / U> stat:
SCntr - Start counter
TCntr - Trip counter
Force - Enabling and disabling force function (ON/OFF)
Status - -, Start, Trip
3 2 Operating levels
The relay features three operating levels, i.e. the User, the
Operator and the Configuration level. The purpose of the
operating levels is to prevent accidental change of relay
configurations, parameterizations or settings.
USER level
Use: Parameter values, for example, can be read
Opening: Level permanently open
Closing: Closing not possible
OPERATOR level
Use:
Settings of protection stages, for example, can be
changed.
Opening: The default password is 1.
Setting state: On entering the parameter setting state a
password must be given, see 3.2.1
Closing: The level is automatically closed 10 minutes
after a key being pushed last or a setting being
performed via the local port. Closing can also be
performed by giving the password 9999.

VAMP Ltd Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP 135
VM135.EN008 VAMP 24h support phone : +358 (0)20 53 3264
13
CONFIGURATOR level
Use: The configuration level is needed during the
commissioning of the relay. The turns ratios of
the voltage transformers, for example, can be
set.
Opening: The default password is 2
Setting state: On entering the parameter setting state a
password must be given, see 3.2.1
Closing: The level is automatically closed 10 minutes
after a key being pushed last or a setting being
performed via the local port. Closing can also be
performed by giving the password 9999.
3 2 1 Opening operating levels
1. Move to the item to be changed, e.g. U SETTING/U>Set/
U>: 120%Un. Push the ENTER key twice on the front
panel.
+++0
Figure 3.2.1-1. Opening an operating level
2. Enter the password needed for the desired level: The
password may contain four digits. The digits are supplied
one by one by first moving to the position of the digit using
the RIGHT key and then setting the desired digit value
using the UP key.
3. Push ENTER.
3 2 2 Changing of passwords
The set password can only be changed locally using a PC
connected to the local RS 232 port on the relay.

VAMP 135 Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP Ltd
14
VAMP 24h support phone : +358 (0)20 53 3264
VM135.EN008
4 Operating measures
General
Carefully study the operating instructions in Chapters 1
through 3 of this manual before any operating measures are
taken or before any relay settings or functions are changed.
The relay can be controlled by means of the MMI on the relay
front panel, a PC running the VAMPSET software, a PC
running suitable terminal software or a remote control system.
4 1 Measured data
The measured values can be read from the main menu
MEASURES and its submenus shown in the figure below.
MEASURES U12: 10950V
U23: 10960V
U31: 10950V
UL1: 6320V
UL2: 6330V
UL3: 6320V
U0: 0.0 %
f= 50.2Hz
measuremode.eps
U0: 0V
Figure 4.1-1. Measures menu of the VAMP 13 relay.

VAMP Ltd Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP 135
VM135.EN008 VAMP 24h support phone : +358 (0)20 53 3264
15
4 2 Operation indicators
LED indic
LED indicLED indic
LED indica
aa
ators
torstors
tors
Explanation
ExplanationExplanation
Explanation
Measure/ remarks
Measure/ remarksMeasure/ remarks
Measure/ remarks
Power LED lit The auxiliary power
switched on
Normal operating state
Error LED lit An internal relay fault has
been detected
The relay attempts to
reboot. If the error LED
remains lit, call for
maintenance
Alarm LED lit One or several signals of the
output relay matrix have
been assigned to output
Alarm and the output has
been activated by one of the
signals. (see Chapter . )
The LED is switched off,
when the signal that
caused output Alarm to
activate, e.g. the START
signal, resets. The
resetting depends on the
type of configuration;
Connected or Latched.
TRIP LED lit One or several signals of the
output relay matrix have
been assigned to output
Trip and the output has
been activated by one of the
signals. (see Chapter . )
The LED is switched off,
when the signal that
caused output Trip to
activate, e.g. the TRIP
signal, resets. The
resetting depends on the
type of configuration;
Connected or Latched.
Resetting latched indicators and output relays
All indicators and output relays can be given a latching
function in the configuration.
There are two ways to reset latched indicators and relays:
1. Move to the initial display, from the alarm list, by pushing
the CANCEL key for approx. 3 s. Then reset the latched
indicators and output relays by pushing the ENTER key.
2. Acknowledge each event in the alarm list one by one, by
pushing ENTER the equivalent times. Then, in the initial
display, reset the latched indicators and output relays by
pushing the ENTER key.
The latchings can also be reset via the communications bus or
via a DI input configured for that purpose.

VAMP 135 Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP Ltd
16
VAMP 24h support phone : +358 (0)20 53 3264
VM135.EN008
4 3 Reading of event register
The event register can be read from the Events item of the
main menu:
1. Push the RIGHT key once, the displays shows the Event
info text
2. Push the RIGHT key once, the displays shows Count: x,
where x = the number of recorded events
3. Push the DOWN key once, the display shows the ClrEv
text. The event register can now be reset.
4. Push the LEFT key to return to the Event info menu (by
pressing twice you can return to the main menu)
. Push the DOWN key to return to the Event list menu:
Figure 4.3-1. Event register, example.
6. Push the RIGHT key once to enter the event list, the
display shows the last Event list text. Scroll the event list
by pushing the UP and DOWN keys.
7. Push the LEFT key twice to move from the event list to the
main menu.

