REV 1 TRF-250 USER’S MANUAL
4
1.2 TRF-250 Technical Specifications
Table 1. TRF-250 Technical Specifications
TYPE Portable, lightweight, automatic, 3-phase transformer turns-ratio meter
PHYSICAL SPECIFICATIONS 18”W x 5”H x 12”D(45.7 cm x 12.7 cm x 30.5 cm); Weight: 20 lbs(9.1 Kg)
OPERATING VOLTAGE 100 – 240 Vac, 50/60 Hz
MEASUREMENT METHOD ANSI/IEEE C57.12.90
TURNS-RATIO MEASURING
RANGE 0.8 – 50,000 to 1
TURNS-RATIO ACCURACY 0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.25%. 4,000 – 14,999: ±1%,
15,000 – 50,000: ±2% @ 4Vac
0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.20%. 4,000 – 14,999: ±1%,
15,000 – 50,000: ±1.5% @ 40Vac
0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.20%. 4,000 – 14,999: ±1%,
15,000 – 50,000: ±1.5% @ 100Vac
0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.15%. 4,000 – 14,999: ±0.8%,
15,000 – 50,000: ±1.2% @ 250Vac
TEST VOLTAGES 4 Vac @ 1 Amp, 40 Vac @ 200 mA, 100 Vac @ 100 mA, 250 Vac @ 50
mA
EXCITATION CURRENT READING
RANGE 0 – 2 Amperes; Accuracy: ±0.1 mA, ±2% of reading (±1 mA)
PHASE-ANGLE MEASUREMENT 0 – 360 Degrees; Accuracy: ±0.2 degree (±1 digit)
DISPLAY Back-lit LCD screen (128 x 64 pixels) viewable in bright sunlight and low-
light levels
PRINTER Built-in 4.5-inch wide thermal printer
COMPUTER INTERFACES Bluetooth, USB port
EXTERNAL DATA STORAGE One USB Flash drive interface port; Up to 999 transformer test records
can be stored on a USB Flash drive (not included)
INTERNAL TEST RECORD
STORAGE Can store 112 transformer test records internally. Each record holds the
test record header and up to 99 readings.
INTERNAL TEST PLAN STORAGE Can store 128 transformer test plans internally. Test plans can be
transferred to the unit from the PC via Bluetooth/USB port or via the USB
Flash drive interface
PC SOFTWARE Windows®-based Transformer Turns Ratio Analyzer application is
included with purchase price
LOAD TAP CHANGER CONTACT 240 Vac, 2 Amps
SAFETY Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92
standards
ENVIRONMENT Operating: -10˚ to 50˚ C (15˚ to +122˚ F); Storage: -30˚ C to 70˚ C (-22˚
to +158˚ F)
HUMIDITY (MAX) 90% RH @ 40˚ C (104˚ F) non-condensing
ALTITUDE (MAX) 2000m (6562 ft) to fully safety specifications
CABLES One 15-foot single-phase set, one 15-foot 3-phase set, one 25-foot
extension set, one safety ground, one USB, cable bag
WARRANTY One year on parts and labor
NOTE
The above specifications are valid at nominal operating voltage and at a
temperature of 25°C (77°F). Specifications may change without prior notice.