Vega VEGASWING 61 User manual

Operating Instructions
Vibrating level switch for liquids
VEGASWING 61
- contactless electronic switch
Document ID: 29223

2
Contents
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
Contents
1 About this document
1.1 Function ........................................................................................................................... 4
1.2 Target group ..................................................................................................................... 4
1.3 Symbolism used............................................................................................................... 4
2 For your safety
2.1 Authorised personnel ....................................................................................................... 5
2.2 Appropriate use................................................................................................................ 5
2.3 Warning about incorrect use............................................................................................. 5
2.4 General safety instructions............................................................................................... 5
2.5 Safety label on the instrument .......................................................................................... 5
2.6 CE conformity................................................................................................................... 5
2.7 SIL conformity .................................................................................................................. 6
2.8 Safety instructions for Ex areas ........................................................................................ 6
2.9 Environmental instructions ............................................................................................... 6
3 Product description
3.1 Conguration.................................................................................................................... 7
3.2 Principle of operation........................................................................................................ 8
3.3 Operation ......................................................................................................................... 8
3.4 Storage and transport....................................................................................................... 9
4 Mounting
4.1 General instructions ....................................................................................................... 10
4.2 Instructions for installation.............................................................................................. 12
5 Connecting to power supply
5.1 Preparing the connection ............................................................................................... 14
5.2 Connection procedure.................................................................................................... 14
5.3 Wiring plan, single chamber housing.............................................................................. 15
6 Setup
6.1 General information........................................................................................................ 17
6.2 Adjustment elements...................................................................................................... 17
6.3 Function chart ................................................................................................................ 18
7 Maintenanceandfaultrectication
7.1 Maintenance .................................................................................................................. 20
7.2 Rectify faults................................................................................................................... 20
7.3 Exchanging the electronics ............................................................................................ 21
7.4 Instrument repair ............................................................................................................ 22
8 Dismounting
8.1 Dismounting steps.......................................................................................................... 23
8.2 Disposal ......................................................................................................................... 23
9 Supplement
9.1 Technical data ................................................................................................................ 24
9.2 Dimensions .................................................................................................................... 30

3
Contents
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
Supplementary documentation
Information:
Supplementary documents appropriate to the ordered version come
withthedelivery.Youcanndthemlistedinchapter"Product descrip-
tion".
Instructions manuals for accessories and replacement parts
Tip:
To ensure reliable setup and operation of your VEGASWING 61, we
oeraccessoriesandreplacementparts.Thecorrespondingdocu-
mentations are:
• Operatinginstructionsmanual"Remote housing - VEGASWING"
• Operatinginstructionsmanual"Oscillator VEGASWING series 60"
Editing status: 2012-12-06

4
1 About this document
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
1 About this document
1.1 Function
This operating instructions manual provides all the information you
need for mounting, connection and setup as well as important instruc-
tionsformaintenanceandfaultrectication.Pleasereadthisinforma-
tion before putting the instrument into operation and keep this manual
accessible in the immediate vicinity of the device.
1.2 Target group
Thisoperatinginstructionsmanualisdirectedtotrainedqualied
personnel.The contents of this manual should be made available to
these personnel and put into practice by them.
1.3 Symbolism used
Information, tip, note
This symbol indicates helpful additional information.
Caution: If this warning is ignored, faults or malfunctions can result.
Warning: If this warning is ignored, injury to persons and/or serious
damage to the instrument can result.
Danger: If this warning is ignored, serious injury to persons and/or
destruction of the instrument can result.
Ex applications
This symbol indicates special instructions for Ex applications.
• List
The dot set in front indicates a list with no implied sequence.
→ Action
This arrow indicates a single action.
1 Sequence
Numbers set in front indicate successive steps in a procedure.
Battery disposal
This symbol indicates special information about the disposal of bat-
teries and accumulators.

