Vents KRDP Series User manual

USER’S MANUAL
KRDP
Fire protection pressure control valve

2
KRDP
www.ventilation-system.com
CONTENTS
This user’s manual is a main operating document intended for technical, maintenance, and operating staff.
The manual contains information about purpose, technical details, operating principle, design, and installation of the KRDP unit and all
its modifications.
Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to
work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.
Safety requirements..................................................................................................................................................................... 2
Purpose................................................................................................................................................................................................ 3
Delivery set........................................................................................................................................................................................ 3
Designation key.............................................................................................................................................................................. 3
Technical data.................................................................................................................................................................................. 3
Unit design and operating principle................................................................................................................................. 5
Installation and set-up................................................................................................................................................................ 5
Technical maintenance.............................................................................................................................................................. 5
Storage and transportation regulations.......................................................................................................................... 5
Manufacturer’s warranty........................................................................................................................................................... 6
Certificate of acceptance.......................................................................................................................................................... 7
Seller information.......................................................................................................................................................................... 7
Installation certificate.................................................................................................................................................................. 7
Warranty card................................................................................................................................................................................... 7
SAFETY REQUIREMENTS
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS
SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE
Follow general and special safety regulations during preparation for operation and operation of the valve.
Only persons who have studied the device and have been instructed in safety regulations are allowed to install and operate the valve.

3
www.ventilation-system.com
PURPOSE
DELIVERY SET
The valve is intended for use in ventilation and air conditioning systems in public and industrial buildings, in emergency smoke ventilation
systems to ensure evacuation of people from premises at the initial stage of a fire.
The valve automatically opens at the required pressure difference (design pressure difference) to allow air to flow freely from the space
where the air is pressurised (e.g. stairwell or elevator shaft) to the space where the pressure is lower (e.g. hall, room).
In case of a fire, the dual action of the design features makes the valve a fire protection valve with a fire resistance rating of EIS 120.
NAME NUMBER
Valve 1 pc.
User’s manual 1 pc.
Packing box 1 pc.
DESIGNATION KEY
TECHNICAL DATA
Pressure control range [Pa] 20–150
Minimum air flow rate [m/s] not less than 2
Operating temperature [˚C] –5...+40
Valve actuation temperature +72 ± 2
Designation example: KRDP 400x400 / 120 F2
Series
Fire protection pressure control valve
Width
200; 250; 300; 350; 400; 450; 500; 550; 600; 650; 700; 750; 800; 850; 900;
950; 1000; 1050; 1100; 1000
Height
200; 250; 300; 350; 400; 450; 500; 550; 600; 650; 700; 750; 800; 850; 900;
950; 1000; 1050; 1100; 1000
Fire resistance rating EI
120
Valve connection type (number of anges)
F1 – one flange (wall type)
F2 – two flanges (air duct type)

