Vents-us MICRA 60 User manual

www.ventsus.com MIU_53(MICRA_60)-02
Bodor Vents, LLC DBA: VENTS-US
11013 Kenwood Road Cincinnati, Ohio 45242
Phone: (513)348-3853
e-mail: [email protected]
SINGLE-ROOM AIR HANDLING UNIT WITH HEAT RECOVERY
MICRA 60
INSTALLATION GUIDE
INSTALLATION
Tools required
Pencil Drill Ø 8 (Ø 5/16''), 40 mm (1 9/16'') Screwdriver Dowel Ø 8 (Ø 5/16''), 40 mm (1 9/16'')
2 pcs.
Screws
5 (1/5''),50 (2)
2 pcs.
MOUNTING
239 (9 7/16")
160 (6 5/16")
503 (19 13/16")
89,5 (3 1/2")160 (6 5/16")
2 holes for the round Ø 125 mm (Ø 5”) duct. Fill
the gaps between the wall and the air duct
with a mounting foam.
drill 2 holes in the wall, 60 mm (2 3/8”)
deep, with a Ø 8 mm (Ø 5/16”) tool.
PAPER MASTER PLATE FOR HOLE MARKING [MM] (INCHES)
The unit is mounted with the master plate from the
delivery set, fig. 1. Please prepare also two air ducts of
required length or one of the mounting sets MICRA 60.
The mounting set MICRA 60 is specially designed for
mounting of the unit at general construction stage. It
includes two plastic air ducts, each 19 13/16'' long and two
master plates for marking the holes on inner and outer wall
sides.
Fig. 1

www.ventsus.com MIU_53(MICRA_60)-02
Bodor Vents, LLC DBA: VENTS-US
11013 Kenwood Road Cincinnati, Ohio 45242
Phone: (513)348-3853
e-mail: [email protected]
10 mm (3/8")
vinkel 3°
Ø130 mm (5 1/8")
vinkel 3°
60 mm (2 3/8")
Ø 8 mm (5/16’’)
Fig. 2
Fig. 4
Fig. 3
Unit mounting sequence:
1. Fix the master plate from the delivery set on the wall with a
sealing tape on required level, fig. 2.
2. Use the master plate to mark two Ø 130 (5 1/8'') mm holes for the air ducts and two Ø 8 (5/16'') mm holes for the dowels.
3. Remove the master plate and drill through holes for the air
ducts and the 60 mm (2 3/8'') deep holes for the dowels. Drill the
holes for the air ducts sloped down by 2-3.Then insert the dowels
(included intro delivery set) intro respective holes.
4. Remove the perforated holes for the air ducts from the master
plate. Re-install it with a sealing tape. If you use either MICRA 60
set, fix the master plate from the mounting set on outer wall side
to align the air ducts with respect to each other. Fix this master
plate somewhat lower to ensure the minimum required slope by
3° to outside.
5. Inset the air ducts into the master plate holes and seal those
with a mounting foam through the provided openings in the
master plate, fig. 4. Install the air ducts sloped down by 2-3°
outside to ensure the condensate drainage.
6. After the mounting foam hardening (see the solidification time
in the product specification) remove the master plates. At the
inner wall cut the protruding parts of the air ducts to be flush with
the wall. On outer wall side, the air ducts must protrude by 10 mm
(3/8'') to prevent condensate dropping on the wall.