5
2 For your safety
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
2 For your safety
2.1 Authorised personnel
All operations described in this operating instructions manual must
be carried out only by trained specialist personnel authorised by the
plant operator.
During work on and with the device the required personal protective
equipment must always be worn.
2.2 Appropriate use
The VEGASWING 61 is a sensor for level detection.
Youcannddetailedinformationontheapplicationrangeinchapter
"Product description".
Operational reliability is ensured only if the instrument is properly
usedaccordingtothespecicationsintheoperatinginstructions
manual as well as possible supplementary instructions.
For safety and warranty reasons, any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer. Arbi-
traryconversionsormodicationsareexplicitlyforbidden.
2.3 Warning about incorrect use
Inappropriate or incorrect use of the instrument can give rise to
application-specichazards,e.g.vesseloverllordamagetosystem
components through incorrect mounting or adjustment.
2.4 General safety instructions
This is a high-tech instrument requiring the strict observance of stand-
ard regulations and guidelines.The user must take note of the safety
instructionsinthisoperatinginstructionsmanual,thecountry-specic
installation standards as well as all prevailing safety regulations and
accident prevention rules.
Theinstrumentmustonlybeoperatedinatechnicallyawlessand
reliable condition.The operator is responsible for trouble-free opera-
tion of the instrument.
During the entire duration of use, the user is obliged to determine the
compliance of the necessary occupational safety measures with the
current valid rules and regulations and also take note of new regula-
tions.
2.5 Safety label on the instrument
The safety approval markings and safety tips on the device must be
observed.
2.6 CE conformity
ThisdevicefulllsthelegalrequirementsoftheapplicableECguide-
lines.ByattachingtheCEmark,VEGAprovidesaconrmationof

6
2 For your safety
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
successfultesting.YoucanndtheCEconformitydeclarationinthe
downloadareaof"www.vega.com".
2.7 SIL conformity
VEGASWING61fulllstherequirementsoffunctionalsafetyaccord-
ingtoIEC61508resp.IEC61511.Youcanndfurtherinformationin
theSafetyManual"VEGASWING series 60".
2.8 Safety instructions for Ex areas
PleasenotetheEx-specicsafetyinformationforinstallationandop-
eration in Ex areas.These safety instructions are part of the operating
instructions manual and come with the Ex-approved instruments.
2.9 Environmental instructions
Protection of the environment is one of our most important duties.
That is why we have introduced an environment management system
with the goal of continuously improving company environmental pro-
tection.Theenvironmentmanagementsystemiscertiedaccording
to DIN EN ISO 14001.
Pleasehelpusfullthisobligationbyobservingtheenvironmental
instructions in this manual:
• Chapter"Packaging, transport and storage"
• Chapter"Disposal"

7
3 Product description
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
3 Product description
3.1 Conguration
The scope of delivery encompasses:
• VEGASWING 61 point level switch
• Documentation
– this operating instructions manual
– SafetyManual"Functional safety (SIL)"(optional)
– Supplementaryinstructionsmanual"Plug connector for level
sensors"(optional)
– Ex-specic"Safety instructions"(withExversions)
– ifnecessary,furthercerticates
The VEGASWING 61 consists of the components:
• Housing cover
• Housing with electronics
• Processttingwithtuningfork
1
2
3
Fig. 1: VEGASWING 61 with plastic housing
1 Housing cover
2 Housing with electronics
3 Processtting
Thetypeplatecontainsthemostimportantdataforidenticationand
use of the instrument:
• Article number
• Serial number
• Technical data
• Article numbers, documentation
• SILidentication(withSILratingexworks)
With the serial number, you can access the delivery data of the instru-
ment via www.vega.com,"VEGA Tools"and"serial number search".
Inadditiontothetypelabeloutside,youcanalsondtheserialnum-
ber on the inside of the instrument.
Scope of delivery
Constituent parts
Type plate