4
KRDP
www.ventilation-system.com
Cross-sectional area [m2]
H
А200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
200 0,034 0,044 0,054 0,064 0,074 0,078 0,088 0,098 0,108 0,118 0,128 0,138 0,148 0,152 0,162 0,172 0,182
250 0,0425 0,055 0,0675 0,08 0,0925 0,0975 0,11 0,1225 0,135 0,1475 0,16 0,1725 0,185 0,19 0,2025 0,215 0,2275
300 0,051 0,066 0,081 0,096 0,111 0,117 0,132 0,147 0,162 0,177 0,192 0,207 0,222 0,228 0,243 0,258 0,273
350 0,0595 0,077 0,0945 0,112 0,1295 0,1365 0,154 0,1715 0,189 0,2065 0,224 0,2415 0,259 0,266 0,2835 0,301 0,3185
400 0,068 0,088 0,108 0,128 0,148 0,156 0,176 0,196 0,216 0,236 0,256 0,276 0,296 0,304 0,324 0,344 0,364
450 0,0765 0,099 0,1215 0,144 0,1665 0,1755 0,198 0,2205 0,243 0,2655 0,288 0,3105 0,333 0,342 0,3645 0,387 0,4095
500 0,085 0,11 0,135 0,16 0,185 0,195 0,22 0,245 0,27 0,295 0,32 0,345 0,37 0,38 0,405 0,43 0,455
550 0,0935 0,121 0,1485 0,176 0,2035 0,2145 0,242 0,2695 0,297 0,3245 0,352 0,3795 0,407 0,418 0,4455 0,473 0,5005
600 0,102 0,132 0,162 0,192 0,222 0,234 0,264 0,294 0,324 0,354 0,384 0,414 0,444 0,456 0,486 0,516 0,546
650 0,1105 0,143 0,1755 0,208 0,2405 0,2535 0,286 0,3185 0,351 0,3835 0,416 0,4485 0,481 0,494 0,5265 0,559 0,5915
700 0,119 0,154 0,189 0,224 0,259 0,273 0,308 0,343 0,378 0,413 0,448 0,483 0,518 0,532 0,567 0,602 0,637
750 0,1275 0,165 0,2025 0,24 0,2775 0,2925 0,33 0,3675 0,405 0,4425 0,48 0,5175 0,555 0,57 0,6075 0,645 0,6825
800 0,136 0,176 0,216 0,256 0,296 0,312 0,352 0,392 0,432 0,472 0,512 0,552 0,592 0,608 0,648 0,688 0,728
850 0,1445 0,187 0,2295 0,272 0,3145 0,3315 0,374 0,4165 0,459 0,5015 0,544 0,5865 0,629 0,646 0,6885 0,731 0,7735
900 0,153 0,198 0,243 0,288 0,333 0,351 0,396 0,441 0,486 0,531 0,576 0,621 0,666 0,684 0,729 0,774 0,819
950 0,1615 0,209 0,2565 0,304 0,3515 0,3705 0,418 0,4655 0,513 0,5605 0,608 0,6555 0,703 0,722 0,7695 0,817 0,8645
1000 0,17 0,22 0,27 0,32 0,37 0,39 0,44 0,49 0,54 0,59 0,64 0,69 0,74 0,76 0,81 0,86 0,91
L1 = H/n – 150 — blade overhang size beyond the body dimension (mm), where:
H – height of the valve [mm];
n – number of blades.
Valves with dimensions that are not included in the table can be manufactured on request.
KRDP 120 F1 KRDP 120 F2
200 ≤ H ≤ 500
H + 40
H + 20
H
A + 40
A + 20
A
Ø9 200
L1 200
L1
H + 40
H + 20
H
A + 40
A + 20
A
Ø 9
500 ≤ H ≤ 1000
A + 60
A + 30
A
H + 60
H + 30
H
200
A + 60
A + 30
A
H + 60
H + 30
H
L1
A + 60
A + 30
A
H + 60
H + 30
H
200
L1
200 ≤ H = 400 – 1 blade;
400 < H = 800 – 2 blades;
800 < H – 3 blades.

5
www.ventilation-system.com
TECHNICAL MAINTENANCE
Maintenance of the valve involves checking its serviceability: free (without jamming) rotation of the flaps; reliability of installation. The
valve maintenance intervals should correspond to the established maintenance periods for the fire protection equipment complex of
the operated facility.
The fusible link triggering mechanism is restored by replacing the fusible link (in the absence of fire impact).
STORAGE AND TRANSPORTATION REGULATIONS
• Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
• Follow the handling requirements applicable for the particular type of cargo.
• The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and
mechanical damage. Avoid sharp blows, scratches, or rough handling during loading and unloading.
INSTALLATION AND SETUP
The valve is installed in ventilation ducts or in intersections of enclosing structures and closes in the event of a fire.
Valve’s position in the valve space is vertical (air flow is horizontal).
Visually inspect the valve before installing it.
Repair any damage or dents caused by improper transportation or storage.
The valves should be configured to the required working pressure after their installation during the adjustment (commissioning) of the
pressure generation ventilation system.
UNIT DESIGN AND OPERATING PRINCIPLE
The valve consists of a rectangular galvanized steel mounting casing (1). Inside the casing there is one or more flaps made of heat-
resistant material (2) of rotary type, a spring mechanism (3) for adjusting the valve opening start. The adjustment is performed during
commissioning.
In case of a fire, the valve design ensures that the blade is automatically locked at the stops by melting the fusible link (4). The valve’s
tightness in case of fire is ensured by a tape that is fixed around the perimeter of the blade and expands at high temperatures.
2
1
3
1
2
3
4