www.ventsus.com MIU_53(MICRA_60)-02
Bodor Vents, LLC DBA: VENTS-US
11013 Kenwood Road Cincinnati, Ohio 45242
Phone: (513)348-3853
e-mail: [email protected]
Wall
Outer ventilation hood
Round air duct
sloped down by 2-3°
Fasteners
Micra 60
unit
Round air duct sloped
down by 2-3°
Fig. 6 Fig. 7
Install the ventilation hood MICRA 60 on the outer side of the building to prevent ingress of foreign objects into the air ducts, fig. 7.
Fig. 5
7. Unit installation sequence:
- Open the front panel and remove the heat exchanger.
- Connect the unit spigots to the plastic air ducts.
- Fix the unit to wall with the screws 5,0x50 from the delivery set
by inserting those to the Ø 8 mm (5/16'') holes.
-Install the heat exchanger and close the front panel.
-Install the NB MICRA 60 outer ventilation hood outer of the
building to prevent ingress of large foreign objects into the air
ducts, fig. 5.
Attention! The round plastic air ducts and the outer ventilation hood are not included intro thr delivery set and are available on separate order. You may use other ventilation
grilles and hoods of the matching size.
SPEED SWITCH MOUNTING
MAKE SURE THAT SPEED SWITCH IS NOT DAMAGED. DO NOT OPERATE A DAMAGED SPEED SWITCH! DO NOT INSTALL THE SPEED SWITCH ON AN UNEVEN SURFACE! DO NOT APPLY
EXCESSIVE FORCESWHILE TIGHTENINGTHE SCREWS TO AVOIDTHE SPEED SWITCH CASING DEFORMATION.
- Route all the required cables and wires to the speed switch installation place.
- Insert the junction box from the delivery set inside the wall.

www.ventsus.com MIU_53(MICRA_60)-02
Bodor Vents, LLC DBA: VENTS-US
11013 Kenwood Road Cincinnati, Ohio 45242
Phone: (513)348-3853
e-mail: [email protected]
OUTOUT OUTOUT IN
LL1L2L3L4
1
1
2
3
4
5
PE
L
N
+12V
GND
+12V
+12V GND DIR PWM +12V GND DIR PWM
GND
PE
L
N
+
-
INFLOW_PWM
OUTFLOW_PWM
INFLOW_DIR
5
4
3
2
1
2
2
1
1
GND
NTC
M2
(supply fan)
M1
(exhaust fan)
RT1
t°
NTC_10K
5
4
3
2
1
+
-
iD
iP
0
P
N N
L L
L3
L2
L1
speed
3
speed
2
speed
1
2
3
N
L
PE
N
L
PE
N
L
PE
yellow-green
brown
yellow
green
white
Input voltage: 110-240V
Output current: 1 A
red
blue
yellow
white
red
blue
yellow
white
High
Middle
Low
ContactCircuitSticker
Contact Circuit Sticker
ContactCircuitSticker
Contact Circuit Sticker
P3-1-300 mechanical speed switch mounting:
- Connect the executive element according to the wiring diagram and insert it intro
junction box.
- Fasten the executive element with two screws from the delivery set.
- Cover the executive element of the speed switch with a decorative panel and press the
latches to fix the panel.
CONNECTION TO POWER MAINS
DISCONNECTTHE UNIT FROM POWER MAINS PRIOR TO ANY ELECTRIC INSTALLATION OPERATIONS.
CONNECTTHE UNIT TO A CORRECT INSTALLED SOCKET WITH A GROUNDEDTERMINAL.
ANY INTERNAL CONNECTION MODIFICATIONS ARE NOT ALLOWED AND RESULT IN WARRANTY LOSS.
• The unit is rated for connection to single-phase ac 1~100-240 V/ 50-60 Hz power mains.
• The control unit is installed under the unit protecting panel.
• The unit is connected to the control unit via a 3 m long four-wire cable from the delivery set.
WIRING DIAGRAM FORTHE UNIT WITH P3-1-300 MECHANICAL SPEED SWIITCH
Popular Heating System manuals by other brands

Truma
Truma Trumatic E 2400 E Operating instructions and installation instructions

Aqua-Hot
Aqua-Hot 200 Series installation manual

Vent-Axia
Vent-Axia HR100S Installation and maintenance instructions

aerauliqa
aerauliqa QR350ABP installation manual

WatchGas
WatchGas ATEX BEACON manual

Lampoassa
Lampoassa 203GT user manual