8
3 Product description
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
3.2 Principle of operation
VEGASWING 61 is a point level sensor with tuning fork for level
detection.
It is designed for industrial use in all areas of process technology and
can be used in liquids.
Typicalapplicationsareoverllanddryrunprotection.Withitstuning
fork of only 40 mm length, VEGASWING 61 can also be mounted e.g.
in pipelines from DN 32.The small tuning fork allows use in vessels,
tanks and pipes. Thanks to its simple and robust measuring system,
VEGASWING61isvirtuallyunaectedbythechemicalandphysical
properties of the liquid.
Itfunctionsevenunderdicultconditionssuchasturbulence,airbub-
bles, foam generation, buildup, strong external vibration or changing
products.
Fault monitoring
The electronics module of VEGASWING 61 continuously monitors via
frequency evaluation the following criteria:
• Strong corrosion or damage on the tuning fork
• Loss of vibration
• Linebreaktothepiezodrive
If a malfunction is detected or in case of power failure, the electronics
takesonadenedswitchingcondition,i.e.thecontactlesselectronic
switchopens(safecondition).
Thetuningforkispiezoelectricallyenergisedandvibratesatits
mechanicalresonancefrequencyofapprox.1200Hz.Thepiezosare
xedmechanicallyandarehencenotsubjecttotemperatureshock
limitations.The frequency changes when the tuning fork is covered
by the medium.This change is detected by the integrated electronics
module and converted into a switching command.
VEGASWING 61 is a compact instrument, i.e. it can be operated with-
out external evaluation system.The integrated electronics evaluates
the level signal and outputs a switching signal.With this switching
signal,aconnecteddevicecanbeoperateddirectly(e.g.awarning
system,apumpetc.).
Thedataforpowersupplyarespeciedinchapter"Technical data".
3.3 Operation
The switching condition of VEGASWING 61 with plastic housing can
becheckedwhenthehousingisclosed(signallamp).Withthebasic
setting,productswithadensity>0.7g/cm³(0.025lbs/in³)canbede-
tected.The instrument can be adapted if products with lower density
are to be measured.
Ontheelectronicsmoduleyouwillndthefollowingindicatingand
adjustment elements:
• Signallampforindicationoftheswitchingcondition(green/red)
• DIL switch for sensitivity adjustment
Application area
Functional principle
Voltage supply

9
3 Product description
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
• Modeadjustmentforselectionoftheswitchingcondition(A/B)
3.4 Storage and transport
Your instrument was protected by packaging during transport. Its
capacity to handle normal loads during transport is assured by a test
according to DIN EN 24180.
The packaging of standard instruments consists of environment-
friendly, recyclable cardboard.The sensor is also equipped with a
protective cap of ABS. For special versions, PE foam or PE foil is also
used. Dispose of the packaging material via specialised recycling
companies.
Transport must be carried out under consideration of the notes on the
transport packaging. Nonobservance of these instructions can cause
damage to the device.
The delivery must be checked for completeness and possible transit
damage immediately at receipt. Ascertained transit damage or con-
cealed defects must be appropriately dealt with.
Up to the time of installation, the packages must be left closed and
stored according to the orientation and storage markings on the
outside.
Unless otherwise indicated, the packages must be stored only under
the following conditions:
• Not in the open
• Dry and dust free
• Not exposed to corrosive media
• Protected against solar radiation
• Avoiding mechanical shock and vibration
• Storageandtransporttemperatureseechapter"Supplement -
Technical data - Ambient conditions"
• Relative humidity 20 … 85 %
Packaging
Transport
Transport inspection
Storage
Storage and transport
temperature

10
4 Mounting
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
4 Mounting
4.1 General instructions
Make sure that all parts of the instrument coming in direct contact with
the process, especially the sensor element, process seal and process
ttingandsuspensioncable,aresuitablefortheexistingprocess
conditions, such as process pressure, process temperature as well as
the chemical properties of the medium.
Youcanndthespecicationsinchapter"Technical data"andonthe
type plate.
In general, VEGASWING 61 can be installed in any position.The
instrument only has to be mounted in such a way that the tuning fork
is at the height of the desired switching point.
Thetuningforkhaslateralmarkings(notches)thatindicatethe
switching point with vertical mounting.The switching point refers
towaterwiththebasicsettingofthesensitivityswitch≥0.7g/cm³
(0.025lbs/in³).WhenmountingVEGASWING61,makesurethat
this marking is at the height of the requested switching point. Keep in
mind that the switching point of the instrument is shifted if the medium
hasadensityotherthanwater-water1g/cm³(0.036lbs/in³).For
products<0.7g/cm³(0.025lbs/in³)and>0.5g/cm³(0.018lbs/in³)
thedensityswitchmustbesetto≥0.5g/cm³.
Keepinmindthatfoamswithadensity>0.45g/cm³(0.016lbs/in³)
are detected by the sensor. This can cause faulty switchings particu-
lary when used as dry run protection system.
2
3
14
Fig. 2: Mounting vertical
1 Switching point approx. 13 mm (0.51 in)
2 Switching point with lower density
3 Switching point with higher density
4 Switching point approx. 27 mm (1.06 in)
Suitability for the process
conditions
Switching point

