
LuminaireInstallaon
1. Open shell referring to diagram overleaf.
2. Pass luminaire power cable through strain relief
gland and connect to top power terminal.
3. Connect baery to PCB header.
4. Snap pod casing onto hanger.
5. Light source can be mounted on compable Venture luminaire or
reflector with supplied brackets.
PowerIn
ToLuminaire
ReflectorMounng LuminaireMounng
Self‐Test
During self –test the light source will illuminate and the red indi‐
cator LED will flash connuously. On compleon the pod returns
to normal operaon.
Schedule
Every month ‐ 10 minute self‐test.
Annually ‐ 3 hours self‐test.
LEDStatusIndicator
Green Normal operaon
Single red flash Baery failure or not connected
Double red flash Light source failure
Triple red flash 3Hr self test failed. Baery at end of life
DocumentRevision2 09/08/2019
Switched Live (Black)
Live (Brown)
Neutral (Blue)
(Green/Yellow)
Switched Live
Neutral
ManualTest
Aer installaon emergency func‐
on can be checked by pressing
the test buon for 3 seconds. The
light will illuminate for 5 minutes
before resuming normal operaon.
TimerReset
Monthly and annual mers can be
reset by pressing the test buon
for 1s.