6
KRDP
www.ventilation-system.com
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND
TROUBLEFREE OPERATION OF THE UNIT
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION
OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE
PURCHASE DATE STAMP
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby
declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European
Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking
Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user's observance
of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation
through the Manufacturer's fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the
manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults
in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means
of replacement or repair of the unit components or a specific part of such unit component.
The warranty repair does not include:
• routine technical maintenance
• unit installation/dismantling
• unit setup
To benefit from warranty repair, the user must provide the unit, the user's manual with the purchase date stamp, and the payment
paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty
service.
The manufacturer’s warranty does not apply to the following cases:
• User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing
component parts previously dismounted by the user.
• Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user's manual.
• User’s failure to ensure timely technical maintenance of the unit.
• External damage to the unit casing (excluding external modifications as required for installation) and internal components caused
by the user.
• Redesign or engineering changes to the unit.
• Replacement and use of any assemblies, parts and components not approved by the manufacturer.
• Unit misuse.
• Violation of the unit installation regulations by the user.
• Violation of the unit control regulations by the user.
• Unit connection to power mains with a voltage different from the one stated in the user's manual.
• Unit breakdown due to voltage surges in power mains.
• Discretionary repair of the unit by the user.
• Unit repair by any persons without the manufacturer’s authorization.
• Expiration of the unit warranty period.
• Violation of the unit transportation regulations by the user.
• Violation of the unit storage regulations by the user.
• Wrongful actions against the unit committed by third parties.
• Unit breakdown due to circumstances of insuperable force (flood, earthquake, war, hostilities of any kind, blockades).
• Missing seals if provided by the user’s manual.
• Failure to submit the user’s manual with the unit purchase date stamp.
• Missing payment paperwork certifying the unit purchase.

7
www.ventilation-system.com
CERTIFICATE OF ACCEPTANCE
Unit Type Fire protection pressure control valve
Model
Serial Number
Manufacture Date
Quality Inspector’s
Stamp
SELLER INFORMATION
Seller
Seller’s Stamp
Address
Phone Number
E-mail
Purchase Date
This is to certify acceptance of the complete unit delivery with the user’s manual. The warranty terms are
acknowledged and accepted.
Customer’s Signature
INSTALLATION CERTIFICATE
The _____________________________________ unit is installed pursuant to the requirements stated
in the present user's manual.
Installation Stamp
Company name
Address
Phone Number
Installation
Technician’s Full Name
Installation Date: Signature:
The unit has been installed in accordance with the provisions of all the applicable local and national construction,
electrical and technical codes and standards. The unit operates normally as intended by the manufacturer.
Signature:
WARRANTY CARD
Unit Type Fire protection pressure control valve
Seller’s Stamp
Model
Serial Number
Manufacture Date
Purchase Date
Warranty Period
Seller

V243-1EN-01
This manual suits for next models
2
Table of contents
Other Vents Control Unit manuals
Popular Control Unit manuals by other brands

Wistron NeWeb
Wistron NeWeb DNUR-W1 user manual

Viessmann
Viessmann 5222 Operation manual

Hansen
Hansen PXV Series Specifications, Applications, Service Instructions & Parts

Domino
Domino XM2 Directions for the use

KIESELMANN
KIESELMANN 406 Series Operating instruction

Aeroflex
Aeroflex 3010 Series operating manual

Festo
Festo SPC200-MMI-DIAG Brief description

Siko
Siko AS510/1 User information

QuantAsylum
QuantAsylum QA450 user manual

Freescale Semiconductor
Freescale Semiconductor MC33696MOD Series Quick start user guide

Telit Wireless Solutions
Telit Wireless Solutions GC864-QUAD V2 Hardware user's guide

CALEFFI
CALEFFI Z-one ZVR10 Series manual