11
4 Mounting
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
1
Fig. 3: Mounting horizontal
1 Switching point
1
2
Fig. 4: Horizontal installation (recommended mounting position, particularly for
adhesive products)
1 Switching point
2 Markingwithscrewedversionontop,withangeversionsdirectedtothe
angeholes
Withangeversions,theforkisdirectedasfollowstotheangeholes.
Fig.5:Forkpositionwithangeversions
Usetherecommendedcables(seechapter"Connecting to power
supply")andtightenthecablegland.
You can give your instrument additional protection against moisture
penetration by leading the connection cable downward in front of the
cableentry.Rainandcondensationwatercanthusdraino.Thisap-
plies mainly to outdoor mounting as well as installation in areas where
highhumidityisexpected(e.g.throughcleaningprocesses)oron
cooled or heated vessels.
Moisture

12
4 Mounting
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
Fig. 6: Measures against moisture penetration
Caution:
Do not hold VEGASWING 61 on the tuning fork. Particularly with
angeortubeversions,thetuningforkcanbedamagedjustbythe
weight of the instrument.Transport coated instruments very carefully
and avoid touching the tuning fork.
Remove the packaging or the protective cover just before installation.
Theprocessttingmustbesealedifthereisgaugeorlowpressurein
the vessel. Before use, check if the seal material is resistant against
the measured product and the process temperature.
Themax.permissiblepressureisspeciedinchapter"Technical
data"oronthetypelabelofthesensor.
The vibrating level switch is a measuring instrument and must be
treated accordingly. Bending the vibrating element will destroy the
instrument.
Warning:
The housing must not be used to screw the instrument in! Applying
tightening force can damage internal parts of the housing.
Use the hexagon above the thread for screwing in.
4.2 Instructions for installation
VEGASWING61hasadenedthreadstartingpoint.Thismeans
that every VEGASWING 61 is in the same fork position after being
screwed in. Remove therefore the supplied seal from the thread of
VEGASWING 61.This seal is not required when using a welded
socket with O-ring in front.
Keep in mind that this welded socket is not suitable for coated instru-
ment versions.
Screw VEGASWING 61 completely into the welded socket.The
later position can be determined already before welding. Mark the
appropriate position of the welded socket. Before welding, unscrew
VEGASWING 61 and remove the rubber ring from the welded socket.
Theweldedsockethasamarking(notch).Weldthesocketwiththe
notchfacingupward,orincaseofpipelines(DN32uptoDN50),
alignedwiththedirectionofow.
Transport
Pressure/Vacuum
Handling
Welded socket

13
4 Mounting
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
1
Fig. 7: Marking on the welded socket
1 Marking
Incaseofhorizontalmountinginadhesiveandviscousproducts,
the surfaces of the tuning fork should be vertical in order to reduce
builduponthetuningfork.Onthescrewedversionyouwillnda
marking on the hexagon.With this, you can check the position of the
tuning fork when screwing it in.When the hexagon touches the seal,
thethreadcanstillbeturnedbyapprox.halfaturn.Thisissucientto
reach the recommended installation position.
Withangeversions,theforkisdirectedtotheangeholes.
When used in adhesive and viscous products, the tuning fork should
protrude into the vessel to avoid buildup. For that reason, sockets
forangesandmountingbossesshouldbeavoidedwhenmounting
horizontally.
IfVEGASWING61ismountedinthellingstream,unwantedfalse
measurement signals can be generated. For this reason, mount VE-
GASWING 61 at a position in the vessel where no disturbances, e.g.
fromllingopenings,agitators,etc.,canoccur.
Tominimiseowresistancecausedbythetuningfork,VEGASWING
61 should be mounted in such a way that the surfaces of the blades
are parallel to the product movement.
The gas-tight leadthrough avoids due to a second sealing the
uncontrolled penetration of the medium.The lifetime of the gastight
leadthrough depends ont he chemical resistance of the materials.
See"Technical data".
Caution:
Ifitisdetermined(e.g.byanerrormessageofVEGASWING61)that
medium has already penetrated into the vibrating element, the instru-
ment must be exchanged immediately.
Adhesive products
Inowingmedium
Flows
Gas-tight leadthrough