VAMP Ltd Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP 135
VM135.EN008 VAMP 24h support phone : +358 (0)20 53 3264
1
4 4 Forced control (Force)
In the SERVICE menu it is possible to use forced control of the
output relays, e.g. for testing purposes.
To activate the forced control function (also see Figure 4.4-1):
1. Open access level CONFIGURATION
2. Move to the SERVICE level of the main menu.
3. Push the RIGHT key once to move to the submenu Relays
4. Push the RIGHT key once to move to the output relays’
force setting parameter Force:
Figure 4.4-1. Activation of the Force function.
. Push the ENTER key while on the Force: level to be able to
change the setting (the parameter to be set is blinking)
6. Push the UP and DOWN keys to change the OFF text to the
ON text in the display (Force function activated).
7. Push the ENTER key to confirm the setting and to move
back to the Force: level
8. The Force: level has a selection list. Push the UP and
DOWN keys to select the desired output relay, which is
controlled on and off by forced control:
9. Push the ENTER key to obtain the setting state, e.g.
Relays/T1.
10. Push the UP or DOWN key to change the selection 0 -> 1.
11. Push the ENTER key to perform a controlled operation of
the output relay (e.g. the T1 is activated) and to return to
the Force: level.
12. Push the LEFT key for more than 2 s to return from the
Force: setting state to the normal Force: state without
changing the control state.
13. Push the LEFT key to return from the Force: setting state
to the Relays submenu.
14. Push the LEFT key to return to the main menu.

VAMP 135 Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP Ltd
18
VAMP 24h support phone : +358 (0)20 53 3264
VM135.EN008
4 5 Setting range limits
Note!
If parameters requiring a setting value are given out-of-range
settings, a fault message will be obtained when the setting is
confirmed with the ENTER key. Adjust the setting to within
the allowed setting range.
4 6 Adjusting display contrast and scroll
speed
The readability of the LCD varies with the brightness of the
surrounding. When needed, the brightness can be adjusted in
the SERVICE/Setup/Bright: menu.
The scroll speed of the text in the display can be adjusted in the
SERVICE/Setup/ScrolDelay: menu.
4 7 Setting date and time
Date, time and style are set in the SERVICE/Setup/Date, Time
and Style menus.

VAMP Ltd Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP 135
VM135.EN008 VAMP 24h support phone : +358 (0)20 53 3264
19
5 Configuration and parameter
setting
User level: CONFIGURATOR
•
Choose the protection functions in the ENABLE position of
the main menu, see chapter .2.
NOTE!
Protection functions not enabled will not be shown in the
submenus.
•
Change the parameters of over- and undervoltage
protection functions in the U SETTING position of the main
menu, see chapter .3.
•
Change the parameters of residual voltage protection
functions in the Uo SETTING position of the main menu,
see chapter .3.
Note!
The U
0
protection functions are available only if U
mode
:
Line+ U
0
or Phase is selected. See Chapter 2.2. of Technical
description.
•
Change the parameters of frequency protection functions in
the f SETTING position of the main menu, see chapter .3.
•
Change the parameters of Circuit Breaker Failure
Protection function in the CBFP Set position of the main
menu, see chapter .3.
•
Set the voltage scaling (e.g. U
prim
, U
sec
, U
mode
, etc.) in the
SCALING position of the main menu, see chapter .4.
•
Set the residual voltage scaling (U
0sec
) in the U
0
SCALING
position of the main menu, see chapter .4.
•
Configure the digital outputs in the DOUT position of the
main menu, see chapter . .
•
Configure the interlockings in the BLOCKING position of
the main menu, see chapter .6.
•
Configure the digital input in the DIGITAL IN position of
the main menu, see chapter .7.
•
Choose and configure the communication buses in the COM
position of the main menu, see chapter .8.
•
Configure the analog output in the mA OUTPUT position of
the main menu, see chapter .9.
•
Set the Date and time in the SERVICE position of the main
menu, see chapter .11.

VAMP 135 Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP Ltd
20
VAMP 24h support phone : +358 (0)20 53 3264
VM135.EN008
NOTE!
Some of the parameters, for instance the password, can only be
altered via the RS 232 serial communication port using a PC.
5 1 Principle of parameter setting
This example shows how to change the scaling of the voltage
transformers. Same principle is used to change other
parameters, see Figure .1-1.
1. Use the DOWN key of the front panel to move to item
SCALING of the main menu.
2. Use the RIGHT key to move one step to the right, the text
Uprim: 10000V appears in the display. Use the DOWN key
to select the Usec, Umode and Un.
3. Use the ENTER key twice to move to give the operator
password. Use the ENTER key to confirm the password.
4. Use the UP and DOWN key to change the setting value and
use the RIGHT and LEFT key to move from digit to digit.
. Use the ENTER key to confirm the function or push the
LEFT key for >2 s to cancel the function.
6. Push the LEFT key twice to return to the main menu.
UpPrim:10000V
Usec :100V
Umode
Un: 10000V
change setting
change setting
change setting
SCALING 10000
10900
10100
101
100
109
10100
101
100
109
Line
Line+Uo
Phase
scalingmode
Figure .1-1. Changing parameters.
Table of contents
Other VAMP Relay manuals