14
5 Connecting to power supply
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
5 Connecting to power supply
5.1 Preparing the connection
Always keep in mind the following safety instructions:
• Connect only in the complete absence of line voltage
Inhazardousareasyoumusttakenoteoftherespectiveregulations,
conformityandtypeapprovalcerticatesofthesensorsandpower
supply units.
Connect the operating voltage according to the connection diagrams.
The electronics module SWE60C is designed in protection class I.
To maintain this protection class, it is absolutely necessary that the
earth conductor be connected to the inner earth conductor terminal.
Keep the general installation regulations in mind.Take note of the
correspondinginstallationregulationsforhazardousareaswithEx
applications.
Thedataforpowersupplyarespeciedinchapter"Technical data".
The instrument is connected with standard three-wire cable without
screen. If electromagnetic interference is expected which is above the
test values of EN 61326 for industrial areas, screened cable should
be used.
Use cable with round cross-section. A cable outer diameter of
5…9mm(0.2…0.35in)ensuresthesealeectofthecablegland.
Ifyouareusingcablewithadierentdiameterorcross-section,
exchange the seal or use a suitable cable gland.
Inhazardousareas,onlyuseapprovedcableconnectionsforVEGAS-
WING 61.
Take note of the corresponding installation regulations for Ex applica-
tions.
Cover all housing openings conforming to standard according to
EN 60079-1.
5.2 Connection procedure
With Ex instruments, the housing cover may only be opened if there is
no explosive atmosphere present.
Proceed as follows:
1. Unscrew the housing cover
2. Loosen compression nut of the cable entry
3. Removeapprox.10cm(4in)ofthecablemantle,stripapprox.
1cm(0.4in)ofinsulationfromtheendsoftheindividualwires
4. Insert the cable into the sensor through the cable entry
5. Open the terminals with a screwdriver
6. Insert the wire ends into the open terminals according to the wir-
ing plan
7. Tighten the terminals with a screwdriver
Note safety instructions
Take note of safety
instructions for Ex
applications
Voltage supply
Connection cable
Connection cable
for Ex applications

15
5 Connecting to power supply
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
8. Check the hold of the wires in the terminals by lightly pulling on
them
9. Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
10. Screw the housing cover back on
Theelectricalconnectionishencenished.
5.3 Wiring plan, single chamber housing
The following illustrations apply to the non-Ex as well as to the Ex-d
version.
1
4
44
2 3
Fig. 8: Material versions, single chamber housing
1 Plastic (not with Ex d)
2 Aluminium
3 Stainless steel (not with Ex d)
4 Filter element for pressure compensation (not with Ex d)
C
20-253V AC/DC
max 400mA
A
B
L
N
LN
12
0,5 g / cm3
0,7 g / cm3
+
+
12
12
3
5
1
2
4
Fig. 9: Electronics and connection compartment, single chamber housing
1 Control lamp
2 DIL switch for mode adjustment
3 DIL switch for switching point adaptation
4 Ground terminal
5 Connection terminals
We recommend connecting VEGASWING 61 in such a way that the
switching circuit is open when there is a level signal, line break or
failure(safecondition).
Housing overview
Electronics and connec-
tion compartment
Wiring plan

16
5 Connecting to power supply
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
Information:
The contactless electronic switch is always shown in non-operative
condition.
Warning:
The instrument must not be operated without an intermediately
connected load, because the electronics would be destroyed if con-
nected directly to the mains. It is not suitable for connection to low
voltage PLC inputs.
Examples for typical applications:
• Loadresistanceat24VDC:88…1800Ω
• Rated power, relay 253 V AC: > 2.5 VA
• Rated power, relay 24 V AC: > 0.5 VA
For direct control of relays, contactors, magnet valves, warning lights,
horns etc.
Domestic current is temporarily lowered below 1 mA after switching
otheloadsothatcontactors,whoseholdingcurrentislowerthan
the constant domestic current of the electronics, are reliably switched
o.
WhenVEGASWING61isusedaspartofanoverllprotectionsystem
according to WHG, also note the regulations of the general type ap-
proval.
12
AC
DC
L1
+
-
N
-
+
Fig. 10: Wiring plan, single chamber housing

17
6 Setup
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
6 Setup
6.1 General information
Theguresinbracketsrefertothefollowingillustrations.
With plastic housings, the switching condition of the electronics can
becheckedwhenthehousingcoverisclosed(controllamp).Withthe
basicsetting,productswithadensity>0.7g/cm³(0.025lbs/in³)can
be detected. For products with lower density, the switch must be set
to>0.5g/cm³(0.018lbs/in³).
Ontheelectronicsmoduleyouwillndthefollowingindicatingand
adjustment elements:
• Signallamp(1)
• DILswitchformodeadjustment-A/B(2)
• DILswitchforsensitivityadjustment(3)
Note:
For test purposes, immerse the tuning fork of VEGASWING 61 always
in liquids. Do not test the function of VEGASWING 61 with your hand.
This can damage the sensor.
6.2 Adjustment elements
12
1
2
3
Fig. 11: Oscillator SWE60C - Contactless electronic switch
1 Signal lamp (LED)
2 DIL switch for mode adjustment
3 DIL switch for sensitivity adjustment
Control lamp for indication of the switching status
• Green = Output closed
• Red = Output open
• red(ashing)=failure
Withthemodeadjustment(A/B)youcanchangetheswitching
condition of the relay.You can set the required mode according to the
Function/Conguration
Signal lamp (1)
Mode adjustment (2)

18
6 Setup
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
"Function chart"(A-max.detectionoroverowprotection,B-min.
detectionordryrunprotection).
WiththisDILswitch(3)youcansettheswitchingpointtoliquids
havingadensitybetween0.5and0.7g/cm³(0.018and0.025lbs/
in³).Withthebasicsetting,liquidswithadensityof>0.7g/cm³(0.025
lbs/in³)canbedetected.Inliquidswithlowerdensity,youmustset
theswitchto>0.5g/cm³(0.018lbs/in³).Thespecicationsforthe
position of the switching point relate to water - density value 1 g/cm³
(0.036lbs/in³).Inproductswithadierentdensity,theswitchingpoint
will shift in the direction of the housing or tuning fork end depending
on the density and type of installation.
Note:
Keepinmindthatfoamswithadensity>0.45g/cm³(0.016lbs/in³)
are detected by the sensor. This can cause faulty switchings particu-
lary when used as dry run protection system.
6.3 Function chart
The following chart provides an overview of the switching conditions
depending on the set mode and the level.
Level Switching status Control lamp
Mode A
Overowprotection
21
Switch closed Green
Mode A
Overowprotection
21
Switch open Red
Mode B
Dry run protection
21
Switch closed Green
Mode B
Dry run protection
21
Switch open Red
Failure of the supply
voltage
(modeA/B)
any
21
Switch open o
Sensitivity adjustment (3)

19
6 Setup
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
Level Switching status Control lamp
Failure any
21
Switch open ashesred

20
7Maintenanceandfaultrectication
VEGASWING 61 • - contactless electronic switch
29223-EN-130409
7 Maintenanceandfaultrectication
7.1 Maintenance
If the instrument is used properly, no special maintenance is required
in normal operation.
7.2 Rectify faults
The operator of the system is responsible for taking suitable meas-
ures to rectify faults.
VEGASWING61oersmaximumreliability.Nevertheless,faultscan
occur during operation.These may be caused by the following, e.g.:
• Sensor
• Process
• Voltage supply
• Signal processing
Therstmeasuretobetakenistochecktheoutputsignal.Inmany
cases,thecausescanbedeterminedthiswayandthefaultsrectied.
Should these measures not be successful, please call in urgent cases
the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is available to you 7 days a week round-the-clock. Since
weoerthisserviceworld-wide,thesupportisonlyavailableinthe
English language.The service is free of charge, only the standard
telephone costs will be charged.
Reaction when malfunc-
tions occur
Failure reasons
Faultrectication
24 hour service hotline
Other manuals for VEGASWING 61
6
Table of contents
Other Vega Switch manuals

Vega
Vega VEGAWAVE 63 User manual

Vega
Vega VEGASWING 51 User manual

Vega
Vega VEGAPOINT 31 User manual

Vega
Vega VEGACAP 65 User manual

Vega
Vega VEGAPOINT 11 User manual

Vega
Vega VEGAWAVE 61 User manual

Vega
Vega VEGASWING 63 User manual

Vega
Vega VEGAVIB 63 User manual

Vega
Vega VEGAWAVE 62 User manual

Vega
Vega VEGASEL 643 User manual

Vega
Vega VEGAWAVE 61 User manual

Vega
Vega VEGAWAVE 63 User manual

Vega
Vega VEGASWING 61 User manual

Vega
Vega VEGASWING 66 User manual

Vega
Vega VEGASWING 51 User manual

Vega
Vega VEGASWING 51 User manual

Vega
Vega VEGAWAVE 62 User manual

Vega
Vega VEGASWING 51 User manual

Vega
Vega EL 4 User manual

Vega
Vega VEGAPOINT 11 User manual